Chapter 4: Programming the Rhino2
66
Beeper On Time
and
Beeper Off Time
together
set the beeper interval time. During
Beeper On Time
the beeper emits a sound.
During
Beeper Off Time
the beeper is silent.
4.4.1.10
Deep Discharge Beeper
Parameter
Possible Values
Default
HHP
Lite
Std Adv
Deep Discharge Beeper
No / Yes
Yes
This parameter is only used when
Enable Beeper
has the value 'Yes'.
Enables beeping if the battery is drained to 90% of the cut-off level set by
Battery Cut-Off Voltage
4.4.1.11
Sleep on Fault or Inhibit
Parameter
Possible Values
Default
HHP
Lite
Std Adv
Sleep on Fault or Inhibit
No / Yes
Yes
Enables going to sleep if a fault or inhibit condition is active. If set to no, the unit will not go to
sleep, but will signal the fault indefinitely.
Notes:
Sleep on Fault or Inhibit
is ignored.
During a throttle fault or OONAPU fault the controller will never go to sleep,
even if this parameter is set to 'Yes'.
4.4.1.12
Power Off after Sleep
Parameter
Possible Values
Default
HHP
Lite
Std Adv
Power Off after Sleep
No / Yes
Yes
Enables powering the unit off automatically after sleeping for approximately 6 hours to save
battery power.
Beeper Off Time
Time
So
un
d
Beeper On
Time