Domino

DFDALI

Technical characteristics

Supply voltage 

Domino

 bus 

side

By specific centralized power 
supply mod. DFPW2

Supply voltage DALI bus 
side

12V~ (at full load) 3VA MIN, or 
12V 

 ±5% 0.25A MIN

Current consumption on

Domino

 bus side

Equal to 2 standard 

Domino

modules

MAX current consumption 
DALI bus side

0.25A at 12V 

 , 3VA at 12V~

Number of managed DALI 
devices

32 MAX

Number of generic
commands

58 (I/V Table)

Operating temperature

-5 

÷

 +50 

°

C

Storage temperature

-20 

÷

 +70 

°

C

Protection degree

IP20

Outline dimensions

9

0c

m

58mm

71mm

DUEMMEGI

MILANO-ITALY

ADDRESS

DFDALI

+

Domino

P

A

T

E

N

T

E

D

D

A

+

OUT

DALI

SUPPLY

+ _

BUS

D

A

-

IN

Correct disposal of this product

(Waste Electrical & Electronic Equipment)
(Applicable   in   the   European   Union   and   other 
European  countries  with  separate  collection  sys-
tems). This marking on the product, accessories or 
literature indicates that the product should not be 
disposed of with other household waste at the end 
of their working life. To prevent possible harm to 

the environment or human health from uncontrolled waste dispos-
al, please separate these items from other types of waste and re-
cycle them responsibly to promote the sustainable reuse of materi-
al resources. Household  users  should  contact either  the retailer 
where they purchased this product, or their local government of-
fice, for details of where and how they can take these items for en-
vironmentally   safe  recycling.   This  product   and  its   electronic   ac-
cessories should not be mixed with other commercial wastes for 
disposal.

Installation and use restrictions

Standards and regulations

The design and the setting up of electrical systems must be per-
formed according to the relevant standards, guidelines, specifica-
tions and regulations of the relevant country. The installation, con-
figuration and programming of the devices must be carried out by 
trained personnel.
The   installation   and   the   wiring   of   the   bus   line   and   the   related 
devices must be performed according to the recommendations of 
the   manufacturers   (reported   on   the   specific   data   sheet   of   the 
product) and according to the applicable standards.
All the relevant safety regulations, e.g. accident prevention regula-
tions, law on technical work equipment, must also be observed.

Safety instructions

Protect the unit against moisture, dirt and any kind of damage dur-
ing transport, storage and operation. Do not operate the unit out-
side the specified technical data.
Never open the housing. If not otherwise specified, install in closed 
housing (e.g. distribution cabinet). Earth the unit at the terminals 
provided, if existing, for this purpose. Do not obstruct cooling of the 
units. Keep out of the reach of children.

Setting up

The physical address assignment and the setting of parameters (if 
any) must be performed by the specific softwares provided togeth-
er the device or by the specific programmer. For the first installa-
tion of the device proceed according to the following guidelines:

Check that any voltage supplying the plant has been removed

Assign the address to module (if any)

Install  and  wire the device according  to the schematic  dia-
grams on the specific data sheet of the product

Only then switch on the 230Vac supplying the bus power sup-
ply and the other related circuits

Applied standards

This device complies with the essential requirements of the follow-
ing directives:
2004/108/CE (EMC)
2006/95/CE (Low Voltage)
2002/95/CE (RoHS)

Note

Technical characteristics and this data sheet are subject to change 
without notice.

DUEMMEGI

 s.r.l. - Via Longhena, 4 - 20139 MILANO

Tel. 02/57300377 - Fax 02/55213686 – 

www.duemmegi.it

Rel.: 2.1 May 2013

Page 11 of 11

HOME AND BUILDING AUTOMATION

Summary of Contents for Domino DFDALI

Page 1: ...ecalling of sceneries can be accomplished by the module The power supply needed for DFDALI module operation is derived from the Domino bus itself and from an auxiliary power supply for the DALI section Three fixed 2 way terminal block allow the connection of the module to the Domino bus to the auxiliary power sup ply and to the DALI bus Near to the Domino bus terminal block the module fea tures a ...

Page 2: ... bus 1 output address and if enabled 1 input address The meaning of the data field of the two sections will be described in the following Input section On the input address if enabled 16 bits are available for the diagnostics of DALI system as described in the follow ing table Point Description 1 Current brightness or Regulation Status of the 8 zones 2 3 4 5 6 7 8 9 10 11 Polling disabled 12 Power...

Page 3: ... HEX DEC 0x00 0x64 0 100 Set the brightness to 0 100 according to the current ramp 0x70 112 Disable polling 0x71 113 Enable polling 0x7D 125 Up command without one touch function 0x7E 126 Down command without one touch function 0x7F 127 Single command without one touch function 0x80 128 No operation in this case the value of the destination must be zero 0x87 135 Set the current brightness a MIN va...

Page 4: ...easing of the buttons A similar example follows to send command to a group of ballasts V1 I1 1 I1 2 I1 3 AO2 P 0x8180 V1 P 0x817D I1 1 P 0x817E I1 2 P 0x8132 I1 3 The specified value at each variation will be transferred to the DALI devices assigned to group 1 At the releasing of each pushbutton the value is always set to 0x8180 no operation but needed to inform the module about the re leasing of ...

Page 5: ...m the menu of DCP IDE or BDTools From the menu select Programming Modules Configura tion and then DFDALI The window shown in Figure 2 will be opened the main parameters and options can be here defined as it will be described in the following of this para graph Before to proceed with any action the communication between the PC and for instance DFCP has to be opened The top side of the configuration...

Page 6: ...d to the line and for a single ballast Restoring of the settings does not imply the reset of the ballast address The visible result of the factory setting restoring is the switching on of the lamps at the bus failure default level that is typically 100 Mapping Once the ballasts have been random addressed it can be useful to reorder the assigned addresses thus simplifying the supervision and the ma...

Page 7: ... 2 the bal lasts 1 3 and the group 3 the ballasts 2 4 5 The button Deselect remove all the X symbols on the grid The execution of the assignment of the groups clicking on the button Start will take in account only the ballast selec ted by the X symbol A timer icon will inform that the opera tion is running At the end of the procedure the normal mouse icon will be restored If the procedure has not ...

Page 8: ...e to be recalled by ballasts during failure of Domino and or DALI bus Ramp the ramp value in seconds Preset writing a value 0 to 100 and clicking on the button on the right side the brightness will be forced to that value M1 M16 the value to be loaded into the 16 presets the button on the right side allows to recall the related preset stored into the ballast DUEMMEGI s r l Via Longhena 4 20139 MIL...

Page 9: ...ontroller and any program ming To compile the table left click with the mouse on the first available cell on the Input column enter address and point without I or V with if needed and press Enter The command list will appear choose the desired function among Mono Up Down Recall Save the other two op tions are related to the automatic bright ness regulation see next paragraph The cell of the column...

Page 10: ...to be sent to the ballasts In practice larger values of K increase the speed of the approaching to the set point Small values of K allow for greater stability of the regulation but a slower response while large values of K make the re sponse faster but some oscillations can appear Start Value is the value from which the regulation starts when it is activated The Auto options when checked place tha...

Page 11: ...gulations of the relevant country The installation con figuration and programming of the devices must be carried out by trained personnel The installation and the wiring of the bus line and the related devices must be performed according to the recommendations of the manufacturers reported on the specific data sheet of the product and according to the applicable standards All the relevant safety r...

Reviews: