6. On a solid, level mounting slab. The mounting slab should extend a minimum of 2 inches
beyond the sides of the Auxiliary Cooling Module. To reduce the possibility of noise
transmission, the mounting slab should NOT be in contact with or be an integral part of the
building foundation.
7. Where conditions or local codes require the Auxiliary Cooling Module to be attached to a
mounting pad or frame, tie down bolts should be used to fasten through the knockouts
provided in the Auxiliary Cooling Module basepan.
8. Elevate the Auxiliary Cooling Module per local climate and code requirements to provide
clearance above estimated snowfall level and ensure adequate water drainage of Auxiliary
Cooling Module. Use snow stand in areas where prolonged freezing temperatures are
encountered.
Do NOT Locate the Auxiliary Cooling Module:
1. On brick, concrete blocks or unstable surfaces
2. Near clothes dryer exhaust vents
3. Near sleeping area or near windows
4. Under eaves where water, snow or ice can fall directly in the unit
5. Within clearance less than 2 Feet from a second unit
6. Within clearance less than 4 Feet on top of unit
7. Within the minimum distance the Auxiliary Cooling Module can be installed from the
property line, where local zoning ordinances apply.