44
Figure 11-3 Condensate Trap - 050,075,100,150,200
Flue Pipe
Temperature
Sensor
Hose Barb w/Cap
Coupling
Condensate Collector
Condensate
Trap Connection
To Condensate
Collector
Flexible Gas Line
11.2 Annual Shut Down Procedure
• Follow instructions “To Turn Off Gas To Appliance”
unless
boiler is also used to supply domestic hot water. See
section 10.
• Drain system completely if system does not have
antifreeze when heating system is to remain out of
service during freezing weather.
• Drain condensate lines when boiler is to be exposed to
freezing temperatures.
WARNING
Following service procedures must be performed
by quali
fi
ed service agent. Boiler owner shall not
attempt these steps. Failure to do so could result in
death or serious injury.
!
11.3 Annual Inspection and Cleaning of Boiler
Components
• Obtain Burner Inspection Kit. Follow kit instructions to
prepare for examination and cleaning.
• Burner and heat exchanger inspection and cleaning.
• Remove gasket and burner. Allow burner to clear top
lip of chassis.
• Remove any residual sleeve and/or gasket material
from removed burner.
• Clean burner using air hose directed into top of
burner opening to dislodge any debris in burner ports.
Inspect burner for foreign matter in
fl
ame ports or
inside burner. Remove foreign matter by blowing with
compressed air or vacuuming. Replace burner if it
cannot be cleaned or is showing deterioration.
• Clean heat exchanger with low pressure water spray.
Use
fl
exible handle nylon brush to loosen sediment
and oxide on all accessible heating surfaces of heat
exchanger. Take care not to get brush stuck in heat
exchanger.
• Remove any remaining loosened sediment using shop
vacuum with snorkel attachment.
• Clean condensate collector if signi
fi
cant debris found in
heat exchanger.
• Expand upper spring tension clip of condensate trap
using hose clamp pliers. Disconnect condensate trap
from condensate collector. See
fi
gures 11-3 & 11-4.
• Disconnect wire harness from vent temperature
sensor. See
fi
gure 11-3 .
• Loosen upper hose clamp securing condensate
collector to
fl
ue pipe using 3/8" socket with 6"
extension.
Figure 11-4 Condensate Trap - 299
11 - GENERAL MAINTENANCE AND CLEANING
Condensate Trap Connection
To Condensate Collector
Flexible Gas Line
Condensate Collector
C
Summary of Contents for DKVLT-050
Page 47: ...47 13 TROUBLE SHOOTING ...
Page 51: ...51 13 TROUBLE SHOOTING ...
Page 53: ...53 13 TROUBLE SHOOTING ...
Page 62: ...62 Supply Water Temperature Sensor Resistance Chart 13 TROUBLE SHOOTING ...
Page 64: ...64 14 WIRING DIAGRAM 14 1 Connection Diagram 050 075 100 150 200 MBH ...
Page 83: ...83 NOTES ...
Page 84: ...ECR International Inc 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com ...