6
Ventilation
1.
It is
MANDITORY
that a minimum building ventilation rate of four (4)
CFM per 1000 BTUH of installed heater input be provided. This rate
of ventilation may be obtained through either gravity or mechanical
ventilation of the building.
2.
In conjunction with building ventilation system, adequate fresh air into
the building must be provided through fresh air inlets and/or building
openings
3.
Local authorities must be contacted to assure the ventilating system
and heater installation are in compliance with any and all applicable
codes.