32
Eaton 9395XC UPS 1200kW/1200kVA, 1350kW/1350kVA or 1500kW/1500kVA 164001079—Rev 01
Table 11. 480V Power Cable Conduit Recommendations
UPS Model
Voltage
Terminal
Number of
Wires in
Conduit
Minimum
Conduit
Trade Size
Number
of
Conduits
Eaton 9395XC-1200/1200
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
8
AC Output
(A, B, C, Ground)
4
3
6
AC B ypass
(A, B, C, Ground)
4
3
6
DC (Common
Battery)
Battery
(Positive, Negative, Ground)
3
2.5
9
Eaton 9395XC-1350/1350
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
9
AC Output
(A, B, C, Ground)
4
3
8
AC B ypass
(A, B, C, Ground)
4
3
9
DC (Common
Battery)
Battery
(Positive, Negative, Ground)
3
2
12
Eaton 9395XC-1500/1500
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
9
AC Output
(A, B, C, Ground)
4
3
8
AC B ypass
(A, B, C, Ground)
4
3
8
DC (Common
Battery)
Battery
(Positive, Negative, Ground)
3
2.5
12
Battery Conductor Routing:
Refer to the notes at the bottom of
Input/Output Ratings and External
Wiring Requirements. External overcurrent protection and disconnect are not provided by this product, but are
required by codes. Refer to
If an output lockable disconnect is required, it is to be supplied by the customer.
Summary of Contents for 9395XC
Page 8: ......
Page 160: ...16400107901 164001079 01 ...