Figure 2

APPLIANCE CONNECTION:  2" - 4"
1.  If the appliance has a PVC/CPVC female 

outlet use the Appliance Adapter/ PVC 
Adapter and Clamp.  

(Fig.3) 

• 

If the appliance has a PVC/CPVC 
Male outlet use a matching PVC/
CPVC coupling to convert to a 
female outlet.

2.  If the appliance outlet has a rubber 

boot or Fernco-style appliance adapter, 
then the PolyPro vent pipe may attach 
directly to the appliance (

Fig.4

).

3.  If the appliance has a FasNSeal outlet 

then use the FasNSeal to PolyPro 
adapter.

6

Figure 4

APPLIANCE 

OUTLET

POLYPRO 

VENT PIPE

TIGHTEN CLAMPS ON 

RUBBER COUPLER 

ADAPTER OR FERNCO 

STYLE ADAPTER TO 

SECURE VENT 

PIPE TO APPLIANCE

JOINT CONNECTIONS
Verify the gasket is seated evenly inside the 
groove in the female end. 

 

For PP / Metal 

pipe with a locking tab, slide Locking Band 
on male pipe section 

Fig.2

.  Insert locking 

tab into locking band recess, rotate button 
away from Locking Band Clasp, insert pipe 
sections, push lock band clamp downward 
into socket, disengage socket / tab 1/4"-5/8" 
from socket 

Fig.2

.  Screws are not allowed 

for joint connection.  Never penetrate the 

wall of PolyPro vent pipe.  (Exception- a SS 

screw may be used outside the building on 

exterior termination fittings to orient an 

elbow, etc).

• 

IMPORTANT: Locking bands are 

mandatory on all exhaust vent joints

POLYPRO TO DURAVENT / SECURITY 

CHIMNEY METAL VENT CONNECTION
Approved M&G Duravent / Security Chimney 
1738/636 metal vent fittings can be used with 
PolyPro.  Follow the above 

(Fig.2) 

for PolyPro 

(female) to Metal Vent (Male) connections.

Figure 3

POLYPRO PIPE

APPLIANCE 

ADAPTER CLAMP

APPLIANCE ADAPTER/

PVC ADAPTER

APPLIANCE 

EXHAUST OUTLET 

OR  PVC UNION

APPLIANCE 

LOCKING

TAB

LOCKING

BAND RECESS

1/4"

CLICK!

LOCKING

BAND CLASP

VERIFY GASKET IS 

SEATED IN FEMALE 

END OF PIPE

Summary of Contents for polypro

Page 1: ...PolyPro Installation Instructions PolyPro Single Wall Gas Vent System for Category II IV Gas Burning Appliances...

Page 2: ...egrity of ALL joints upon completion of assembly This venting system must be free to expand and contract under normal operation Assure unrestricted vent movement where required through walls ceilings...

Page 3: ...ATION 4 PERMITS 4 GENERAL INSTALLATION NOTES 4 CLEARANCES TABLE 1 4 CONDENSATE DRAIN 5 EQUIVALENT LENGTH CHART TABLE 2 5 JOINT CONNECTIONS 6 APPLIANCE CONNECTION 6 INSTALLATION 7 ENCLOSURE REQUIREMENT...

Page 4: ...must not be routed into through or within any other vent such as an existing masonry or factory built chimney flue unless that vent or chimney is not being used to vent another appliance and is only u...

Page 5: ...ecified by the appliance manufacturer If specific guidance is not offered by the appliance manufacturer as to Equivalent Vent Lengths EVL for vent components the general guidelines in Table 2 can be u...

Page 6: ...ing Band on male pipe section Fig 2 Insert locking tab into locking band recess rotate button away from Locking Band Clasp insert pipe sections push lock band clamp downward into socket disengage sock...

Page 7: ...rted by the appliance On Duravent and other certain clamp styles or greater All thread may be used as an extension 6 Vertical installations must be supported every 10 feet 3 meters or less Fig 7 7 Elb...

Page 8: ...stops are not required at the roof deck penetration 2 Cut and or frame hole Table 3 3 Slide the two halves together and attach to the ceiling Figure 9 ALIGN TABS WITH MOUNTS GASKET EXTERIOR WALL PLATE...

Page 9: ...N A N A N A TWIN PIPE HORIZONTAL CLASS IIB 7 3 8 x 25 8 187mm x 65mm 8 3 8 x 37 8 212 x 85mm 9 x 43 8 228 x 100mm N A N A N A TWIN PIPE HORIZONTAL CLASS IIC Framing Dimensions 8 x 3 200 x 77mm 8 7 8...

Page 10: ...outside wall 4 Slide cap through exterior wall plate into hole from outside building Cap must not be installed sloped downward 5 Orient termination so air intake slots face down 6 Seal termination to...

Page 11: ...Figure 16 CENTERLINE OF EXHAUST OUTLET OF APPLIANCE Vertical Concentric Fig 17 1 Locate penetration Fig 16 2 Cut hole in roof Table 3 3 Cut hole in ceiling above appliance Cut hole s big enough for p...

Page 12: ...The upper support plate with a flange for B vent and factory built chimney Fig 21 must be affixed to the top of the conduit via screws Anchor bolts must be used when attaching a flat support plate to...

Page 13: ...are exposed to the elements for wear or damage If damage is found the components should be replaced immediately Where possible look into the Termination Cap to verify no foreign material is there to...

Page 14: ...THIS PAGE INTENTIONALLY LEFT BLANK...

Page 15: ...THIS PAGE INTENTIONALLY LEFT BLANK...

Page 16: ...ty This warranty provides no cash surrender value The terms and conditions of this warranty may not be modified altered or waived by any action inaction or representation whether oral or in writing ex...

Reviews: