EATON BiWire Flexi Installation Manual (PR215-216-520-03 15-03-16, PINSTFLEXIINST)
March 2016 www.eaton.com
30
Operating Instructions
6.9 Self-test Mode
• This function is only available at access level 3.
• Enter the access code 2321.
• Press the “Test” button (2).
• The Test indicator will slow flash and the buzzer will give a
slow pulsing tone.
• The fire indicator on every detector head will turn on.
• This function is useful for checking that each head is fitted
correctly as the fire indicator will not turn on.
• To end the self-test mode, enter the access code 2321
and press button 2.
6.10 Walk Test Mode
• This function is only available at access level 3.
• Enter the access code 2321
• Press “Indicator Test” button (3).
• The Test indicator will turn on and the buzzer will give a
slow pulsing tone.
• This function places all zones in test mode and is used
during commissioning to test every fire detection device
on a zone.
• Repeat the following for each zone (with fire detection
devices) in turn:
• Activate the fire detection device or manual call point on
the
zone.
• All fire alarm devices will sound on all zones for 3
seconds and then will automatically silence.
• The fire panel will then reset the zone from the fire
condition.
• Repeat the above process until all fire detection device
and manual call points on the zone have been tested.
• To end the walk test mode enter the access code 3112 or
2321 and press the “Reset” button.
• If no fire detection device or manual call point is triggered
within 10 minutes of the walk test being started, the test
mode will timeout and return back to access level 1/normal
condition.