46
12.1 Ratings and Capacities
• Constructed and hydrostatically tested for maximum
allowable working pressure of 50 psig (pounds per
square inch gauge) (345 kPa) in accordance with ASME
Boiler and Pressure Vessel Code, Section IV, Rules for
Construction of Heating Boilers.
• Ratings used for elevations up to 2000 ft (600m) above
sea level.
• For elevations between 2000 ft (600m) and 4500 ft
(1350m), install high altitude control kit
• For elevations above 4500 ft (1350m) install high
altitude control kit and :
• USA - Reduce input rate 4% for each 1000 ft
(300m) beyond 4500 ft.
• Canada - Contact Provincial authority having
jurisdiction for installations above 4500 feet (1350
m) above sea level.
TABLE 12-1: SEA LEVEL RATINGS
NATURAL AND PROPANE GASES
Size
Boiler Input Rate (MBH)
(1)
Heating Capacity
(MBH)
(1)(2)
Net AHRI Rating,
Water (MBH)
(1)(3)
AFUE
(2)
Maximum
Minimum
050
50
10
46
40
95.0
075
75
15
69
60
95.0
100
100
20
91
79
95.0
150
150
30
139
121
95.0
200
200
40
185
161
94.0
299
299
60
273
239
94.0
(1)
1000
Btu/hr (British Thermal Units Per Hour)
(2)
Heating Capacity and AFUE (Annual Fuel Utilization Effi ciency) are based on DOE (Department of Energy) test
procedures.
(3)
Net AHRI Ratings based on piping and pickup allowance of 1.15. Contact Technical Support before selecting boiler for
installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems,
etc.
12 - RATINGS AND CAPACITIES
Summary of Contents for DKVLT-050
Page 47: ...47 13 TROUBLE SHOOTING ...
Page 51: ...51 13 TROUBLE SHOOTING ...
Page 53: ...53 13 TROUBLE SHOOTING ...
Page 62: ...62 Supply Water Temperature Sensor Resistance Chart 13 TROUBLE SHOOTING ...
Page 64: ...64 14 WIRING DIAGRAM 14 1 Connection Diagram 050 075 100 150 200 MBH ...
Page 83: ...83 NOTES ...
Page 84: ...ECR International Inc 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com ...