Transfer from Double Conversion to Bypass Mode
To transfer the critical load to Bypass mode:
CAUTION
In Bypass mode, the critical load is not protected from commercial power interruptions and
abnormalities.
1.
Tap the
CONTROLS
tab on the main menu navigation bar. The System Control screen is displayed.
2.
Tap the
GO TO BYPASS
button.
All of the UPSs transfer to Bypass mode. and the critical load is immediately supplied by the bypass
source. If the bypass source is not available, the power module remains on and an alarm sounds.
The
BYPASS
status indicator is illuminated. The power module remains on.
WARNING
Power is present inside the UPS cabinet.
6.4.6
Transfer from Bypass to Double Conversion Mode
To transfer the critical load to Normal mode:
1.
Tap the
CONTROLS
tab on the main menu navigation bar. The System Control screen is displayed.
2.
Tap the
GO ONLINE
button.
All of the UPSs transfer to Double Conversion mode. If the power module is not available, the system
remains on bypass and an alarm sounds.
The
NORMAL
status indicator is illuminated.
6.4.7
Transfer from ESS Mode to Double Conversion Mode
To transfer the load to Standard Normal mode:
1.
Tap the
CONTROLS
tab on the main menu navigation bar. The Control screen is displayed.
2.
Tap the
EAA CONTROLS
tab on the secondary Control menu navigation bar. The
EAA CONTROLS
screen is displayed.
3.
Tap the
DISABLE ESS
button.
All of the UPSs transfer to Double Conversion mode.
The
NORMAL
status indicator is illuminated.
Summary of Contents for 93PM UPS
Page 1: ...Eaton 93PM UPS 20 50 kW 480V Four Wire 50 kW Frame Installation and Operation Manual...
Page 2: ......
Page 3: ...Eaton 93PM UPS 20 50 kW 480V Four Wire 50 kW Frame Installation and Operation Manual...
Page 25: ...Section 1 Installation...
Page 26: ......
Page 87: ...Section 2 Operation...
Page 88: ......
Page 145: ......
Page 146: ...P 164000540 4 P 164000540 4...