9.
Do the transfer from the bypass mode to the double conversion mode:
a.
In the home screen, press
Controls
.
b.
Select UPS controls (Single UPS) or System controls (UPS system).
c.
Press
Go online
button. Confirm your selection.
The UPS is now in the double conversion mode.
Figure 42: Normal positions of the switches
A
Bypass input
1
Bypass input switch (BIS)
B
Rectifier input
2
Maintenance bypass switch
(MBS)
C
UPS output
© Eaton Corporation plc 2020. All rights reserved.
Revision: 001
Document ID: P-164000956
109
(141)
Eaton 93PM G2 UPS 50 – 360 kVA
User’s and Installation Guide