UPS Installation Plan and Unpacking
Eaton 93PM UPS (20–50 kW, 480V Four Wire – 50 kW Frame) Installation and Operation Manual P-164000540—Rev 4
www.eaton.com/powerquality
3-3
The UPS equipment operating environment must meet the weight requirements shown in Table 3-2 and the
size requirements shown in Figure 3-1 through Figure 3-8. Dimensions are in millimeters (inches).
The UPS cabinet uses forced air cooling to regulate internal component temperature. Air inlets are in the front
of the cabinet and outlets are on top or in the back of the cabinet. Allow clearance in front of and on top or in
back of the cabinet for proper air circulation. The clearances required around the UPS cabinet are shown in
Table 3-3.
NOTE
Refer to the
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass Installation
and Operation (50 kW and 100 kW SIAC-B) Manual
, listed in paragraph 1.8, for
Sidecar Integrated Accessory Cabinet-Bypass (SIAC-B) size requirements.
Table 3-2. UPS Cabinet Weights
Model
Internal
Battery Strings
Weight
kg (lb)
Frame
Shipping
Installed
Point Loading
Eaton 93PM-50-1
0
Capacity
338 (745)
318 (702)
4 at 80 (176)
3
Capacity
781 (1721)
761 (1678)
4 at 190 (420)
4
Capacity
885 (1952)
865 (1909)
4 at 216 (477)
0
Redundant
354 (780)
334 (737)
4 at 84 (184)
Eaton 93PM-50-2
0
Redundant
441 (972)
421 (929)
4 at 105 (232)
Eaton 93PM-50-1 with UPS Top Entry Wiring Sidecar (no breakers)
0
Capacity
425 (937)
402 (887)
4 at 101 (222)
3
Capacity
844 (1862)
821 (1812)
4 at 205 (453)
4
Capacity
949 (2093)
926 (2043)
4 at 232 (511)
0
Redundant
441 (972)
418 (922)
4 at 105 (231)
Eaton 93PM-50-2 with UPS Top Entry Wiring Sidecar (no breakers)
0
Redundant
505 (1113)
482 (1063)
4 at 121 (266)
Table 3-3. UPS Cabinet Clearances
From Front of Cabinet
914.4 mm (36") working space
From Top of Cabinet with Top Exhaust (Zones 1 and 3 – see Figure 3-2 )
457.2 mm (18") minimum clearance for ventilation
From Top of Cabinet (Zones 2 and 3– see Figure 3-2 )
457.2 mm (18") working space
From Top of Cabinet with rear service access (Zone 2– see Figure 3-2)
Can be less than 457.2 mm (18")
From Back of Cabinet with Rear Exhaust
254 mm (10") minimum clearance for ventilation
From Back of Cabinet with Top Exhaust
None Required
From Back of Cabinet – Seismic Installation
914.4 mm (36") working space
From Right Side of Cabinet
None Required
From Left Side of Cabinet
None Required
Summary of Contents for 93PM UPS
Page 1: ...Eaton 93PM UPS 20 50 kW 480V Four Wire 50 kW Frame Installation and Operation Manual...
Page 2: ......
Page 3: ...Eaton 93PM UPS 20 50 kW 480V Four Wire 50 kW Frame Installation and Operation Manual...
Page 25: ...Section 1 Installation...
Page 26: ......
Page 87: ...Section 2 Operation...
Page 88: ......
Page 145: ......
Page 146: ...P 164000540 4 P 164000540 4...