BIT0
:
Motor overload protection selection
0
:
Invalid 1
:
Valid
BIT1
:
Ground fault duringpower-on
0
:
Invalid 1
:
Valid
BIT2
:
Input phase loss protection selection
0
:
Invalid 1
:
Valid
BIT3
:
Output phase loss protection selection
0
:
Invalid 1
:
Valid
1011
Protection
function
selection 1
P9
-
00
0900H
BIT0: Output load loss protection selection
0: Invalid 1: Deceleration 2: Ramp to stop
BIT1: Instantaneous power failure action
selection
0: Invalid 1: Valid
BIT2: Continue operation frequency selection
in case of failure
0: Operate at current operation frequency
1: Operate at set frequency
2: Operate at the upper limit frequency
3: Operate at the lower limit frequency
4: Operation at abnormal standby frequency
BIT3: Action selection of fault “DO”during
fault automatic reset
0: No action 1: Action
0000
Protection
function
selection 2
P9
-
01
0901H
P9
-
02
Fault auto
reset times
0
0902H
0: OFF
Automatic reset function is turned off, only
manual reset is allowed.
1-20: ON
This function is on, 1-20 is the number of
times of self recovery after failure (defined
as the maximum number of times of auto reset
after each failure)
P9
-
03
Time interval of
fault auto reset
1.0s
0903H
0.1
~
100.0s
The waiting time from the fault of AC drive
to each reset.
P9
-
04
1st
fault type
Read-only
0904H
1 -- ERROR_INVERTER UNIT
2 -- ERROR_OC_DURING_ACC
3 -- ERROR_OC_DURING_DEC
4 -- ERROR_OC_AT_CONST_SPEED
5 -- ERROR_OV_DURING_ACC
6 -- ERROR_OV_DURING_DEC
7 -- ERROR_OV_AT_CONST_SPEED
8 -- ERROR_CONTROL POWER SUPPLY
9 -- ERROR_UV
10 -- ERROR_OL_AC DRIVE
11 -- ERROR_OL_MOTOR
12 -- ERROR_LOSE_PHASE_INPUT
13 -- ERROR_LOSE_PHASE_OUTPUT
14 -- ERROR_OH_MODULE
15 -- ERROR_EXTERNAL EQUIPMENT
16 -- ERROR_COMMUNICATE
17 -- ERROR_CONTACTOR
18 -- ERROR_CURRENT_DETECTION
19 -- ERROR_AUTO-TUNING
20 -- ERROR_ENCODER
21 -- ERROR_EEPROM_READWRITE
22 -- ERROR_HARDWARE_AC DRIVE
23 -- ERROR_MOTOR_SHORT_TO_GND
24 -- ERROR_ERRPROM_INITIALIZETE
26 -- ERROR_RUNNING TIME_REACHED
27 -- ERROR_USER-DEFINED_1
28 -- ERROR_USER-DEFINED_2
29 -- ERROR_POWER-ON_TIME_REACHED
30 -- ERROR_LOAD_0
31 -- ERROR_PID_FDB_LOSE
40 -- ERROR_PBP_CURRENT_LIMIT
41 -- ERROR_SWITCH_MOTOR_WHEN_RUN
42 -- ERROR_TOO_LARGE_SPEED_DEVIATION
43 -- ERROR_MOTOR_OS
45 -- ERROR_MOTOR_OH
51 -- ERROR_POLE_POSITION_DETECTION
P9
-
05
2nd
fault type
Read-only
0905H
Read-only
3rd
fault type
P9
-
06
0906H
P9-07
P9-08
P9-09
P9-10
0907H
0908H
0.00
~
maximum frequency
BIT0
:
Direction of operation
0
:
FWD 1
:
REV
BIT1
:
Running state
0
:
STOP 1
:
CONST
2
:
ACC 3
:
DEC
BIT2
:
RESERVED BIT3
:
RESERVED
0.1
~
2000.0A
Failure operation
frequency
Failure
output current
Failure
DC-bus voltage
Failure AC
drive status
Read-only
Read-only
Read-only
0909H
Read-only
090AH
0
~
3000V
P9
-
11
Failure S
terminal status
Read-only
090BH
See input terminal status diagram
P9
-
12
Failure Y
terminal status
090CH
See input terminal status diagram
P9
-
13
Failure
power on time
090DH
Failure power on time
P9
-
14
Failure
running time
090EH
Failure running time
P9
-
15
Frequency
upon 2nd fault
090FH
Same as P9-05
P9
-
16
Current upon
2nd fault
0910H
Same as P9-06
P9
-
17
Output voltage
upon 2nd fault
0911H
Same as P9-07
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
P9
-
18
AC drive status
upon 2nd fault
0912H
Same as P9-09
P9
-
19
S terminal status
upon 2nd fault
0913H
Same as P9-10
Read-only
Read-only
-
2 9
-
-
3 0
-
F u n c t i o n C o d e T a b l e
EC620
EC620
F u n c t i o n C o d e T a b l e