It is suggested to use, for the DALI line, a normal 2-core 
cable with double insulation. It's allowed to lay these cables 
in the same pipe in which there are power cables, provided 
that they have double isolation too.

It is recommended to avoid the using of multi core cables 
carrying both the two DALI signals and ballast supply, be-
cause the capacitive coupling between the signal wires and 
the power lines may cause very dangerous conditions for 
the human safety.

The   following   table   gives   some   rules   for   the   MINIMUM 
cable   section.   As   said   above,   no   special   cables   are   re-
quired for the DALI line, provided that they have double in-
sulation. In any case, the distance between DFDALI mod-
ule and the farthest ballast must not be more than 300m.

Connection

Suggested cable

Domino

  bus

2 x 0.8 mmq unshielded

DALI SUPPLY

1 mmq (if the power supply is near 
to the module)

DALI line

Up to120m: 2 x 0.50mmq
Up to 175m: 2 x 0.75mmq
Up to 230m: 2 x 1.00mmq
Up to 300m: 2 x 1.50mmq

Information on the bus

DFDALI  takes,  inside the  

Domino

  bus,  1 output  address 

and, if enabled, 1 input address. The meaning of the data 
field of the two sections will be described in the following.

Input section

On the input address, if enabled, 16 bits are available for 
the diagnostics of DALI system, as described in the follow-
ing table:

Point

Description

1

Current brightness

or

Regulation Status of the 8 zones

2
3
4
5
6
7
8
9

-

10

-

11

Polling disabled

12

Power supply loss on DALI side

13

Test button pressed

14

Lamp failure

15

DALI line broken

16

DALI line short circuit

The first available information (points  1

÷

8 of the channel) 

can be chosen by the option “Regulation Status” in the con-
figuration panel featured by DCP IDE or BDTools; the two 
possibilities are:

Case 1(unchecked option):

the brightness level of the ballast having address 1 which is 
assumed as reference for all the other ballasts. Thus, to 
use this function, the ballasts have to be addressed starting 
from address 1.

DUEMMEGI

 s.r.l. - Via Longhena, 4 - 20139 MILANO

Tel. 02/57300377 - Fax 02/55213686 – 

www.duemmegi.it

Rel.: 2.1 May 2013

Page 2 of 11

HOME AND BUILDING AUTOMATION

+

BUS

_

DUEMMEGI

MILANO-ITALY

ADDRESS

DFDALI

+

_

Domino

P

A

T

E

N

T

E

D

D

A

+

OUT

DALI

SUPPLY

AUX

SUPPLY

12V~ 

12V=

 

DALI

32

DALI

1

+ _

BUS

D

A

-

IN

Figure 1: DFDALI wiring diagram

Summary of Contents for Domino DFDALI

Page 1: ...ecalling of sceneries can be accomplished by the module The power supply needed for DFDALI module operation is derived from the Domino bus itself and from an auxiliary power supply for the DALI section Three fixed 2 way terminal block allow the connection of the module to the Domino bus to the auxiliary power sup ply and to the DALI bus Near to the Domino bus terminal block the module fea tures a ...

Page 2: ... bus 1 output address and if enabled 1 input address The meaning of the data field of the two sections will be described in the following Input section On the input address if enabled 16 bits are available for the diagnostics of DALI system as described in the follow ing table Point Description 1 Current brightness or Regulation Status of the 8 zones 2 3 4 5 6 7 8 9 10 11 Polling disabled 12 Power...

Page 3: ... HEX DEC 0x00 0x64 0 100 Set the brightness to 0 100 according to the current ramp 0x70 112 Disable polling 0x71 113 Enable polling 0x7D 125 Up command without one touch function 0x7E 126 Down command without one touch function 0x7F 127 Single command without one touch function 0x80 128 No operation in this case the value of the destination must be zero 0x87 135 Set the current brightness a MIN va...

Page 4: ...easing of the buttons A similar example follows to send command to a group of ballasts V1 I1 1 I1 2 I1 3 AO2 P 0x8180 V1 P 0x817D I1 1 P 0x817E I1 2 P 0x8132 I1 3 The specified value at each variation will be transferred to the DALI devices assigned to group 1 At the releasing of each pushbutton the value is always set to 0x8180 no operation but needed to inform the module about the re leasing of ...

Page 5: ...m the menu of DCP IDE or BDTools From the menu select Programming Modules Configura tion and then DFDALI The window shown in Figure 2 will be opened the main parameters and options can be here defined as it will be described in the following of this para graph Before to proceed with any action the communication between the PC and for instance DFCP has to be opened The top side of the configuration...

Page 6: ...d to the line and for a single ballast Restoring of the settings does not imply the reset of the ballast address The visible result of the factory setting restoring is the switching on of the lamps at the bus failure default level that is typically 100 Mapping Once the ballasts have been random addressed it can be useful to reorder the assigned addresses thus simplifying the supervision and the ma...

Page 7: ... 2 the bal lasts 1 3 and the group 3 the ballasts 2 4 5 The button Deselect remove all the X symbols on the grid The execution of the assignment of the groups clicking on the button Start will take in account only the ballast selec ted by the X symbol A timer icon will inform that the opera tion is running At the end of the procedure the normal mouse icon will be restored If the procedure has not ...

Page 8: ...e to be recalled by ballasts during failure of Domino and or DALI bus Ramp the ramp value in seconds Preset writing a value 0 to 100 and clicking on the button on the right side the brightness will be forced to that value M1 M16 the value to be loaded into the 16 presets the button on the right side allows to recall the related preset stored into the ballast DUEMMEGI s r l Via Longhena 4 20139 MIL...

Page 9: ...ontroller and any program ming To compile the table left click with the mouse on the first available cell on the Input column enter address and point without I or V with if needed and press Enter The command list will appear choose the desired function among Mono Up Down Recall Save the other two op tions are related to the automatic bright ness regulation see next paragraph The cell of the column...

Page 10: ...to be sent to the ballasts In practice larger values of K increase the speed of the approaching to the set point Small values of K allow for greater stability of the regulation but a slower response while large values of K make the re sponse faster but some oscillations can appear Start Value is the value from which the regulation starts when it is activated The Auto options when checked place tha...

Page 11: ...gulations of the relevant country The installation con figuration and programming of the devices must be carried out by trained personnel The installation and the wiring of the bus line and the related devices must be performed according to the recommendations of the manufacturers reported on the specific data sheet of the product and according to the applicable standards All the relevant safety r...

Reviews: