Eaton 9395XC UPS 1200kW/1200kVA, 1350kW/1350kVA or 1500kW/1500kVA 164001079—Rev 01
5
provides connectivity and operational mode control. The distributed bypass system consists of two to five
UPSs each with a parallel CAN card, and a customer-supplied tie cabinet or load distribution panel to act as a tie
point.
The tie cabinet is provided by the customer and must contain Module Output Breakers (MOBs) with dual
auxiliary contacts for control of the system.
11..22..55
C
Coonnttiinnuuoouuss S
Sttaattiicc S
Sw
wiittcchh
A continuous static switch is used to provide transfer of the load from the inverter to the bypass source in the
event the inverter become unavailable.
11..22..66
M
Moonniittoorriinngg aanndd C
Coom
mm
muunniiccaattiioonn
•
Minislot Cards
– Optional Minislot cards support several protocols, such as SNMP, SMTP, HTTP,
Modbus
®
, and TCP/IP. See Chapter 7 Communication, for additional information on monitoring and
communication features.
•
Remote Monitoring Device (RMD)
– An optional RMD contains a touch screen status display and a local
audible alarm, allowing monitoring of the operational status and alarm condition of the UPS from virtually
any location within the facility, up to 300 feet from the UPS. Refer to the Eaton Remote Monitoring Device
(RMD) Installation and Operation Manual, listed in paragraph
for additional
information.
•
PredictPulse™ Remote Monitoring and Management Service
– PredictPulse is a subscription
monitoring and management service from Eaton that collects and analyzes data from connected power
infrastructure devices, providing us with the insight needed to make recommendations and take action on
your behalf. It’s also powered by CA Technologies, bringing together the best in hardware and software.
Like a second set of eyes on your power infrastructure, PredictPulse provides 24/7 remote monitoring of
alarms and system performance (load, temperature/humidity, battery health, energy savings and service
level) to reduce downtime risk and expedite repairs. PredictPulse also shares real-time status and trend
information via an online dashboard and smartphone mobile app (Apple and Android), giving subscribers
insights about past and current performance, a list of all active alarms, and asset management data (i.e.,
battery date codes, last and next scheduled service dates, firmware versions). The service notifies
customers of critical alarms, supports remote diagnostics, and facilitates smart dispatch of technicians.
PredictPulse requires a Power Xpert
®
Gateway Minislot Card (PXGMS) connectivity card in a Minislot
communication bay and an Environmental Monitoring Probe (EMP) for battery temperature/humidity
monitoring.
See
for additional information on monitoring and communication features.
11..33
B
Baatttteerryy S
Syysstteem
m
Although not provided with the UPS, a battery system is required to provide emergency short-term backup
power to safeguard operation during brownouts, blackouts, and other power interruptions. The battery system
should be equipped with lead-acid or lithium-ion batteries. An external battery disconnect switch must be used.
UPSs in distributed bypass and parallel systems must use a separate battery system.
See the battery related documents located in the system manual for battery cabinet specifics.
11..44
U
Ussiinngg TThhiiss M
Maannuuaall
This manual describes how to install and operate the Eaton 9395XC UPS. Read and understand the procedures
described in this manual to ensure trouble-free installation and operation. In particular, be thoroughly familiar
with the REPO procedure (see paragraph and ).
The information in this manual is divided into sections and chapters. The system, options, and accessories
being installed dictate which parts of this manual should be read. At a minimum, Chapters 1 through 4 and
Chapter 7 should be examined.