Domino

DFDALI

Enter   the   desired  parameters   and   then  click   on   Start   to 
send the configuration. The time required by this procedure 
is about 15 seconds.
If   the   procedure   has   not   been   successfully   executed,   a 
warning window will be shown; in this case the procedure 
has to be repeated.

Status

This TAB, Figure 6, shows, if the ballasts have been ad-
dressed, the current brightness level of each ballast. These 
values are in the range 1 to 100; when a ballast does not 
answer to the polling, the reported value will be 255 (and 
the table will show “-”).
If a lamp failure occurs, a X symbol on a pink background 
will be shown.
In addition it is possible to force the brightness entering the 
value in the cell related to the desired device and confirm-
ing by the Enter key.
A pair of buttons on the top side of the table allow to enable 
and disable the polling on the DALI line. When the polling is 
disabled, the label “Base address” will be shown over a red 
background.
The buttons “Snapshot to File” and “Restore from File” al-
low respectively to save and recall a given configuration  of 
brightness levels; in this way it is possible to save on the 
PC one or more sceneries (each scenery will be a file).

I/V Table

The TAB shown in Figure 7 allows to create up to 58 rela-
tionship between real or virtual inputs of the  

Domino

  bus 

and the following commands: Up, Down, Single Command, 
Save   scenery   and   Recall   scenery.   For   each   command 
simply enter the input point (without I or V, with ! if negation 
is required), the function and the channel or the scenery.

These functions are managed directly by DFDALI module, 
thus without the need of any controller and any program-
ming.
To compile the table, left click with the mouse on the first 
available cell on the Input column, enter address and point 
(without I or V, with ! if needed) and press 
Enter.   The   command   list   will   appear: 
choose the desired function among Mono, 
Up, Down, Recall, Save; the other two op-
tions   are   related   to   the   automatic   bright-
ness  regulation,   see   next   paragraph.   The 
cell of the column Cmd will then show the 
symbol of the chosen function; to change 
the function, simply click again on the cell.
Select the desired function; the cell of the column Cmd will 
then show the symbol of the chosen function (U, D, M, R, 
S); to change the function, simply click again on the cell. 
The next cell on the column B/G (Broadcast or Group) will 
be then automatically highlighted: enter the desired value, 
that is 0 for Broadcast or the desired group number number 
1 to 15 (

note: group 16 cannot be used in the I/V table

) and 

press Enter.  If instead the desired function is Save or Re-
call scenery, press Enter again: the related cell will be auto-
matically highlighted in the column S (Scenery): enter the 
desire number, that is the number of the scenery (1 to 16) 
to be saved or recalled, then press Enter.
The buttons Start Prog. and Start Read. in the I/V Table 
TAB   allow,   respectively,   to   transfer   the   values   currently 
shown in the I/V Table to DFDALI module and read the cur-
rent configuration of DFDALI and report it into the table.

The buttons   From File and To File allow, respectively, to 
open   a   file,   with   .TIV   extension,   containing   a   previously 
saved I/V table and to save the I/V table shown in the win-
dow to a file. The Default button clears the table.

DUEMMEGI

 s.r.l. - Via Longhena, 4 - 20139 MILANO

Tel. 02/57300377 - Fax 02/55213686 – 

www.duemmegi.it

Rel.: 2.1 May 2013

Page 9 of 11

HOME AND BUILDING AUTOMATION

Figure 7: I/V Table

Summary of Contents for Domino DFDALI

Page 1: ...ecalling of sceneries can be accomplished by the module The power supply needed for DFDALI module operation is derived from the Domino bus itself and from an auxiliary power supply for the DALI section Three fixed 2 way terminal block allow the connection of the module to the Domino bus to the auxiliary power sup ply and to the DALI bus Near to the Domino bus terminal block the module fea tures a ...

Page 2: ... bus 1 output address and if enabled 1 input address The meaning of the data field of the two sections will be described in the following Input section On the input address if enabled 16 bits are available for the diagnostics of DALI system as described in the follow ing table Point Description 1 Current brightness or Regulation Status of the 8 zones 2 3 4 5 6 7 8 9 10 11 Polling disabled 12 Power...

Page 3: ... HEX DEC 0x00 0x64 0 100 Set the brightness to 0 100 according to the current ramp 0x70 112 Disable polling 0x71 113 Enable polling 0x7D 125 Up command without one touch function 0x7E 126 Down command without one touch function 0x7F 127 Single command without one touch function 0x80 128 No operation in this case the value of the destination must be zero 0x87 135 Set the current brightness a MIN va...

Page 4: ...easing of the buttons A similar example follows to send command to a group of ballasts V1 I1 1 I1 2 I1 3 AO2 P 0x8180 V1 P 0x817D I1 1 P 0x817E I1 2 P 0x8132 I1 3 The specified value at each variation will be transferred to the DALI devices assigned to group 1 At the releasing of each pushbutton the value is always set to 0x8180 no operation but needed to inform the module about the re leasing of ...

Page 5: ...m the menu of DCP IDE or BDTools From the menu select Programming Modules Configura tion and then DFDALI The window shown in Figure 2 will be opened the main parameters and options can be here defined as it will be described in the following of this para graph Before to proceed with any action the communication between the PC and for instance DFCP has to be opened The top side of the configuration...

Page 6: ...d to the line and for a single ballast Restoring of the settings does not imply the reset of the ballast address The visible result of the factory setting restoring is the switching on of the lamps at the bus failure default level that is typically 100 Mapping Once the ballasts have been random addressed it can be useful to reorder the assigned addresses thus simplifying the supervision and the ma...

Page 7: ... 2 the bal lasts 1 3 and the group 3 the ballasts 2 4 5 The button Deselect remove all the X symbols on the grid The execution of the assignment of the groups clicking on the button Start will take in account only the ballast selec ted by the X symbol A timer icon will inform that the opera tion is running At the end of the procedure the normal mouse icon will be restored If the procedure has not ...

Page 8: ...e to be recalled by ballasts during failure of Domino and or DALI bus Ramp the ramp value in seconds Preset writing a value 0 to 100 and clicking on the button on the right side the brightness will be forced to that value M1 M16 the value to be loaded into the 16 presets the button on the right side allows to recall the related preset stored into the ballast DUEMMEGI s r l Via Longhena 4 20139 MIL...

Page 9: ...ontroller and any program ming To compile the table left click with the mouse on the first available cell on the Input column enter address and point without I or V with if needed and press Enter The command list will appear choose the desired function among Mono Up Down Recall Save the other two op tions are related to the automatic bright ness regulation see next paragraph The cell of the column...

Page 10: ...to be sent to the ballasts In practice larger values of K increase the speed of the approaching to the set point Small values of K allow for greater stability of the regulation but a slower response while large values of K make the re sponse faster but some oscillations can appear Start Value is the value from which the regulation starts when it is activated The Auto options when checked place tha...

Page 11: ...gulations of the relevant country The installation con figuration and programming of the devices must be carried out by trained personnel The installation and the wiring of the bus line and the related devices must be performed according to the recommendations of the manufacturers reported on the specific data sheet of the product and according to the applicable standards All the relevant safety r...

Reviews: