Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual
S
164201710 Rev 2
www.eaton.com\powerquality
10-1
Chapter 10
Product Specifications
10.1
Model Numbers
The UPS is housed in a free‐standing cabinet with safety shields behind the door and
front panels. The UPS is available in 50 or 60 Hz with various output power ratings.
Models
Power Rating
Frequency
Eaton 9395-275/225
225 kVA
50/60 Hz
Eaton 9395-275/275
275 kVA
50/60 Hz
10.2
Specifications
The following sections detail the input, output, battery, and environmental
specifications for the UPS.
10.2.1
UPS Input
Operating Input Voltage
400 Vac
480 Vac
Operating Input Frequency Range
50/60 Hz
Operating Input Current
See Table 3‐4 on page 3-8, Table 3‐5 on page 3-9, or Table 3‐6 on
page 3-10.
Reduced for Generator
Adjustable
Input Current Harmonic Content
5% THD at full load
Power Factor
Minimum 0.99
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801‐4
Battery Voltage
480 Vdc
Battery Charging Capacity
Configurable per UPM at nominal line voltage:
Up to 120A with less than 85% load
Up to 80A with 100% load
Battery Shunt Trip
48 Vdc