Eaton BiWire Flexi Installation Manual Download Page 13

EATON BiWire Flexi Installation Manual  (PR215-216-520-03 15-03-16, PINSTFLEXIINST)                 

March 2016   www.eaton.com 

13

The BiWire Flexi Fire Detection & Alarm System

Detector Zone Inputs

Each zone is configured by default to BiWire mode and is 
provided with an EOLM-3 fitted inside panel.

For zones that need to be in BiWire mode the EOLM-3 must 
be removed from the panel and fitted to the last device on 
each zone (Figure 7). Any unused BiWire zones must be 
terminated inside the panel by the EOLM-3 otherwise the 
zone will go into fault condition.

For zones that need to be in Standard Conventional mode 
then for new installs the EOLM-3 must be removed from the 
panel and fitted to the last device on each zone (Figure 7), for 
retro-fit installs that already has an EOLM-1 fitted at the end 
of the zone then the EOLM-3 needs to be removed from the 
panel and not used, for retro-fit installs without an EOLM-1 
then the EOLM-3 must be removed from the panel and used 
to replace the termination in the last device on the zone. Any 
unused standard conventional zone must be terminated with 
either an EOLM-3 or EOLM-1.

For zones to be configured in Intrinsically Safe Conventional 
mode the EOLM-3 must be removed and replaced by a 5K1 
resistor (not supplied) and fitted in the last device at the 
end of zone after the intrinsically safe barrier. Any unused 
intrinsically safe zone must be terminated by the 5K1 end-
of-line resistor.

It is recommended that any zone that is not in use should 
remain in the factory default configuration of BiWire mode 
with the EOLM-3 fitted in the panel.

Conventional Sounder Circuits

For 2 and 4 zone panels the following sounder circuit rules 
apply:

• All Zones in BiWire Mode = 2 Sounder Outputs Available

• Half Zones in BiWire and Half in Conventional Mode = 2 
Sounder Outputs Available

For 8 zone panels the following sounder circuits apply:

• 

8 BiWire Zones = 0 Sounder Outputs Available

• 

1-4 Conventional Zones = 2 Sounder Outputs Available

• 

5-8 Conventional Zones = 4 Sounder Outputs Available

Each sounder circuit must be terminated by a 6K8 resistor 
whether the alarm devices are standard or intrinsically safe 
in order for the panel to detect Short and Open circuit faults. 
Even if the conventional sounder circuits are not in use they 
must be terminated by the 6K8 resistors inside the panel.

Figure 13: Repeater Panel Connection

Repeater I/O

Each repeater has its own mains supply and standby battery. 
The repeater output is designed to connect to another 
panel configured as a repeater using the RS485 protocol. 
The repeater would follow the indication of the main Panel 
showing faults, fires and disablements (Figure 13).

2.9 Option Board (FRE/FPE/Zonal Relays)

The options board is an additional daughter card that 
provides outputs to Fire Protection Equipment (FPE), Fire 
Alarm Routing Equipment (FRE) and Zonal Relays.

Fire Alarm Routing Equipment (FRE)

The FRE output is designed to activate during a fire  
event and is connected to phone diallers and/or Building 
Management Systems. When the FRE option board is fitted 
SW12-1 dip switch is set to Fitted. See figure 6. The output 
complies with EN54-2 clause:

•  Outputs to fire alarm routing equipment (option with  
 requirements)

Fire Protection Equipment (FPE)

The FPE output is designed to activate during a fire event 
and when connected to external devices drive door release 
mechanisms, fire screens, sprinkler systems, and gas 
release systems. When FPE option board is fitted SW12-1 
dip switch is set to Fitted. The output complies with EN54-2 
clause:

•  7 .10.1 Outputs to fire protection equipment (Type A)

Zonal Relay Contacts

Zonal relay contacts are volt free and do not provide any  
voltage. The relays are selectable to be either set to C/NO  
or C/NC. The zonal relays are designed to follow the fire  
condition of the associated zone circuit on the Main board.

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for BiWire Flexi

Page 1: ...BiWire Flexi BiWire Flexi Fire Panel EFBW8ZONE FLEXI EFBW4ZONE FLEXI EFBW2ZONEFLEXI Installation Manual www acornfiresecurity com www acornfiresecurity com...

Page 2: ...E 12 Fire Protection Equipment FPE 12 Zonal Relay Contacts 12 3 INSTALLATION INSTRUCTIONS 13 3 1 Before You Begin 13 3 2 Cabling Routing Device Installation 13 3 3 Panel Installation 14 Mounting the P...

Page 3: ...tion Buttons 26 6 2 Silence Fire Alarm Devices 26 6 3 Sound Fire Alarm Devices 26 6 4 Reset System 26 6 5 Mute Buzzer 27 6 6 Enable Disable 27 6 7 Individual Zone Test 28 6 8 Lamp Test 28 6 9 Self Tes...

Page 4: ...m The installation of this system can only be carried out by a competent person with relevant current training and experience with access to requisite tools equipment and information as stipulated by...

Page 5: ...ectors and manual call points and 20 output devices connected via a single 2 core screened cable The Fire Panel is available to support 4 conventional sounder circuits see technical specification for...

Page 6: ...r the zone mode setting A maximum of 32 inputs devices detectors and or manual call points and 20 output devices is possible as one BiWire configuration example a loading calculator is available to as...

Page 7: ...cation of power supply Further technical data for the PSE can be found in section 7 2 Note that the charging circuit will be in its high impedance state approximately 3V DC if no batteries faulty batt...

Page 8: ...e must have the intelligent end of line module EOLM 1 fitted to continually monitor each zone for the presence of fault conditions such as detector head removal open or short circuit and for end of li...

Page 9: ...call points devices are wired into the barrier with a 5K1 EOLR embedded in the last device Standard conventional and BiWire detection and alarm devices cannot be wired onto an intrinsically safe conv...

Page 10: ...W Battery impedance fault Charger Fault ON ON ON SLOW Charger voltage fault Sounder Fault ON ON SLOW SLOW Short or Open circuit condition on the sounder circuit FRE Fault ON ON SLOW SLOW Short or Open...

Page 11: ...perated by an external volt free contact A short circuit at this terminal will activate non latching sounders no indication will show on the fire alarm panel The sounders will automatically silence wh...

Page 12: ...terlink Relay in conjunction with a non latching zone can be used to link two BiWire Flexi fire panels together Figure 12 or to link a BiWire Flexi to a BiWire Ultra panel It is recommended to use a n...

Page 13: ...g sounder circuits apply 8 BiWire Zones 0 Sounder Outputs Available 1 4 Conventional Zones 2 Sounder Outputs Available 5 8 Conventional Zones 4 Sounder Outputs Available Each sounder circuit must be t...

Page 14: ...MPT TO INSTALL THIS EQUIPMENT UNTIL YOU HAVE FULLY READ AND UNDERSTOOD THE OPERATION AS DESCRIBED WITHIN THIS MANUAL FAILURE TO DO SO MAY RESULT IN DAMAGE TO THE EQUIPMENT AND COULD INVALIDATE YOUR WA...

Page 15: ...LLY ON THE PERIMETER OF A BUILDING NEAR A PERMANENT ENTRANCE Mounting the Panel To remove the front cover of the panel unscrew the two retraining screws located at the top corners of the panel see Fig...

Page 16: ...Fit the glands to the back box and pull through the required cables Using the mounting holes in the back box drill holes into the wall and insert wall plugs and secure the panel to the wall as shown i...

Page 17: ...igure 16 OBEY VOLT DROP LIMITATION WHEN SIZING CABLES USE ONLY APPROVED CABLE TYPES DO NOT TIGHTEN TERMINAL CONNECTOR SCREWS TOO TIGHT KEEP POLARITY THROUGHOUT NON COLOURED CONDUCTORS SHOULD BE PERMAN...

Page 18: ...NOTE Figure 22 Panel Wiring Diagram Battery Connections Figure 21 Battery Connection CAUTION IT IS IMPORTANT THAT ZONE CABLING IS CONNECTED TO THE CORRECT ZONE INPUT OTHERWISE ANY FIRE OR FAULT INDICA...

Page 19: ...IWIRE FLEXI PANEL BEFORE POWERING UP THE SYSTEM Connecting a Repeater Panel Connect the cables from the repeater panel to the Repeater terminals on the main board of the fire alarm panel observing the...

Page 20: ...d not at the option board terminals IF EITHER THE FRE OR FPE IS NOT BEING USED THEN THE 6K8 RESISTOR SHOULD BE FITTED AT THE APPROPRIATE TERMINAL ON THE OPTION BOARD THIS PREVENTS ERRONEOUS FAULTS CON...

Page 21: ...d regardless of any new fire conditions detected 3 6 Zone Configuration Figure 27 Silence Mode Setting Zone BiWire Mode Standard Conventional IS Conventional 1 SW3 1 N A SW3 1 OFF SW3 1 ON SW5 1 ON SW...

Page 22: ...ode then care must be taken that before any zone is re enabled that a walk round of the zone is carried out to check that all detectors and manual call points are not latched in the fire condition If...

Page 23: ...r to C NC Connect the detector back on its base then check the following General fault indicator amber is off Zone fault disable indicator amber is off Fault relay has switched back to C NO Press butt...

Page 24: ...ins fault The panel should not lose power during the following test Activate a call point in any zone Check the following on the panel General fire indicator red is on Correct zone fire indicator red...

Page 25: ...d in accordance to BS5839 part 1 Annex H The commissioning certificate must be completed and any variances noted The system configuration and variances should be recorded on the log book 4 2 System Ha...

Page 26: ...ires specialist equipment and may not be possible for all premises At a minimum a different manual call point should be tested each week Place the zone to be tested into test mode using the Individual...

Page 27: ...und Alarms button Only the fire alarm devices will stop sounding the panel buzzer will continue sounding This function will immediately exit back to Access Level 1 6 3 Sound Fire Alarm Devices This fu...

Page 28: ...equipment attached to the fire alarm system This function will allow the following to be disabled Individual Zones All fire alarm devices FRE if fitted FPE if fitted Enter the access code 3112 Press...

Page 29: ...Test indicator will remain lit and the zone disabled indicator will also remain lit When a fire detection device or manual call point is activated in the zone under test it will sound all fire alarm...

Page 30: ...ll turn on and the buzzer will give a slow pulsing tone This function places all zones in test mode and is used during commissioning to test every fire detection device on a zone Repeat the following...

Page 31: ...onal Zones EOLM 1 Only Intrinsically Safe Zones 6K8 resistor CONVENTIONAL SOUNDER CIRCUITS Number of Sounder Circuits 4 Maximum Loading Per Circuit 500mA Fuse Protection Per Circuit 500mA PTC End of L...

Page 32: ...85 the scope of EN54 certification Nodes 1 ENVIRONMENTAL Operating temperature 5 C to 40 C Relative Humidity 93 3 non condensing IP Rating IP30 MECHANICAL Dimensions 375mm Wide x 366mm Tall x 134mm De...

Page 33: ...7V Maximum ripple voltage 425mVrms 1 2Vp p Imin 39mA Imax A 2 1A Imax B 2 6A Ri max 1 PSE FAULT OPTIONS MAINS OK J4 pin4 3V Mains present 3V Mains fault FAULT_CHARGER J4 pin1 3V for 1s pulsed at 0 2H...

Page 34: ...9 1 2013 6 8 9 and BS5266 1 Technical Specifications 7 5 Option Board Specification BiWire Flexi Fire Panel EFBW2ZONE FLEXI EFBW4ZONE FLEXI EFBW8ZONE FLEXI Operating Voltage 18 75 30 7V Rating 24V 50m...

Page 35: ...tional Reliability Pass Electrical Stability Durability Of Operational Reliability Pass Humidity Resistance 0359 Eaton Industries Manufacturing GmbH Electrical Sector EMEA Route de la Longeraie 7 1110...

Page 36: ...2016 Eaton All Rights Reserved Printed in UK March 2016 Eaton is a registered trademark All other trademarks are property of their respective owners www acornfiresecurity com www acornfiresecurity com...

Reviews: