background image

INSTALLATION
1.  Pipe lengths may be cut to length 

(Fig.5).  Use an alternate clamp (Fig.3- 

PPS-PAC / PPS-LBC) for the connection 

if a locking tab (Fig.2) is removed.

• 

Cut square (not at an angle) to the 
end of the pipe.  

• 

Remove burrs before assembly.

Figure 5

MARK

CUT WITH 

HACKSAW

DEBURR

7

Figure 6

12"

5/8" 

MIN

1/4" - 5/8"

(7.5mm - 15mm)

TO APPLIANCE

2.  Check with appliance manufacturer for 

any restrictions or limits on vent length, 
number of elbows, etc.

3.  The slope of the vent pipe must be at 

least 3° (5/8" per ft, 50mm per meter) 
back to the appliance. 

(Fig.6)

4.  Every horizontal section must be 

supported. 

(Fig.7)

5.  The venting system shall be securely 

supported using suitable hangers.  
Duravent hardware is recommended; field 
supplied support hardware suitable to 
the AHJ is acceptable, hardware must not 
deform or damage the vent. (

Fig. 6 and 7

)  

Make sure the load of the vent system is not 
supported by the appliance.  

• 

On Duravent and other certain clamp 
styles, ¼” or greater All-thread may be 
used as an extension.

6.  Vertical installations must be supported 

every 10 feet (3 meters) or less. 

(Fig.7)

7.  Elbows and Tees are sufficiently supported 

when a bracket is fixed at the female end of 
the connected straight section. (

Fig.7)

 

PP Pipe sections must be disengaged 1/4"-

5/8" per joint (to allow for expansion) and 

sloped 3°(5/8"per ft) back to the appliance 

per 

Fig.6

 for proper condensate flow.

IMPORTANT

Figure 7

ALL-THREAD

WALL STRAP 

(MINIMUM 1PER 

HORIZONTAL PIPE 

SECTION)

LOCKING BANDS 

REQUIRED AT EVERY 

EXHAUST JOINT

MAX 

10FT 

(3m)

8.  Vertical components can be insulated in 

unconditioned space or when ran outside.

9.  Use black UV protected components on 

venting installed on the exterior.

ENCLOSURE  REQUIREMENTS 

Through Rooms: Interior vents shall be 
enclosed where they extend through closets, 
storage areas, occupied spaces, or anyplace 
where the surface of the vent could be 
contacted by persons or combustible materials 
except when installed in the room with the 
appliance. 

 

Summary of Contents for polypro

Page 1: ...PolyPro Installation Instructions PolyPro Single Wall Gas Vent System for Category II IV Gas Burning Appliances...

Page 2: ...egrity of ALL joints upon completion of assembly This venting system must be free to expand and contract under normal operation Assure unrestricted vent movement where required through walls ceilings...

Page 3: ...ATION 4 PERMITS 4 GENERAL INSTALLATION NOTES 4 CLEARANCES TABLE 1 4 CONDENSATE DRAIN 5 EQUIVALENT LENGTH CHART TABLE 2 5 JOINT CONNECTIONS 6 APPLIANCE CONNECTION 6 INSTALLATION 7 ENCLOSURE REQUIREMENT...

Page 4: ...must not be routed into through or within any other vent such as an existing masonry or factory built chimney flue unless that vent or chimney is not being used to vent another appliance and is only u...

Page 5: ...ecified by the appliance manufacturer If specific guidance is not offered by the appliance manufacturer as to Equivalent Vent Lengths EVL for vent components the general guidelines in Table 2 can be u...

Page 6: ...ing Band on male pipe section Fig 2 Insert locking tab into locking band recess rotate button away from Locking Band Clasp insert pipe sections push lock band clamp downward into socket disengage sock...

Page 7: ...rted by the appliance On Duravent and other certain clamp styles or greater All thread may be used as an extension 6 Vertical installations must be supported every 10 feet 3 meters or less Fig 7 7 Elb...

Page 8: ...stops are not required at the roof deck penetration 2 Cut and or frame hole Table 3 3 Slide the two halves together and attach to the ceiling Figure 9 ALIGN TABS WITH MOUNTS GASKET EXTERIOR WALL PLATE...

Page 9: ...N A N A N A TWIN PIPE HORIZONTAL CLASS IIB 7 3 8 x 25 8 187mm x 65mm 8 3 8 x 37 8 212 x 85mm 9 x 43 8 228 x 100mm N A N A N A TWIN PIPE HORIZONTAL CLASS IIC Framing Dimensions 8 x 3 200 x 77mm 8 7 8...

Page 10: ...outside wall 4 Slide cap through exterior wall plate into hole from outside building Cap must not be installed sloped downward 5 Orient termination so air intake slots face down 6 Seal termination to...

Page 11: ...Figure 16 CENTERLINE OF EXHAUST OUTLET OF APPLIANCE Vertical Concentric Fig 17 1 Locate penetration Fig 16 2 Cut hole in roof Table 3 3 Cut hole in ceiling above appliance Cut hole s big enough for p...

Page 12: ...The upper support plate with a flange for B vent and factory built chimney Fig 21 must be affixed to the top of the conduit via screws Anchor bolts must be used when attaching a flat support plate to...

Page 13: ...are exposed to the elements for wear or damage If damage is found the components should be replaced immediately Where possible look into the Termination Cap to verify no foreign material is there to...

Page 14: ...THIS PAGE INTENTIONALLY LEFT BLANK...

Page 15: ...THIS PAGE INTENTIONALLY LEFT BLANK...

Page 16: ...ty This warranty provides no cash surrender value The terms and conditions of this warranty may not be modified altered or waived by any action inaction or representation whether oral or in writing ex...

Reviews: