33
The ground fault circuit interrupter must be a high-speed
type breaker of 30 mA (<0.1 s).
Procedure
Door 2
: electrical parts of the hydraulic compartment, backup
heater:
XT5
(
3-phase
)
/XT4(1-phase)
For remote alarm:
1. Connect the cable to the appropriate terminals as shown on the
diagram.
2. Fix the cable with cable ties to the cable tie mountings to ensure
stress relief.
Procedure
1. Connect the cable to the appropriate terminals as shown in the
picture
2. Fix the cable with cable ties to the cable tie mountings to ensure
stress relief.
Procedures
1. Connect the valve cable to the appropriate terminals as shown
in the picture
2. Fix the cable with cable ties to the cable tie mountings to ensure
stress relief
For 2-way valve SV2:
For 3-way value SV1
NOTE
: Only a normal closing valve is available for this unit
NOTE
: Wiring of the 3-way
valve is different for NC(normal
close) and NO (normal open).
Before wiring, read the Installation
& Owner's manual for the 3-way
valve carefully and install the valve
as showed in the picture. Make
sure to connect it to the correct
terminal numbers.
9.6.6 Connection for other components
Port provide the control signal to the load.Two kind of control signal
port:
Type 1:dry connector without voltage.
NOTE
N
L
4
T
X
5
T
X
3
L
2
L
1
L
POWER SUPPLY FOR
ELECTRIC HEATER
POWER SUPPLY FOR
ELECTRIC HEATER
Maximum running current
Wiring size
Voltage
220-240VAC
0.75mm
2
0.2A
1
SL1 SL2
2
CONNECT TO SOLAR
PUMP SATATION
220-240VAC INPUT
Maximum running current
Wiring size
Voltage
Passive signal port
0.2A
0.75mm
2
REMOTE ALARM
FUSE
REMOTE ALARM
12
24
18
SV2
SV2
N
19
SV1
ON OFF
6
7
N
21
Method 1
Method 2
ON OFF
6
7
N
21
For remote shutdown:
SWITCH SIGNAL INPUT
9
10
M1
M2
CLOSE:SHUT DOWN
For solar energy kit
Type 2: Port provide the signal with 220V voltage. If the current of
load is <0.2A, load can connect to the port directly.
If the current of load is >=0.2A, the AC connector is required to
connected for the load.
Type 1
Control signal port of hydraulic part : The
XT7
contains terminals
for solar energy, remote alarm, 2-way valve, 3-way valve, pump,
booster heater and external heating source, etc.
The parts wiring is illustrated below:
Load
Running
Control port signal type
Maximum running current
Wiring size
Voltage
220~240VAC
0.2A
0.75mm
2
Type 2
Control port signal type
Maximum running current
Wiring size
Voltage
220~240VAC
0.2A
0.75mm
2
Type 2
Control port signal type
Type 1
Type 2
4
7 5 3
1
A1
A2
2
4
6
8
TBH
Power supply
Contactor
N
15
SV1
P_s N
22
23
SOLAR PUMP
CONTROL SIGNAL
OUTPUT
Maximum running current
Wiring size
Voltage
220~240VAC
0.2A
0.75mm
2
Type 2
Control port signal type
FUSE
25
26
R1 R2
V.2
Summary of Contents for ETH-80VM
Page 4: ...4 1 2 1 3 1 1 1 1 1 1 1 2 3 1 1 0 1 0 1 0 Forma Nombre V 2...
Page 7: ...NOTA NOTA NOTA 404 502 1210 361 760 1404 760 361 1404 100mm 80mm 7 kW 10 12 14 16 kW 7 V 2...
Page 49: ...50 11 PRUEBA DE FUNCIONAMIENTO Y COMPROBACI N FINAL V 2...
Page 50: ...51 NOTA V 2...
Page 56: ...57 Equipos Monof sicos 5 y 7kW ANEXO 1 ESQUEMA EL CTRICO UNIDAD INTERIOR V 2...
Page 57: ...58 Equipos Monof sicos 10 a 16kW V 2...
Page 86: ...60mm B C A 25 V 2...
Page 176: ...V 2 WIRE CONTROL WITH WEEKLY PROGRAMMING OWNER S MANUAL MODEL ECRTH...
Page 199: ...V 2 www easelectric es...