Eaton 9395XC UPS 1200kW/1200kVA, 1350kW/1350kVA or 1500kW/1500kVA 164001079—Rev 01
55..11
IInnssttaalllliinngg D
Diissttrriibbuutteedd B
Byyppaassss C
Coonnttrrooll W
Wiirriinngg
NOTE
When installing interface wiring for the CAN and pull chain, conduits must be installed
between UPSs.
Interface control terminals are located on the right side of the Minislot communication bay (see
Figure 42. External Interface Terminals Detail
RS485
(not used)
}
1
2
3
1
2
3
4
1
2
3
4
5
6
7
8
9
10
1
2
3
4
1
2
J6 (Port 2)
J76 (Port 1)
J77 (Port 3)
CN13
CN15
CN5
J90
J19
Minislot Communication Bay
To install distributed bypass control wiring:
1.
Verify the UPS system is turned off and all power sources are removed. See
for shutdown instructions.
2.
For each installed UPS:
a.
If not already opened, open the front door and swing the door open (see
b.
Remove an Interface Entry Conduit Landing panel to drill or punch holes (see
c.
Reinstall the conduit landing panel and install the conduit.
Summary of Contents for 9395XC
Page 8: ......
Page 160: ...16400107901 164001079 01 ...