39
Gas
CO
2
CO
Min.
Max.
Natural Gas
9.0
9.5
<100ppm
Propane
10.0
11.0
<150ppm
NOTICE
Contact Technical Support @ 800-325-5479 for
additional information or assistance.
Natural Gas only**
1.
Measure input. Compare to table above. Continue
to measure input and CO
2
until both measured
values are within range speci
fi
ed in tables
.
Propane Gas
Most propane systems do not have
fl
ow meters.
1.
Check CO
2
. Propane should be between 10% and
11.0%.
• If CO
2
is low increase gas
fl
ow following
fi
gure
9-3 & 9-4.
• If CO
2
is high decrease gas
fl
ow following
fi
gure 9-3
& 9-4.
FIGURE 9-3 Gas Valve - Models
050/075/100/150/200 MBH
• To increase gas
fl
ow turn 'throttle' left or counter
clockwise
.
• To decrease gas
fl
ow turn 'throttle' right or
clockwise
.
• Limit adjustment to one turn and retest.
FIGURE 9-4 Gas Valve - Model 299 MBH
• To increase gas
fl
ow turn 'throttle' left or counter
clockwise
.
• To decrease gas
fl
ow turn 'throttle' right or
clockwise
.
• Limit adjustment to one turn and retest.
Verify Burner, Proper Operation
1.
Inspect burner
fl
ame through Sight Glass. See
fi
gure 11-1 & 11-2.
2.
Operate boiler through several heating cycles,
including domestic hot water, if used. Verify proper
operation.
9 - START UP PROCEDURE
Summary of Contents for DKVLT-050
Page 47: ...47 13 TROUBLE SHOOTING ...
Page 51: ...51 13 TROUBLE SHOOTING ...
Page 53: ...53 13 TROUBLE SHOOTING ...
Page 62: ...62 Supply Water Temperature Sensor Resistance Chart 13 TROUBLE SHOOTING ...
Page 64: ...64 14 WIRING DIAGRAM 14 1 Connection Diagram 050 075 100 150 200 MBH ...
Page 83: ...83 NOTES ...
Page 84: ...ECR International Inc 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com ...