P0
-
10
Maximum output
frequency
000AH
0.00
~
320.00Hz
That is to say, the maximum frequency limit
allowed by the AC drive is also the accele-
ration and deceleration time reference
50.00Hz
P0
-
11
P0
-
12
P0
-
13
P0
-
17
P0
-
15
P0
-
18
Source of
frequency
upper limit
selection
Acceleration
time 1
Acceleration/
Deceleration
time unit
Source of
frequency
upper limit
digital setting
Source of
frequency
lower limit
digital setting
Stopping
method
000BH
000CH
000DH
000FH
0011H
0012H
0: Set by P0-12
1: AI1 2: AI2 3: AI3
4: Terminal pulse setting
5: RS485 Communication setting
0.1
~
6500.0s
Frequency lower limit
~
100.0%
0: 0.1s
1: 0.01s
0: Ramp to stop
1: Coast to stop
0
~
Frequency upper limit
0
100.0%
0.0%
P0
-
14
Frequency
lower limit
run mode
000EH
0: Stop
1: Run at frequency lower limit
2: Run at zero speed
1
Model
dependent
0
1
Rotation
direction
selection
P0
-
19
0013H
BIT0:
0: Forward direction operation
1: Reverse direction operation
BIT1:
0: Reverse operation enable
1: Reverse operation disable
0
P0
-
16
Deceleration
time 1
0010H
0.1
~
6500.0s
Model
dependent
Carrier
frequency
P0
-
20
1.0~15.0KHz
If the carrier frequency is set higher than
the factory value, it will cause the tempe-
rature rise of the AC drive to increase. At
this time, the user needs to use the AC drive
derating, otherwise the AC drive will have
the danger of overheating alarm.
0014H
Model
dependent
Carrier
frequency
accuracy unit
P0
-
21
0
:
0.1Hz
1
:
0.01Hz
0015H
2
P0
-
22
Reserved
0016H
0: Invalid
1: Effective in the whole process
2: Invalid in deceleration, valid in other
states
2
P0
-
23
Restore default
setting
0017H
0
:
No operation
1
:
Data locked
2
:
Reset Error message
0
~
210
P0
-
23
Restore default
setting
0017H
3
~
6
:
Undefined
7
:
Initialization setting—User data reset
10
:
Back up current user parameters
210
:
Restore user backup parameters
0
~
210
P1
M o tor p a ram e ter s
Setting Range
Function
Code
Parameter Name
Address
Default
P1
-
00
Motro
Auto-tuning
selection
0100H
In order to obtain better VF or vector
control performance, it is necessary to
tune the motor parameters, and the accuracy
of the adjustment results is closely related
to the correct setting of the motor name-
plate parameters.
0
:
No auto-tuning
1
:
Asynchronous motor stationary auto-tuning
2
:
Asynchronous motor (rotational)complete
auto-tuning
0
P1
-
01
Motor type
0101H
0: Common asynchronous motor
1: Variable frequency asynchronous motor
2: Permanent magnetic synchronous motor
0
P1
-
02
Motor rated power
0102H
0.1kW
~
1000.0kW Set rated power
Model
dependent
P1
-
03
Motor rated
voltage
0103H
0.1V
~
2000V Set rated voltage
Model
dependent
P1
-
04
Motor rated
current
0104H
0.01
~
655.35A (AC Drive≤55kW)
0.1
~
6553.5A (AC Drive>55kW)
Model
dependent
P1
-
05
Motor rated
frequency
0105H
0.01Hz
~
maximum frequency
Model
dependent
P1
-
06
Motor rated
rotational speed
0106H
1rpm
~
65535rpm
Model
dependent
P1
-
07
Stator resistance
(asynchronous
motor)
0107H
0.001
Ω
~
65.535
Ω
(AC Drive≤55kW)
0.0001
Ω
~
6.5535
Ω
(AC Drive>55kW)
Model
dependent
P1
-
08
Rotor resistance
(asynchronous
motor)
0108H
Model
dependent
P1
-
09
Leakage inductive
reactance
(asynchronous
motor)
0109H
0.01mH
~
655.35mH
(AC Drive≤55kW)
0.001mH
~
65.535mH
(AC Drive>55kW)
Model
dependent
P1
-
10
010AH
Model
dependent
Mutual inductive
reactance
(asynchronous
motor)
P1
-
11
No-load current
(asynchronous
motor)
010BH
0.01A
~
P1-04 (AC Drive≤55kW)
0.1A
~
P1-04 (AC Drive>55kW)
Model
dependent
P 2
V ect o r Con t rol P a ram e ter s
Function
Code
Parameter Name
Setting Range
Default
Address
-
1 1
-
-
12
-
F u n c t i o n C o d e T a b l e
EC620
EC620
F u n c t i o n C o d e T a b l e