Installation Instructions
3.3 Panel Installation
THE FOLLOWING INSTRUCTIONS MUST BE FOLLOWED
WITH MAINS AND BATTERY SUPPLIES DISCONNECTED
UNLESS OTHERWISE STATED.
THE PANEL SHOULD BE INSTALLED IN A CLEAN, DRY,
REASONABLY WELL VENTILATED PLACE, AND NOT IN
DIRECT SUNLIGHT. TEMPERATURES IN EXCESS OF 40°C
AND BELOW 5°C MAY CAUSE PROBLEMS, IF IN DOUBT
CONSULT EATON FIRE SYSTEMS. THE PANEL SHOULD
BE LOCATED AWAY FROM ANY POTENTIAL HAZARD,
IN A POSITION WHERE IT IS READILY ACCESSIBLE TO
AUTHORISED STAFF, AND THE FIRESERVICES, IDEALLY
ON THE PERIMETER OF A BUILDING NEAR A PERMANENT
ENTRANCE
Mounting the Panel
•
To remove the front cover of the panel, unscrew the
two retraining screws located at the top corners of the
panel, see Figure 13.
•
It is recommended to remove the PCB shelf and the
PSE from the back box before drilling the holes.
•
To remove the PCB shelf push the clips down (1), then
push the shelf towards the top of the back box and then
lift forwards (2), see Figure 14.
•
To remove the PSE PCB from the back box unplug the
cables from the main board as shown in Figure 15, then
simply remove the screw and push the PCB up, to the
right and forwards as shown in Figure 16.
Figure 13: Removing the Front Cover
Figure 14: Removing the PCB Shelf
NOTE
NOTE
Figure 15: Disconnecting the PSE
Figure 16: Removing the PSE