background image

5

IMPORTANT

To prevent possible recirculation of flue 

gases, the installer must consider the  

effects of prevailing wind conditions, 

eddy zones, nearby buildings, 

obstructions, or other obstacles such as 

shrubs when planning exhaust and air 

intake locations.  M&G DuraVent can not 

be held responsible for poor appliance 

performance or damage to buildings 

due to an incorrect installation.  The 

minimum clearances detailed within our 

instructions may not be adequate in some 

circumstances depending on the specifics 

of the installation. For this reason we 

always recommend vertical venting.

Refer to the appliance manufacturer's 
instructions for maximum and minimum 
vent lengths permitted with your specific 
appliance model. This information should 
include guidance on the maximum number 
of elbows and related pressure-drops. The 
total vent length from the appliance to 
the termination shall not be greater than 
specified by the appliance manufacturer. 
If specific guidance is not offered by the 
appliance manufacturer as to Equivalent 
Vent Lengths (EVL) for vent components, the 
general guidelines in Table 2 can be used.

CONDENSATE DRAIN 

(Fig.1)

 

Refer to the appliance manufacturer’s 
installation instructions for requirements of 
condensate drainage.  Ensure proper system 
slope for drainage.  

(Fig.6)

Figure 1

SIPHON

Table 2 - Equivalent Length Chart

2" Equivalent 

Length

3" Equivalent 

Length

4" Equivalent 

Length

5" Equivalent 

Length

6" Equivalent 

Length

8" Equivalent 

Length

1-ft Vent Pipe

1-ft

1-ft

1-ft

1-ft

1-ft

1-ft

1-ft Flex Pipe

2-ft

(same diameter 

as rigid)

2-ft

(same diameter 

as rigid)

2-ft

(same diameter 

as rigid)

2-ft

(same diameter 

as rigid)

N/A

N/A

1-ft Flex Pipe

0.4-ft 

(updsized one 

diameter)

0.6-ft 

(updsized one 

diameter)

0.6-ft 

(updsized one 

diameter)

N/A

N/A

N/A

45 Elbow

3-ft

3-ft

5-ft

6-ft

6-ft

13-ft

90 Elbow

5-ft

7-ft

12-ft

14-ft

14-ft

19-ft

Tee

9-ft

12-ft

19-ft

21-ft

22-ft

29-ft

WARNING

CARBON MONOXIDE POISONING HAZARD

 

Failure to follow these installation 

instructions could result in personal 

injury or death

P-TRAP

Summary of Contents for polypro

Page 1: ...PolyPro Installation Instructions PolyPro Single Wall Gas Vent System for Category II IV Gas Burning Appliances...

Page 2: ...egrity of ALL joints upon completion of assembly This venting system must be free to expand and contract under normal operation Assure unrestricted vent movement where required through walls ceilings...

Page 3: ...ATION 4 PERMITS 4 GENERAL INSTALLATION NOTES 4 CLEARANCES TABLE 1 4 CONDENSATE DRAIN 5 EQUIVALENT LENGTH CHART TABLE 2 5 JOINT CONNECTIONS 6 APPLIANCE CONNECTION 6 INSTALLATION 7 ENCLOSURE REQUIREMENT...

Page 4: ...must not be routed into through or within any other vent such as an existing masonry or factory built chimney flue unless that vent or chimney is not being used to vent another appliance and is only u...

Page 5: ...ecified by the appliance manufacturer If specific guidance is not offered by the appliance manufacturer as to Equivalent Vent Lengths EVL for vent components the general guidelines in Table 2 can be u...

Page 6: ...ing Band on male pipe section Fig 2 Insert locking tab into locking band recess rotate button away from Locking Band Clasp insert pipe sections push lock band clamp downward into socket disengage sock...

Page 7: ...rted by the appliance On Duravent and other certain clamp styles or greater All thread may be used as an extension 6 Vertical installations must be supported every 10 feet 3 meters or less Fig 7 7 Elb...

Page 8: ...stops are not required at the roof deck penetration 2 Cut and or frame hole Table 3 3 Slide the two halves together and attach to the ceiling Figure 9 ALIGN TABS WITH MOUNTS GASKET EXTERIOR WALL PLATE...

Page 9: ...N A N A N A TWIN PIPE HORIZONTAL CLASS IIB 7 3 8 x 25 8 187mm x 65mm 8 3 8 x 37 8 212 x 85mm 9 x 43 8 228 x 100mm N A N A N A TWIN PIPE HORIZONTAL CLASS IIC Framing Dimensions 8 x 3 200 x 77mm 8 7 8...

Page 10: ...outside wall 4 Slide cap through exterior wall plate into hole from outside building Cap must not be installed sloped downward 5 Orient termination so air intake slots face down 6 Seal termination to...

Page 11: ...Figure 16 CENTERLINE OF EXHAUST OUTLET OF APPLIANCE Vertical Concentric Fig 17 1 Locate penetration Fig 16 2 Cut hole in roof Table 3 3 Cut hole in ceiling above appliance Cut hole s big enough for p...

Page 12: ...The upper support plate with a flange for B vent and factory built chimney Fig 21 must be affixed to the top of the conduit via screws Anchor bolts must be used when attaching a flat support plate to...

Page 13: ...are exposed to the elements for wear or damage If damage is found the components should be replaced immediately Where possible look into the Termination Cap to verify no foreign material is there to...

Page 14: ...THIS PAGE INTENTIONALLY LEFT BLANK...

Page 15: ...THIS PAGE INTENTIONALLY LEFT BLANK...

Page 16: ...ty This warranty provides no cash surrender value The terms and conditions of this warranty may not be modified altered or waived by any action inaction or representation whether oral or in writing ex...

Reviews: