Eaton 9395XC UPS 1200kW/1200kVA, 1350kW/1350kVA or 1500kW/1500kVA 164001079—Rev 01
69
1.
If not already installed, install the LAN drops.
2.
Unfasten the front door latch and swing the door open (see
).
3.
Remove a UPS top cabinet interface entry conduit landing plate(s) as required to drill or punch holes (see
).
4.
Reinstall the interface entry plates and install the conduit.
5.
Route and connect the LAN, telephone, and other cables to the appropriate Minislot cards. See
and
for Minislot communication bay locations.
6.
Close the front door and secure the latch.
7.
Refer to the manual supplied with the Minislot card for operator instructions.
Figure 37. Minislot Communication Bays
Minislot Commnunication Bay 1
Minislot Commnunication Bay 2
Minislot Commnunication Bay 3
Minislot Commnunication Bay 4
TB1
TB2
TB3
44..88
IInnssttaalllliinngg aa R
REEP
PO
O S
Sw
wiittcchh
A latching-type Remote Emergency Power-off (REPO) switch can be used in an emergency to shut down the
UPS and remove power to the critical load from a location away from where the UPS is installed.
shows a REPO switch.
NOTE
Before installing a REPO switch, verify that the UPS was installed according to the
instructions in paragraphs
Unloading the UPS Cabinet from the Pallet
through
Installing Interface Connections
NOTE
When installing the REPO switch, you must install conduit between the device and the
UPS cabinet for wiring the switch.