Display speed
factor
P7
-
04
P7
-
05
P7
-
06
P7
-
07
P7
-
08
Copy of function
parameters
First line
run display
First line
stop display
Second line
run display
0704H
0705H
0706H
0707H
0708H
0: Read data into keyboard
1: Proofread data
2: Write keyboard data to AC drive
0.000 50.000
~
BIT0: The first group displays
BIT1: The second group displays
BIT2: The third group displays
BIT3: The fourth group displays
0: Given frequency
1: Output frequency
2: Output current
3: Output voltage
4: Output voltage
5: Mechanical speed
6: Bus voltage
7: Output power
8: Model temperature
9: Actual frequency
A: Target torque
B: Output torque
C: Output excitation D: Power factor
E: PID setting F: PID feedback
1.000
3210
3210
3210
-
0709H
P7
-
09
Second line
stop display
3210
070AH
0
~
7
P7
-
10
Multi-function
expansion card
selection
-
070CH
070DH
070EH
070FH
0710H
0 65535
~
0.0 24.0
~
0 65535
~
0.0 24.0
~
0
~
655.35 million kWh
P7
-
12
P7
-
13
P7
-
14
P7
-
15
P7
-
16
Accumulated
power-on days
Accumulated
power-on hours
Accumulated
running days
Accumulated
running hours
Accumulative power
consumption
(10000 kWh)
Read-only
Read-only
Read-only
Read-only
Read-only
070BH
Led BIT0: LCD keyboard display language
Set LCD keyboard display language, only
valid when using LCD keyboard.
0: Chinese
1: English
BIT1: Output frequency display selection
0: Target frequency displays the target
frequency of the current control motor.
1: Synchronous frequency displays the
output frequency after converting operation.
BIT2: Mechanical speed display selection
0: Target speed displays the target speed
of the current control motor.
1: Actual speed displays the motor speed
actually detected by the AC drive.
BIT3: Reserved
P7
-
11
operation
panel display
item selection
0
0711H
0
~
9999kWh
P7
-
17
Accumulative
power
consumption
Read-only
BIT0: 0: Stop 1: Run
BIT1: 0: Forward RUN 1: Reverse RUN
BIT2: Reserved BIT3: Reserved
AC drive status
before power off
P7
-
18
0712H
Read-only
P8
Auxiliary Functions
Function
Code
Parameter Name
Setting Range
Default
Address
0.00Hz
~
Maximum frequency
5.00Hz
5.00Hz
10.0s
Forward JOG
running
frequency(FJOG)
Reverse JOG
running
frequency(RJOG)
JOG acceleration
time
P8
-
00
P8
-
01
P8
-
02
0800H
0801H
0802H
0.00Hz
~
Maximum frequency
10.0s
JOG deceleration
time
P8
-
03
0803H
10.0s
Acceleration
time 2
P8
-
04
0804H
10.0s
Deceleration
time 2
P8
-
05
0805H
10.0s
Acceleration
time 3
P8
-
06
0806H
10.0s
P8
-
07
0807H
0.1
~
6500.0s
10.0s
Acceleration
time 4
P8
-
08
0808H
10.0s
Deceleration
time 4
P8
-
09
0809H
10.0s
Emergency stop
deceleration
time
P8
-
10
080AH
Deceleration
time 3
0.0
~
360.00s
This function is defined as the transition time
for the AC drive to wait at 0Hz in the process
of turning from positive to reverse or from
reverse to forward. The dead time of positive
and reverse rotation is mainly set for the
equipment with large inertia load and mechanical
dead time when changing the steering.
0.0s
Forward/Reverse
rotation dead-zone
time
P8
-
11
080BH
Jump frequency 1
P8
-
12
0.00Hz
080CH
Jump frequency 2
P8
-
13
0.00Hz
080DH
0.00Hz
~
Maximum frequency
When the frequency converter operates with
load, in order to make the output frequency of
the AC drive avoid the resonance frequency point
of the mechanical load, the jump frequency can
be used to avoid the resonance point. The AC
drivecan set one jumping point to perform
jumping. After setting the jumping frequency
parameter, even if the given frequency of the
AC drive is within the resonance frequency
point of the mechanical load, the output
frequency of the AC drive will be automatically
adjusted outside the resonance frequency point
of the mechanical load to avoid running on the
resonance point.
Jump frequency
amplitude
P8
-
14
0.00Hz
080EH
-
2 5
-
-
26
-
F u n c t i o n C o d e T a b l e
EC620
EC620
F u n c t i o n C o d e T a b l e