Trend View graphs PV; or Max/Min PV between samples, plus active alarms. Trend Scale Values
adjust automatically to visible data (between 2 to 100% of the input span). Sample intervals are
set in Display Configuration. Pressing or moves the Cursor Line back through the last 240 data
points.
Note: Data is not retained at power down or the Sample Interval is changed.
Over/Under Range & Input Fail Indications
If the process or auxiliary inputs are >5% above or below the scale max/min, their displayed value is
replaced with the word “
HIGH
” or “
LOW
”. If a signal break is detected, their value is replaced with
“
OPEN
” and an uncalibrated input is replaced by “
ERROR
”. In OPEN or ERROR conditions, the
Control
Outputs go to the pre-set power value (see Control Config).
Caution:
Correct the problem before continuing normal operation.
6. Serial Communications
Set Ethernet option IP address with supplied software for networks without DHCP.
Refer to the User guide (from your supplier) for help with communications.
7. Strain Gauge Calibration Mode
Press the + to enter calibration mode from any location for quick access (see Strain Gauge
Calibration in Configuration Mode)Only applicable when Sensor input type is set to Strain Gauge.
8. Auto/Manual Key Press
Press the + to change the control mode. When pressing these keys it will put the unit into
manual mode if already in Auto and move back to the main operator screen. Pressing while in
Manual will put the controller into Auto control and back to Main operator screen.
Use with Caution
9. Pressure Control Description
This mode is entered at power on, or accessed from the Main Menu. If required, all Operation Mode
parameters can be made read only (see Display Configuration).
Note: Configuration must be completed before starting normal operations.
Output value indication:
Selectable between the following modes:
- range 0/100.0%.
- scalable with two proper values for RPM indication. (Same value as above only two
point scaled to give RPM)
In automatic mode either mode is available (not at the same time)
In manual mode a parameter is provided to select the first or second method of
indication.