Eaton 9395XC UPS 1200kW/1200kVA, 1350kW/1350kVA or 1500kW/1500kVA 164001079—Rev 01
41
C
Chhaapptteerr 44 U
UP
PS
S S
Syysstteem
m IInnssttaallllaattiioonn
44..11
P
Prreelliim
miinnaarryy IInnssttaallllaattiioonn IInnffoorrm
maattiioonn
Installation should be performed only by qualified personnel.
AVERTISSEMENT!
L’installation ne doit être effectuée que par du personnel qualifié.
Refer to the following while installing the UPS system:
•
UPS Installation Plan and Unpacking
for cabinet dimensions, equipment weight, wiring and
terminal data, and installation notes.
•
Do not tilt the cabinet more than ±10° during installation.
•
Remove the conduit landing plates to add conduit landing holes as required. Plate material is 16 gauge
steel (1.5 mm/0.06" thick).
•
If perforated floor tiles are required for ventilation, place them in front of the UPS.
44..22
U
Unnllooaaddiinngg tthhee U
UP
PS
S C
Caabbiinneett ffrroom
m tthhee P
Paalllleett
The I/O and ISBM/PM sections are bolted to separate wooden pallets supported by wood skids. To remove the
pallets:
The I/O and ISBM/PM section is heavy (see
). If unpacking and unloading instructions are not closely
followed, the cabinet may tip and cause serious injury.
AVERTISSEMENT!
Les sections de l’onduleur sont lourdes (voir le
). Suivre attentivement les instructions de déchargement
et de déballage pour éviter de renverser les armoires, ce qui pourrait causer de graves blessures.