UPS Operating Instructions
6-30
Eaton 93PM UPS (20–50 kW, 480V Four Wire – 50 kW Frame) Installation and Operation Manual P-164000540—Rev 4
www.eaton.com/powerquality
6.4.11 Single UPM Restart
To restart a single UPM from a shutdown state:
1.
Tap the
CONTROLS
tab on the main menu navigation bar. The System Control screen is displayed.
2.
Tap the
MODULES CONTROLS
tab on the secondary Control menu navigation bar. The UPM Select
screen is displayed.
3.
On the UPM Select screen, select the UPM to start. The UPM Control Screen is displayed.
4.
Tap the
START MODULE
button.
The UPM rectifier and inverter turn on. When the inverter reaches full voltage, the UPS is ready to transfer
to the Double Conversion mode and supply the critical load.
6.4.12 Single UPS Shutdown
To Shutdown a single UPS:
To shut down a single UPS:
1.
Open the MOB for the UPS being shut down.
2.
On the UPS being shut down, tap the
CONTROLS
tab on the main menu navigation bar. The System
Control screen is displayed.
3.
Tap the
GO TO BYPASS
button.
The UPS being shut down transfers to Bypass mode. The
BYPASS
status indicator is illuminated. The
power module remains on.
4.
Tap the
CONTROLS
tab on the main menu navigation bar. The System Control screen is displayed.
5.
Tap the
MODULES CONTROLS
tab on the secondary Control menu navigation bar. The UPM Select
screen is displayed.
6.
On the UPM Select screen, select UPM 1. The UPM Control Screen is displayed.
7.
Tap the
SHUT DOWN MODULE
button.
The UPM status indicates SHUTDOWN. The input, output, and battery switchgear open, and the power
module is turned off.
Logic power remains on.
8.
Repeat Steps 4 through 7 selecting UPM 2 to shut down UPM 2.
The UPM status indicates SHUTDOWN. The input, output, and battery switchgear open, and the power
module is turned off.
Logic power remains on.
WARNING
Power is present inside the UPS cabinet until the upstream input feeder circuit breakers and
battery breakers are opened.
NOTE
To shut down a single UPS, MOBs with dual auxiliary contacts must be installed
and connected according to the procedure in paragraph 4.7.6.
Summary of Contents for 93PM UPS
Page 1: ...Eaton 93PM UPS 20 50 kW 480V Four Wire 50 kW Frame Installation and Operation Manual...
Page 2: ......
Page 3: ...Eaton 93PM UPS 20 50 kW 480V Four Wire 50 kW Frame Installation and Operation Manual...
Page 25: ...Section 1 Installation...
Page 26: ......
Page 87: ...Section 2 Operation...
Page 88: ......
Page 145: ......
Page 146: ...P 164000540 4 P 164000540 4...