3.8 Installation Testing
Initial Power-up Check
Power up the panel by engaging the fuse spur to supply
mains, then connect the white socket of the battery cable to
the power supply (see Figure 22).
Check that all indicators turn on in turn momentarily and turn
off again.
Only the power on indicator should be lit afterwards.
Any fault indications should be investigated and corrective
actions taken before continuing with the installation tests
(see section 2.7 for fault indications). All corrective actions
should be undertaken with the panel powered off.
If there are detectors or manual call points showing the fire
condition then the panel should be reset to clear the fire con-
dition before the zone is re-enabled. Check that the following
outputs are in the correct state:
•
Auxillary Output (30V)
•
Fire Relay (C/NC)
•
Fault Relay (C/NO)
•
Interlink Relay (C/NC)
•
FRE (0V, if fitted)
•
FPE (0V, if fitted)
Installation Instructions
WARNING
Zone Fault Detection Check
Repeat the following per zone:
• Disconnect the last detector head on the zone then
check the following
General fault indicator (amber) is on.
Correct zone fault/disable indicator (amber) is fast
flashing for detector removed fault.
Fault relay has switched over to C/NC.
Connect the detector back on its base then check the
following
General fault indicator (amber) is off.
Zone fault/disable indicator (amber) is off.
Fault relay has switched back to C/NO.
Press button 5 “Mute Buzzer” to silence the panel
buzzer.
Battery Fault Detection Check
Disconnect the battery.
After about 20 seconds check the following:
• General fault indicator (amber) is on.
• Battery/Mains fault indicator (amber) is flashing for
battery
fault.
• Battery/Charger fault indicator (amber) is on for charger
fault.
Connect the battery.
After about 4 seconds check the following:
• General fault indicator is off.
• Battery/Mains fault indicator is off.
• Battery/Charger fault indicator is off.
Press button 5 “Mute Buzzer” to silence the panel buzzer.
Zone Fire Detection Check
Repeat the following per zone:
• Place the individual zone into Zone Test mode (see
section
6.7).
• Activate a manual call point (or a detector if there is no
call point on the zone) in that zone and then check the
following:
General fire indicator (red) is on.
Correct zone fire indicator (red) is on.
All fire alarm devices are sounding.
• After approximately 3 seconds the system will
automatically silence and the fire indication will clear.
• Take the zone out of Zone Test mode (see section 6.7).
Reset the system to clear all fire indications.
DO NOT FIX ANY FAULT CONDITIONS WITH THE SYSTEM
STILL POWERED UP, THIS IS PARTICULARY IMPORTANT
WITH SHORT CIRCUIT FAULTS ON ZONES AS THE PTC
FUSE NEEDS TIME TO RECOVER.