background image

Domino

DFDALI

Addressing

3 mutually exclusive functions are available:

Set address.

 In the first case, an address will be assigned 

to all the connected ballasts, and the starting address can 
be chosen (the typical value is 1).
This type of addressing assigns consecutive values, in the 
range 1 to 32, to the ballasts in a random order.
If   some   ballasts   on   the   line   have   been   previously   ad-
dressed and some other ballasts have to be added, the ad-
dressing procedure can be performed without any modifica-
tion to  the  previously assigned addresses.   Mainly in this 
case, a starting address other than 1 can be useful. A timer 
icon will inform that the operation is running. 

At the end of the procedure, the normal mouse icon will be 
restored. The time required for this procedure is about:

T = 5sec + (6sec x “nr. of ballasts”)

Remove the address.

 If some addressing or reconfiguration 

errors occurred, it can be useful removing the address of all 
the ballasts on the line or of a well specified ballast.

Restore the factory setting.

  The DALI ballasts are factory 

set without any address and with a basic configuration for 
the main parameters; the following table shows a typical 
default configuration:

Parameter

Value

Minimum brightness level

1%

Maximum brightness level

100%

Brightness level in failure condi-
tions

100%

Ramp value

0 seconds

Preset

None

These settings can be restored both for all ballasts connec-
ted to the line and for a single ballast.

Restoring of the settings does not imply the reset of the 
ballast   address.   The   visible   result   of   the   factory   setting 
restoring is the switching on of the lamps at the bus failure 
default level,  that is typically 100%.

Mapping

Once the ballasts have been random addressed, it can be 
useful to reorder the assigned addresses, thus simplifying 
the supervision and the management of ballasts, Figure 3.
The address 1 to 32 of each ballast can be changed to a 
new desired value (always in the range 1 to 32). For each 
address, the program shows a line similar to the following 
one: 

.

The button 0 allows to switch off the ballast with address 
specified in the gray text box (1 in this example) while the 
button I allows the switching on; this function is useful to 
see   where   the   ballast   addressed   1   (in   this   example)   is 
physically located. In the white text box the new desired ad-
dress must be entered (23 in this example) for the ballast 
whose current address is 1.

The execution of the mapping procedure (pressing the but-
ton Start) will take place only for the ballasts selected by 
the related checkbox. A timer icon will inform that the oper-
ation is running. At the end of the procedure, the normal 
mouse icon will be restored. The time require by the map-
ping procedure is about 1sec per ballast.
If the procedure has not been successfully executed, a win-
dow reporting “Error during mapping” will appear.

DUEMMEGI

 s.r.l. - Via Longhena, 4 - 20139 MILANO

Tel. 02/57300377 - Fax 02/55213686 – 

www.duemmegi.it

Rel.: 2.1 May 2013

Page 6 of 11

HOME AND BUILDING AUTOMATION

Figure 3: Mapping

Summary of Contents for Domino DFDALI

Page 1: ...ecalling of sceneries can be accomplished by the module The power supply needed for DFDALI module operation is derived from the Domino bus itself and from an auxiliary power supply for the DALI section Three fixed 2 way terminal block allow the connection of the module to the Domino bus to the auxiliary power sup ply and to the DALI bus Near to the Domino bus terminal block the module fea tures a ...

Page 2: ... bus 1 output address and if enabled 1 input address The meaning of the data field of the two sections will be described in the following Input section On the input address if enabled 16 bits are available for the diagnostics of DALI system as described in the follow ing table Point Description 1 Current brightness or Regulation Status of the 8 zones 2 3 4 5 6 7 8 9 10 11 Polling disabled 12 Power...

Page 3: ... HEX DEC 0x00 0x64 0 100 Set the brightness to 0 100 according to the current ramp 0x70 112 Disable polling 0x71 113 Enable polling 0x7D 125 Up command without one touch function 0x7E 126 Down command without one touch function 0x7F 127 Single command without one touch function 0x80 128 No operation in this case the value of the destination must be zero 0x87 135 Set the current brightness a MIN va...

Page 4: ...easing of the buttons A similar example follows to send command to a group of ballasts V1 I1 1 I1 2 I1 3 AO2 P 0x8180 V1 P 0x817D I1 1 P 0x817E I1 2 P 0x8132 I1 3 The specified value at each variation will be transferred to the DALI devices assigned to group 1 At the releasing of each pushbutton the value is always set to 0x8180 no operation but needed to inform the module about the re leasing of ...

Page 5: ...m the menu of DCP IDE or BDTools From the menu select Programming Modules Configura tion and then DFDALI The window shown in Figure 2 will be opened the main parameters and options can be here defined as it will be described in the following of this para graph Before to proceed with any action the communication between the PC and for instance DFCP has to be opened The top side of the configuration...

Page 6: ...d to the line and for a single ballast Restoring of the settings does not imply the reset of the ballast address The visible result of the factory setting restoring is the switching on of the lamps at the bus failure default level that is typically 100 Mapping Once the ballasts have been random addressed it can be useful to reorder the assigned addresses thus simplifying the supervision and the ma...

Page 7: ... 2 the bal lasts 1 3 and the group 3 the ballasts 2 4 5 The button Deselect remove all the X symbols on the grid The execution of the assignment of the groups clicking on the button Start will take in account only the ballast selec ted by the X symbol A timer icon will inform that the opera tion is running At the end of the procedure the normal mouse icon will be restored If the procedure has not ...

Page 8: ...e to be recalled by ballasts during failure of Domino and or DALI bus Ramp the ramp value in seconds Preset writing a value 0 to 100 and clicking on the button on the right side the brightness will be forced to that value M1 M16 the value to be loaded into the 16 presets the button on the right side allows to recall the related preset stored into the ballast DUEMMEGI s r l Via Longhena 4 20139 MIL...

Page 9: ...ontroller and any program ming To compile the table left click with the mouse on the first available cell on the Input column enter address and point without I or V with if needed and press Enter The command list will appear choose the desired function among Mono Up Down Recall Save the other two op tions are related to the automatic bright ness regulation see next paragraph The cell of the column...

Page 10: ...to be sent to the ballasts In practice larger values of K increase the speed of the approaching to the set point Small values of K allow for greater stability of the regulation but a slower response while large values of K make the re sponse faster but some oscillations can appear Start Value is the value from which the regulation starts when it is activated The Auto options when checked place tha...

Page 11: ...gulations of the relevant country The installation con figuration and programming of the devices must be carried out by trained personnel The installation and the wiring of the bus line and the related devices must be performed according to the recommendations of the manufacturers reported on the specific data sheet of the product and according to the applicable standards All the relevant safety r...

Reviews: