background image

 

ACM-410D-IM (11/12) 

 

Page 11 

4.  Install two-pole terminal strip inside electrical box and fasten into existing hole with screw 

provided. 

5.  Attach pink wire with piggyback connector onto “T2” (for single phase) or “T3” (for three 

phase) on the compressor contractor and the other connector to the center terminal of the 
bottom fuse holder. 

 

 

6.  Attach the gray wire with the piggy back connector onto “L1” on the compressor contactor, 

and the other connector to the center terminal of the top fuse holder. 

7.  Attach the pink wire with connector to the collar connection of the bottom fuse holder, and 

tighten the terminal screw of the terminal block onto the stripped end of the pink wire. 

8.  Attach the gray wire with connector to the collar of the top fuse holder, and tighten the other 

terminal screw of the terminal block onto the stripped end of the gray wire. 

9.  Run high voltage wiring from the two-pole terminal strip in the electrical box out of the 

grommeted end hole of the electrical box and through the conduit connection of the 
compressor cabinet, to the Disconnect shown in Figure 6, and from the Disconnect to the 
Auxiliary Cooling Module, using flexible conduit. 

10. After running the power wiring in flexible conduit to the Auxiliary Cooling Module, remove 

the Auxiliary Cooling Module electric box cover. 

 

11. The Auxiliary Cooling Module control box contains a Ranco pressure control that has been 

factory set to energize the Auxiliary Cooling Module at a predetermined compressor 
discharge pressure. 

DO NOT ATTEMPT TO ADJUST THIS CONTROL! 

Figure 6 illustrates the electrical connections that are to be made at the ACM electric box 
with the two high voltage leads from the compressor unit. 

Summary of Contents for ACM-024C

Page 1: ...12 Earthlinked Technologies Inc EarthLinked Auxiliary Cooling Module Models ACM 024C thru ACM 072C For R 410A Installation Manual CONTENTS PAGE Pre Installation 3 Installation 5 Placement 5 Refrigeran...

Page 2: ...e with the instructions set forth within this manual Failure to provide installation by an authorized trained installer in a manner consistent with this manual will void the limited warranty coverage...

Page 3: ...of the system The table below lists the properly matched EarthLinked Auxiliary Cooling Module models with EarthLinked compressor unit models Application of the Auxiliary Cooling Module ACM to R 410A s...

Page 4: ...t Dimensions Full Load Amps Rated HP Nominal RPM Width inches Depth inches Height inches ACM 024C 230 1 60 207 253 0 9 5 0 0 7 1 10 1010 24 25 24 25 24 50 ACM 036C 230 1 60 207 253 0 9 5 0 0 7 1 10 10...

Page 5: ...1 Auxiliary Cooling Module Placement in EarthLinked System Location Requirements for the Auxiliary Cooling Module 1 Within 40 Feet of the earth loop line set Minimize refrigerant line lengths 2 Highe...

Page 6: ...ate the Auxiliary Cooling Module per local climate and code requirements to provide clearance above estimated snowfall level and ensure adequate water drainage of Auxiliary Cooling Module Use snow sta...

Page 7: ...at the factory They should be un brazed at the time that tubing is to be connected to the Auxiliary Cooling Module After locating the Auxiliary Cooling Module as noted earlier a trench 3 to 4 Feet de...

Page 8: ...12 Page 8 Figure 3 Auxiliary Cooling Module Refrigerant Piping A top view of typical Auxiliary Cooling Module and line set vapor line connections are illustrated in Figure 4 Figure 4 Top View of Line...

Page 9: ...refrigerant piping connections This process eliminates oxidation products from inside joint surfaces TECHNIQUE Trickle nitrogen gas at 1 2 psi pressure through the joint area being brazed to displace...

Page 10: ...ropriate breakers remove the front and top panels of the compressor unit cabinet 2 Reference Figure 5 for compressor unit electrical box Remove available hole covers from the front of the electrical b...

Page 11: ...older and tighten the other terminal screw of the terminal block onto the stripped end of the gray wire 9 Run high voltage wiring from the two pole terminal strip in the electrical box out of the grom...

Page 12: ...ng Module Field Wiring 12 Check all wiring and electrical connections to ensure proper routing and good contact before restoring electric power evacuating and recharging system in accordance with the...

Reviews: