Trouble Shooting (continued)
Problem
Possible Causes
No Spark
Voltage under 24VAC
Improper spark gap (7/64” or
.109)
Loose ground wire
Broken electrode
Faulty electronic module
Burner Won’t Light
Air in gas line
Low gas pressure
Bad gas valve
Blockage in gas line
Manual gas valve turned “OFF”
Inconsistent Operation
Variable gas pressure
(improperly sized gas line)
Variable voltage
Wind exceeding 15 mph
(24kmh)
Tip angle exceeding 30 degrees
Debris inside burner
Erratic winds
Deterioration of the Front
Grill
“The Equator”
must be installed
in such a manner as to allow the
products of combustion or hot
gases to vent out the top portion of
the heaters. When operating
normally, only radiant heat passes
through the front grill. If conditions
exist which force hot gases through
the front grill of heater, the
installation must be altered to
correct the condition.