UPS INSTALLATION PLAN AND UNPACKING
Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual
S
164201710 Rev 2
www.eaton.com\powerquality
3-18
3.3
Inspecting and Unpacking the UPS Cabinet
The UPS cabinet is palleted separately for shipping. The cabinet is shipped bolted to a
wooden pallet (see Figure 3‐8) and protected with outer protective packaging material.
W
A
R
N
I
N
G
The UPS cabinet is heavy (see Table 3‐1 on page 3-2). If unpacking and unloading instructions are not
closely followed, the cabinet may tip and cause serious injury.
C
A
U
T
I
O
N
To prevent damage to the wiring channel and wiring in the UPS cabinet base when lifting or moving the
cabinet:
S
Lift and move the cabinet using only the front or rear forklift slots.
S
Verify that the forklift forks are in a horizontal position before inserting them into the forklift slots.
DO NOT angle fork tips upward.
S
Insert the forks all the way through the base. DO NOT insert forks partially into the base to move the
cabinet.
S
Forks may be partially inserted into the front or rear forklift slots for minor positioning if the forks are
kept in a horizontal position with no upward angling.
S
DO NOT use the forklift slots on the end of the cabinet to move the cabinet.
S
End forklift slots may be used for minor positioning if the forks are kept in a horizontal position with no
upward angling.
If these instructions are not followed, damage to the wiring channel and wiring will occur.
1.
Carefully inspect the outer packaging for evidence of damage during transit.
C
A
U
T
I
O
N
Do not install a damaged cabinet. Report any damage to the carrier and contact an Eaton service
representative immediately.
NOTE
For the following step, verify that the forklift or pallet jack is rated to handle the weight of the
cabinet (see Table 3‐1 on page 3-2 for cabinet weight).
2.
Use a forklift or pallet jack to move the packaged cabinet to the installation site,
or as close as possible, before unpacking. If possible, move the cabinet using the
pallet. Insert the forklift or pallet jack forks from the right side of the pallet (facing
the cabinet), between the supports on the bottom of the pallet (see Figure 3‐6 on
page 3-5 for the UPS cabinet center of gravity measurements). If the cabinet
must be moved using the cabinet front or rear fork lift slots, see the caution
statement at the beginning of this procedure.
C
A
U
T
I
O
N
Do not tilt the UPS cabinet more than 10° from vertical or the cabinet may tip over.
3.
Set the pallet on a firm, level surface, allowing a minimum clearance of 3m (10 ft)
on each side for removing the cabinet from the pallet.
NOTE
The UPS cabinet is shipped with debris shields covering the ventilation grills on top of the unit.
Do not remove the debris shield until installation is complete.