![EAS Electric ETH-80VM Installation & Owner'S Manual Download Page 125](http://html1.mh-extra.com/html/eas-electric/eth-80vm/eth-80vm_installation-and-owners-manual_3432162125.webp)
36
10.1 Climate related curves
It is important that all information in this chapter is read sequentially by the installer and that the system is configured as applicable.
The unit should be configured by the installer to match the installation environment (outdoor climate, installed options, etc.) and user expertise.
10 START-UP AND CONFIGURATION
The climate related curves can be selected in the user interface (refer to the operation manual,
6.2.2 Weather Temperature set,
if ECO mode
is enabled, please refer to the operation manual
6.2.3 ECO Mode
). Once the curve is selected, the target outlet water temperature is determined
by the outdoor temperature. In each mode, you can select one curve from eight curves in the user interface. And it designed for three applications.
Floor heating Low temperature / Floor heating High temperature and Radiator. For some new building with good insulation, you can adopt floor
heating Low temperature curves. And set corresponding curves in controller. If your building insulation is not so well, you can choose floor heating
high temperature curves. If you need relace a boiler for radiator, Please choose radiator curves.
The relationship between outdoor temperature(T4
/℃
) and target outlet water temperature(T1s
/℃
) is described in the table and picture below. The
selection of the low/high temperature curve can be done in the user interface. In cool mode refer to
10.7 Field setting/COOL
control /How to set
the COOL mode
. In heat mode refer to
10.7 Field setting/HEAT control/How to set the HEAT mode
.
Temperature curves for hea�ng mode
-20
-15
-10
-5
0
5
10
15
20
25
35
LOW 1
30
30
30
28
27
25
23
22
20
20
20
LOW 2
34
34
34
32
29
27
25
22
20
20
20
LOW 3
38
38
38
35
32
29
26
23
20
20
20
LOW 4
41
41
41
38
34
31
27
24
20
20
20
LOW 5
45
45
45
41
37
33
28
24
20
20
20
LOW 6
49
46
44
42
39
37
35
32
30
30
30
LOW 7
51
49
46
43
41
38
35
33
30
30
30
LOW 8
54
51
48
45
42
39
36
33
30
30
30
HIGH 1
55
53
50
47
43
40
37
33
30
30
30
HIGH 2
55
55
52
48
45
41
37
34
30
30
30
HIGH 3
55
55
54
50
46
42
38
34
30
30
30
HIGH 4
46
46
46
43
39
36
32
29
25
25
25
HIGH 5
50
50
50
46
42
38
33
29
25
25
25
HIGH 6
53
53
53
48
44
39
34
30
25
25
25
HIGH 7
57
57
57
52
46
41
36
30
25
25
25
HIGH 8
60
60
60
54
48
42
37
31
25
25
25
Floor Heating Low
Temperature
Floor Heating High
Temperature
Radiator
Application
Curve number
T1s
-20
-15
-10
-5
0
5
10
15
20
25
3 5
ECO-LOW 1
25
25
25
23
22
20
20
20
20
20
20
ECO-LOW 2
29
29
29
26
24
22
20
20
20
20
20
ECO-LOW 3
32
32
32
29
26
24
21
20
20
20
20
ECO-LOW 4
36
36
36
32
29
25
22
20
20
20
20
ECO-LOW 5
39
39
39
35
31
27
23
20
20
20
20
ECO-LOW 6
45
42
39
37
34
32
30
30
30
30
30
ECO-LOW 7
48
44
41
38
36
33
30
30
30
30
30
ECO-LOW 8
50
46
43
40
37
34
31
30
30
30
30
ECO-HIGH 1
50
48
45
42
38
35
32
30
30
30
30
ECO-HIGH 2
50
50
47
43
40
36
32
30
30
30
30
ECO-HIGH 3
50
50
49
45
41
37
33
30
30
30
30
ECO-HIGH 4
41
41
41
38
34
31
27
25
25
25
25
ECO-HIGH 5
45
45
45
40
36
32
28
25
25
25
25
ECO-HIGH 6
48
48
48
43
39
34
29
25
25
25
25
ECO-HIGH 7
52
52
52
46
41
36
31
26
25
25
25
ECO-HIGH 8
55
55
55
49
43
37
32
27
25
25
25
Radiator
Application
Outdoor Temperature T4
Floor Heating Low
Temperature
Floor Heating High
Temperature
Curve number
T1s
Temperature curves for hea�ng ECO mode
V.2
Summary of Contents for ETH-80VM
Page 4: ...4 1 2 1 3 1 1 1 1 1 1 1 2 3 1 1 0 1 0 1 0 Forma Nombre V 2...
Page 7: ...NOTA NOTA NOTA 404 502 1210 361 760 1404 760 361 1404 100mm 80mm 7 kW 10 12 14 16 kW 7 V 2...
Page 49: ...50 11 PRUEBA DE FUNCIONAMIENTO Y COMPROBACI N FINAL V 2...
Page 50: ...51 NOTA V 2...
Page 56: ...57 Equipos Monof sicos 5 y 7kW ANEXO 1 ESQUEMA EL CTRICO UNIDAD INTERIOR V 2...
Page 57: ...58 Equipos Monof sicos 10 a 16kW V 2...
Page 86: ...60mm B C A 25 V 2...
Page 176: ...V 2 WIRE CONTROL WITH WEEKLY PROGRAMMING OWNER S MANUAL MODEL ECRTH...