UPS SYSTEM INSTALLATION
Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual
S
164201710 Rev 2
www.eaton.com\powerquality
4-29
3 (NO)
UPS TB1
REPO
Switch
(NC)
Twisted
Wires
1 (NC)
2 (Return)
4 (Return)
NOTE
REPO switch rating is 24 Vdc, 1A minimum.
NOTE
T
he REPO switch must be a latching-type switch not tied to any other circuits.
NOTE
REPO normally-open and normally-closed return terminals are separated on the terminal board but are electrically in common.
1
2
Figure 4‐22. Normally‐Closed REPO Switch Wiring
3 (NO)
UPS TB1
REPO
Switch
(NO)
Twisted
Wires
1 (NC)
2 (Return)
4 (Return)
REPO
Switch
(NC)
NOTE
REPO switch rating is 24 Vdc, 1A minimum.
NOTE
T
he REPO switch must be a latching-type switch not tied to any other circuits.
NOTE
REPO normally-open and normally-closed return terminals are separated on the terminal board but are electrically in common.
Figure 4‐23. Normally‐Closed and Normally‐Open REPO Switch Wiring