Installation – Auxiliary Cooling Module Placement
The Auxiliary Cooling Module unit is placed as shown in Figure 1 relative to other components in
the EarthLinked
®
system.
The Auxiliary Cooling Module is located outdoors and will be
connected to the refrigerant line set outside the building.
Figure 1. Auxiliary Cooling Module Placement in EarthLinked
®
System
Location Requirements for the Auxiliary Cooling Module:
1. Within 40 Feet of the earth loop line set. Minimize refrigerant line lengths.
2. Higher than the compressor unit.
3. No more than 20 feet higher than the earth loop manifolds.
4. With proper clearances around the unit:
•
48 inches minimum on top
•
12 inches minimum on the three sides
•
24 inches minimum on the service side
5. Away from windows, patios, decks, etc., where unit operation sounds may disturb the
occupants.