background image

29

PID target value switchover terminal2

30

PID target value switchover terminal3

31

PID feedback value switchover terminal1

32

PID feedback value switchover terminal2

33

PID feedback value switchover terminal3

34

PLC pause        35

PLC status reset

36

Swing enable     37

Swing pause

38

Swing reset

39

Frequency source switchover terminal1

40

Frequency source switchover terminal2

41

Frequency source switchover terminal3

42

Frequency source switchover terminal4

43

Command source switchover terminal 1

44

Command source switchover terminal 2

45

Counter input terminal

46

Counter reset terminal

47

Counter clock input terminal

48

Counter reset    

49

DC braking command

50

Terminal pre-excitation

51: User-defined fault1
52: User-defined fault2
53: Full water level signal terminal              
54: Zero water level signal terminal                                                 
55: Forced switch to power frequency(closed 
switch to power frequency, open input mode 
controlled by operation panel)   

P4

-

04

S5 terminal 

function

54

0404H

P4

-

05

S6 terminal 

function

55

0405H

P4

-

06

S7 terminal 

function

10

0406H

P4

-

07

S8 terminal 

function

11

0407H

040AH

P4

-

10

0000

BIT0: S5 terminal 
0: Effective closing 

  

1: Effective opening

BIT1: S6 terminal 
0: Effective closing 

  

1: Effective opening

BIT2: S7 terminal 
0: Effective closing 

  

1: Effective opening

BIT3: S8 terminal 
0: Effective closing 

  

1: Effective opening

Characteristic 

selection of 

terminal S5-S8

Characteristic 

selection of 

terminal S1-S4

0408H

P4

-

08

0000

BIT0: S1 terminal 
0: Effective closing 

   

1: Effective opening

BIT1: S2 terminal 
0: Effective closing 

   

1: Effective opening

BIT2: S3 terminal 
0: Effective closing 

   

1: Effective opening

BITE: S4 terminal 
0: Effective closing 

   

1: Effective opening

0409H

P4

-

09

0.10s

0.000

60.00s

This parameter is defined as the size of 
filtering the input signal to eliminate the 
interference signal. The longer the filtering 
time is, the stronger the anti-interference 
ability is, but the slower the response speed 
is; the shorter the filtering time is, the 
weaker the anti-interference ability is, but 
the faster the response speed is.

Filter time of 
terminal S1-S4 

040BH

P4

-

11

0.01s

0.000

60.00s

Same as P4-08

Filter time of 
terminal S5-S8 

0: Two-line mode 1
Terminal set as 1 is forward running,
terminal set as 2 is

 

reverse running

1: Two-line mode 2
Terminal set as 1 is start running, 
terminal set as 2 is switch forward and reverse 
running
2: Three-line mode 1
Terminal set as 1 is forward running,
terminal set as 2 is reverse running,
terminal set as 3 is stop running
3: Three-line mode 2
Terminal set to 1 is start running, terminal 
set as 2 is switch forward reverse, terminal 
set as 3 is Stop running 

P4

-

12

Terminal 

command mode 

040CH

0

P4

-

13

Terminal 

action mode 

selection

040DH

0111

P4

-

16

Terminal 

protection 

function 

selection 

BIT0

0: Invalid terminal operation command when power 
on
1

Valid terminal operation command when power on

BIT1: When the run command

setting channel 

terminal switching,selection of run command is 
valid 
0: The running command is valid after stopping 
during switching
1: The run command is valid immediately when 
switching

0000

0410H

BIT0: Terminal of coast to stop recovery mode 
0: Restore the original instruction after 
invalidation 
1: Do not restore the original instruction 
after invalidation 
BIT1: Terminal of emergency stop recovery mode 
0: Restore the original instruction after 
invalidation  
1: Do not restore the original instruction 
after invalidation  
BIT2: Select the terminal operation mode after 
fault reset 
0: The terminal operation command is valid 
immediately 
1: The terminal operation command is valid 
only after it is canceled

P4

-

14

Reserved

 

-

-

040EH

P4

-

15

Reserved

 

-

-

040FH

P4

-

17

P4

-

18

UP/DW frequency 

value

UP /DW frequency 

adjustment 

selection

0.0

100.0%

P4-23*maximum frequency=actual output frequency

0: Retentive at power failure
1: Non-retentive at power failure
2: Valid operation, stop and reset

0.0%

0

0411H

0412H

1 7

 -

18

 -

  F u n c t i o n C o d e T a b l e

EC620

 

EC620

 

  F u n c t i o n C o d e T a b l e

Summary of Contents for EC620

Page 1: ...Drive Manufacturer EC620 Solar Pump AC Drive Electronic instruction Professional AC Drive Manufacturer ZHEJIANG EACN ELECTRONIC TECHNOLOGY CO LTD Address No 1 Jinhe Road Qinshan Street Haiyan County J...

Page 2: ...arameters 7 5 P4 Input Terminals Function 7 6 P5 Analog Terminal Parameters 7 7 P6 Start Stop Control Parameters 7 8 P7 System Configuration Parameters 7 9 P8 Auxiliary Functions 7 10 P9 Fault and Pro...

Page 3: ...pply is cut off but the indicator light of the mani pulator of AC drive is still on there is still high voltage in the AC drive which is very dangerous please do not touch the interior circuit and com...

Page 4: ...ignal PLC needs to be connected to external power supply and be disconnected from 24V power supply terminal 1 Input voltage range DC 0V 10V 2 Impedance 22k 1 Input range DC 0V 10V 4mA 20mA decided by...

Page 5: ...he startup operation is performed on the rotating motor 7 A sudden load is added during acceleration 8 The AC drive model is of too small power class 1 The output circuit is grounded or short circuite...

Page 6: ...power input is abnormal 2 The drive board is faulty 3 The lightening board is faulty 4 The main control board is faulty 1 Eliminate external faults 2 Seek technical support 3 Seek technical support 4...

Page 7: ...erform the motor autotuning 3 Set P9 40 and P9 41 correctly based on the actual situation 7 Function Code Table Function Code Table EC620 Faults and solutions EC620 P0 Standard Parameter group 0000H A...

Page 8: ...Restore default setting 0017H 3 6 Undefined 7 Initialization setting User data reset 10 Back up current user parameters 210 Restore user backup parameters 0 210 P1 Motor parameters Setting Range Func...

Page 9: ...eleration process of AC drive the overexcitation control can restrain the rise of bus voltage and avoid over voltage fault The larger the overexcitation gain the stronger the suppression effect 64 020...

Page 10: ...the gain is the more obvious the suppression of the oscillation is When using the vibration suppression function the motor rated current and no load current parameters shall be accurate otherwise the...

Page 11: ...rence ability is but the slower the response speed is the shorter the filtering time is the weaker the anti interference ability is but the faster the response speed is Filter time of terminal S1 S4 0...

Page 12: ...put signal selection AI1 input voltage minimum value BIT2 AI3 signal selection 0 0 10V 1 0 20 00ma BIT3 S8 enable HDI function 0 General switch function 1 HDI high speed pulse input function 0 00 10 0...

Page 13: ...0 200 0 Used to adjust the value of analog output of AO1 terminal 10 0 10 0 Used to adjust the zero point of the AO1 terminal output signal 100 0 0 0 P5 35 P5 36 P5 37 0523H 0524H 0525H 100 0 0 0 0 20...

Page 14: ...vibration when the machine starts stops After setting the S word characteristic time the accelera tion and deceleration time will only extend 1 2 of the S word characteristic time at the beginning and...

Page 15: ...nly BIT0 0 Stop 1 Run BIT1 0 Forward RUN 1 Reverse RUN BIT2 Reserved BIT3 Reserved AC drive status before power off P7 18 0712H Read only P8 Auxiliary Functions Function Code Parameter Name Setting Ra...

Page 16: ...of the AC drive The start up of the timer is completed by the external timer trigger terminal of the timer The timing starts from the reception to the external trigger signal After the timing time arr...

Page 17: ...HASE_INPUT 13 ERROR_LOSE_PHASE_OUTPUT 14 ERROR_OH_MODULE 15 ERROR_EXTERNAL EQUIPMENT 16 ERROR_COMMUNICATE 17 ERROR_CONTACTOR 18 ERROR_CURRENT_DETECTION 19 ERROR_AUTO TUNING 20 ERROR_ENCODER 21 ERROR_E...

Page 18: ...at instantaneous rise action 0 50s 0924H returns to normal the AC drive will acce lerate to the set frequency The basis for judging whether the bus voltage returns to normal is that the bus voltage is...

Page 19: ...the specification of no hardware detec tion input phase failure the input phase failure is detected by the change amplitude of bus voltage When the change amplitude of bus voltage is greater than P9...

Page 20: ...tial output PA 13 PID differential limit 0 10 0A0DH 0 00 650 00s PID given change time refers to the time required for PID given value to change from 0 0 to 100 0 PA 14 PID setting change time 0 00s 0...

Page 21: ...tion proportion setting Communication response delay 3 N 8 2 No check data format 8 stop bit 2 4 E 8 2 Even parity check data format 8 stop BIT 2 5 0 8 2 Odd Parity check data format 8 stop BIT 2 0 00...

Page 22: ...Multi frequency 9 0D09H PD 09 Multi frequency 10 0D0AH PD 10 Multi frequency 11 0D0BH 0 0 PD 11 Multi frequency 12 0D0CH 0 0 PD 12 Multi frequency 13 0D0DH 0 0 PD 13 Multi frequency 14 0D0EH 0 0 PD 14...

Page 23: ...ence 8 0D27H 0000 PD 39 Running direction and acceleration deceleration time of PLC reference 9 0D28H 0000 PD 40 Running direction and acceleration deceleration time of PLC reference 10 0D29H 0000 PD...

Page 24: ...12 100 00 2 00 100DH A0 13 Reserved 1009H A0 09 Minimum Error KP1 It determines the regulation intensity of the whole PID regulator The greater the P value is the greater the regulation intensity is...

Page 25: ...will be cleared and restored to the operation state 75 0 101AH A0 26 Full water level detection delay code is still valid when the switch value is full of water 5s 101BH A0 27 Wake up delay at full w...

Page 26: ...ers read only U Setting Range U Monitoring Parameters Function Code Parameter Name Default Address U 00 2110H Set frequency 1E00H AE 00 Timing time 1 AE Scheduled operation Parameters The three sets o...

Page 27: ...put Shielded twisted pair Close to AC drive ground terminal Coil Coil Shielded twisted pair Close to AC drive ground terminal Coil Shielded twisted pair Close to AC drive ground terminal Coil High spe...

Page 28: ...bias voltage and the factory value 24V port and PLC port are short circuited 3 Port S8 is restricted by function parameter P5 00 which can be used as high speed pulse input channel with maximum input...

Page 29: ...ication Number Distributor Contacts Date of delivery Address No 1 Jinhe Road Qinshan Street Haiyan County Jiaxing City Zhejiang Province Website www eacon cn E mail overseas eacon cc Warranty Service...

Reviews: