■ Ground the unit.
Grounding resistance should be according to local laws and
regulations
Do not connect the ground wire to gas or water pipes,
lightning conductors or telephone ground wires.
Incomplete grounding may cause electric shocks.
a) Gas pipes.
Fire or an explosion might occur if the gas leaks.
b) Water pipes.
Hard vinyl tubes are not effective grounds.
c) Lightning conductors or telephone ground wires.
Electrical threshold may rise abnormally if struck by a lightning bolt.
■ Install the power wire at least 3 feet (1 meter) away from
televisions or radios to prevent interference or noise. (Depending
on the radio waves, a distance of 3 feet (1 meter) may not be
sufficient to eliminate the noise.)
■ Do not wash the unit. This may cause electric shocks or fire. The
appliance must be installed in accordance with national wiring
regulations. If the supply cord is damaged, it must be replaced by
the manufacturer, its service agent or similarly qualified persons in
order to avoid a hazard.
■ Do not install the unit in the following places:
a) Where there is mist of mineral oil, oil spray or vapors.
Plastic parts may deteriorate, and cause them to come
loose or water to leak.
b) Where corrosive gases (such as sulphurous acid gas) are
produced.
Where corrosion of copper pipes or soldered parts may cause
refrigerant to leak.
c) Where there is machinery which emits electromagnetic waves.
Electromagnetic waves can disturb the control system and
cause equipment malfunction.
d) Where flammable gases may leak, where carbon fiber or
ignitable dust is suspended in the air or where volatile
flammables such as paint thinner or gasoline are handled.
These types of gases might cause a fire.
e) Where the air contains high levels of salt such as near the
ocean.
11
Pump operation
With no room thermostat connected to the unit (1), the circulation pump (1.8) and (11) will operate as long as the unit is on for space heating.
The pump (1.8) will operate as long as the unit is on for heating domestic hot water.
Space heating and cooling
According to the season, the customer selects cooling or heating through the user interface. The unit (1) will operate in cooling mode or heating
mode to achieve the target water flow temperature. In heating mode, the 2-way valve (20) is open. Hot water is provided to both the fan coil units
and the floor heating loops. In cooling mode, the motorized 2-way valve (20) is closed to prevent cold water running through the floor heating loops
(FHL).
The ON/OFF setting of the heating/cooling operation is done by the user interface.
NOTE
Details on pump configuration can be found in
10.5 setting the pump speed
.
NOTE
CAUTION
When closing several loops in the system by remotely controlled valves, it might be required to install a bypass valve (18) to avoid the
flow switch safety device from being activated. See also
8.2 Application 2
.
Wiring of the 2-way valve (20) is different for a NC (normal closed) valve and a NO (normal open) valve. The NO valve is unavailable
to this unit. Make sure to connect to the correct terminal numbers as detailed on the wiring diagram.
8.5 Application 5
Space heating with an auxiliary boiler (alternating operation).
Space heating application by either the unit or by an auxiliary boiler connected in the system.
■ The unit controlled contact (also called 'permission signal for the auxiliary boiler") is determined by the outdoor temperature (thermistor
located at the outdoor unit). See
10.7 Field settings/OTHER HEATING SOURCE
■ Bivalent operation is possible for both space heating operation and domestic water heating operation.
■ If the auxiliary boiler only provides heat for space heating, the boiler must be integrated in the piping work and in the field wiring according to
the illustration for
application a
.
■ If the auxiliary boiler is also providing heat for domestic hot water, the boiler can be integrated in the piping work and in the field wiring
according to the illustration for
application b
.
■
Application c
can be used If the temperature of water from the outdoor unit is not high enough. An additional 3-way valve should be
installed, if ambient temperature is high and thus water from outdoor unit is high enough, The boiler will not work and water will not flow past
the boiler. When ambient temperature is low and and thus water from outdoor unit is not high enough, the boiler will work and the 3-way valve
will open to make water from outdoor unit flow past the boiler and be heated again.
CAUTION
Be sure that the boiler and the integration of the boiler in the system is in accordance with relevant local laws and regulations.
If the volume of balance tank(9) is larger than 30L, the buffer tank(8) is unnecessary, otherwise the buffer tank(8) should be installed and the
total volume of balance tank and buffer tank should larger than 30L.
The drain valve (6) should be installed at the lowest positon of the system.
For 5/7/9kW unit, the backup heater (1.5) is not integrated in the outdoor unit. An independent backup heater can be selected and installed in the
door.
V.2
Summary of Contents for ETH-80VM
Page 4: ...4 1 2 1 3 1 1 1 1 1 1 1 2 3 1 1 0 1 0 1 0 Forma Nombre V 2...
Page 7: ...NOTA NOTA NOTA 404 502 1210 361 760 1404 760 361 1404 100mm 80mm 7 kW 10 12 14 16 kW 7 V 2...
Page 49: ...50 11 PRUEBA DE FUNCIONAMIENTO Y COMPROBACI N FINAL V 2...
Page 50: ...51 NOTA V 2...
Page 56: ...57 Equipos Monof sicos 5 y 7kW ANEXO 1 ESQUEMA EL CTRICO UNIDAD INTERIOR V 2...
Page 57: ...58 Equipos Monof sicos 10 a 16kW V 2...
Page 86: ...60mm B C A 25 V 2...
Page 176: ...V 2 WIRE CONTROL WITH WEEKLY PROGRAMMING OWNER S MANUAL MODEL ECRTH...
Page 199: ...V 2 www easelectric es...