Vantage 4000

 

 

 

 
 
 
 
 
 
 

Vantage 4000 Recommended System Diagram 

 
 

Input Power

4-20madc output

Metallic Conduit
(by others)

Pull Box
(by others)

Flex Conduit
(by others)

Sensor Cable (1000ft max.)

NEMA 4X/IP66
Enclosure

Sensor connections: 1/2"-14 NPT

7/8" entrance holes
(3 places)

 

 
 
 
 
 
 
 
 
 
 
 
 
 

2-2 

Note:

 The key will have to be left in the hinge handle 

if the door is to remain unlocked. The only way the 
key can be removed is if the hinge handle is locked. 

Summary of Contents for Vantage 4000

Page 1: ...h the manual The change notice will identify the sections in this manual where the changes have occurred Vantage 4000 Table of Contents Scope 1 1 General Specifications 1 2 Installation Procedure 2 1...

Page 2: ...ata Logger Software CD Display Backlit LCD 128x64 Graphic Module Programming Front panel mounted 16 button keypad Computer or Palm Pilot Power 80 240 VAC 50 60 Hz or 12 28 VDC 350 mA continuous Accura...

Page 3: ...hinged door clasps on the front cover of the enclosure To open put thumb on one of the hinges pull toward the outside of the enclosure Once the hinge pops to the outside it will lower allowing the cl...

Page 4: ...Pull Box by others Flex Conduit by others Sensor Cable 1000ft max NEMA 4X IP66 Enclosure Sensor connections 1 2 14 NPT 7 8 entrance holes 3 places 2 2 Note The key will have to be left in the hinge ha...

Page 5: ...C power terminal is separate from the other two terminal strips The power terminal strip has three connections for High Low and Ground for AC voltage only Refer to the wiring diagram below for all int...

Page 6: ...cable and remove the middle cover 4 Remove middle shield Measure 5 8 from the end of the cable With a pair of small cutters cut the shield around the cable at the measured point and remove the cut of...

Page 7: ...inches outside of junction box Select one sensor cable and one cable from the electronic enclosure and place them side by side as shown in Fig 1 Twist each cable s outer pigtails together then the inn...

Page 8: ...g To adjust damping time 06 Lost Signal To adjust Lost signal time and Fail to zero or span 07 Flow Sim Flow simulation 08 Integrator To assign closure for contact integrator 09 Setpoints To assign se...

Page 9: ...s ENTER key and number 01 Flow Units Select the flow engineering unit desired by pressing the number in front of the selection Units available are 01 GPM gallons minute 09 LPD liters day 02 GPD gallon...

Page 10: ...sensor and is 640KHZ operating frequency 06 V30ST 640 is the small new style strap on sensor for high temperature applications and is 640KHZ operating frequency 07 V30L 640 is the large new style stra...

Page 11: ...pe Material screen Pipe Material The pipe material screen will allow you to select the pipe material for the unit Selections are Carbon Steel Stainless Steel PVC Cast Iron Ductile Iron Asbestos Cement...

Page 12: ...sensor placement on the pipe Selections are 01 Z Shot sensors are mounted on opposite sides of pipe 02 V Shot sensors are mounted on the same side of pipe 03 W Shot sensors are mounted on the same sid...

Page 13: ...ards To adjust Span Press the 6 key the cursor arrow will appear before the 6 20 mA line Press the 3 key for coarse adjustment or the 4 key for fine adjustment Now press the 1 key to adjust the mA upw...

Page 14: ...key the next screen to appear is the Lost Signal Action assignment In this screen the user will select the default for the 4 20mADC output during a lost signal condition The selections are 01 Fail to...

Page 15: ...t after the selection is entered Press the ENTER key The Setpoints must be assigned to a Relay 10 Relays Relay Assignment The next option in the program menu is the Relays screen To select this press...

Page 16: ...1 Not active 02 Setpoint 1 03 Setpoint 2 04 Setpoint 3 If set points are selected then the next screen will be storage rate times available 04 Log Channels There are up to 8 channels available for log...

Page 17: ...Display Mode 4 N A Model 4400 01 Display Mode 1 Flow Velocity Totalizer and Status 02 Display Mode 2 N A 03 Display Mode 3 N A 04 Display Mode 4 N A 05 Options N A 06 Totals Reset This option will re...

Page 18: ...s or omissions of others after shipment nor any consequential incidental or contingent damage whatsoever A claim for equipment damaged in transit is the sole responsibility of the customer NUCLEAR DIS...