2

NOTE: T-Link TL250 zone events are transmitted using the standard T-Link SIA protocol. DVACS generated
events are transmitted using the DVACS protocol.

NOTE: DVACS Mode 5 is used in ULC listed installations.

DVACS is a registered trademark of Electro Arts Ltd. Scarborough Ontario, Canada.

1.2

Specifications/Requirements

The typical allowable current draw from a compatible DSC panel on the Aux terminal output is
500mA @ 12V

DC

 (for specific current draw please refer to the compatible control panel Instal-

lation Manual). For the operational current draw of the TL250/TL300 refer to Specifications
below. The T-Link TL250/TL300 modules also have 2 switched negative programmable out-
puts (50mA @ 12 V

DC

, each). 

NOTE: For UL listed fire installations, shared on-premises communication equipment is required to be UL
Listed for Information Technology Equipment. The communication medium between protected property and
communications service provider must be for the exclusive use of the protected property and not shared with
other communications service provider subscriber.

NOTE: When a hub or router/gateway is used on the premises with the T-Link TL250, 24-hr. standby power is
required for these devices (i.e., UL listed UPS, battery backup).

NOTE: It is the installers responsibility to ensure proper bonding between the METALLIC ENCLOSURES of
the ALARM CONTROLLER and the TL250/TL300.

ATTENTION: This equipment (T-Link TL250) shall be installed and used within an environment that pro-
vides the Pollution Degree Max. 2 and Overvoltages Category II non-hazardous locations, indoor only. The
equipment must be fixed and permanently connected, and is intended to be installed by service persons (i.e.,
having the appropriate technical training and experience necessary to be aware of hazards which that person
may be exposed to in performing the task, and of measures to minimize the risks to that person or other per-
sons).

CAUTION

Ethernet communication lines must be connected to an approved (acceptable to local authorities) type NID
(Network Interface Device) before leaving the premises (e.g., UL installations, UL60950 Listed NID).

Specifications

Input Voltage:

  12 V

DC

Hardware Revision 05 or higher 

(

INPUT

 

TERMINAL

 

LABELLED

 + 

AND

 - )

:

  12 - 24 V

DC

Input Current:  

T-Link TL250 Max current draw: 275mA

T-Link TL300 Max current draw: 360mA

Dimensions:

 3.25” × 8.7” (8.3 cm × 22cm)

Operating Temperature:

 32°-122°F (0°-49°C)

Output Protocols:

 UDP/IP 10/100 BaseT half duplex, TCP/IP for Console and DLS communications

Input Protocols:

 PC-Link (SIA format), DVACS (V1.10 and higher), Contact ID protocol. (TL300 Only)

Digital Inputs:

 4-digital inputs (can be increased to 12 using the PC5108)

Connectors:

 4-pin header for the PC-Link and RJ-45 for Ethernet, DVACS adaptor (DVACS kit only)

Programming:

 Panel keypad, console on the RS232 or remote T-Link console 

Network:

 Ethernet LAN/WAN 10 BaseT or 10/100 BaseT

E-mail:

 Sends alarm messages to maximum 2 E-mail addresses (not available for DVACS installations)

Downloading Support for DSC Panels: 

 

DLS 2002 and DLS 4 PC1616/1832/1864 version 4.2 only

Multiple Central Stations:

 Primary & backup via phone line* (not available for DVACS installations)

Call Direction Options:

 Primary or backup communicator using panel call direction  (available for 

DVACS installations)

Approval Listings:

 FCC, IC, CE, CSFM

UL (Central Station and Police Connect with Standard or Encrypted Line Security)

ULC (Active and Passive Fire Monitoring, Burglary Signal Channel Security Level A1-A4)

Summary of Contents for T-LINK TL250

Page 1: ...T Link TL250 TL300 Network Internet Alarm Communicator Software Version 1 5 Installation Manual...

Page 2: ...may not properly alert occupants of a fire for a number of reasons some of which follow The smoke detectors may have been improperly installed or positioned Smoke may not be able to reach the smoke d...

Page 3: ...stallation 9 6 2 DVACS Events 9 Section 7 TL300 Telephone Simulation 11 7 1 TL300 Panel Installation 11 7 2 T Link TL300 Operation 11 Section 8 T Link TL250 TL300 Operation 12 8 1 Remote Control 12 8...

Page 4: ...rovided the recipient agrees to the terms of thisEULA IftheSOFTWAREPRODUCTisanupgrade anytransfermustalso includeallpriorversionsof the SOFTWARE PRODUCT f Termination Without prejudice to any other ri...

Page 5: ...Installer Code has changed from CAFE to 5555 for this software version Software Version 1 3 1 5 Supports TL250 and TL300 and all version 1 20 options Supports programmable heart beat interval Section...

Page 6: ...nected and is intended to be installed by service persons i e having the appropriate technical training and experience necessary to be aware of hazards which that person may be exposed to in performin...

Page 7: ...h conduit to a junction box if possible 4 Mount the T Link TL250 300 Panel 2 2 Testing Mode 4 Standard Mode Ensure the panel is programmed to use the T Link TL250 in accor dance with the settings outl...

Page 8: ...can be done only on power up for 30 seconds and only if the reset to factory default is not activated Access the Installer mode using 8 followed by the installer code NOTE The and keys are not support...

Page 9: ...C enclosure model PC5003C when used in a Bell Follower configuration Refer to section 036 99 Connect the and terminals to the external 12 24Vdc power source NOTE Bell Follower mode can not be used in...

Page 10: ...uire an external 12VDC power supply PC5003C Cabinet NOTE Wiring between the control panel and the T Link TL250 TL300 must be enclosed in metal conduit Outputs Input 12 24Vdc TX RX GND RED BLK YEL GRN...

Page 11: ...earth ground connection 5 2 Standard Connection with PC1616 1832 1864 PC4020 CF PC5020 CF NOTE All circuits are supervised and power limited Refer to section 5 4 UL Listed Commercial Fire Sys tems di...

Page 12: ...should power up Program the T Link TL250 as instructed in Section 9 NOTE If a Bell Siren will not be used wire the Bell Siren terminals on the panel with a 1000 ohm resistor For Commercial Fire instal...

Page 13: ...ith receiver set as 1 digit line number Printer Computer Example 2 DVACS with receiver set as 3 digits line number Printer Computer 01 Nov 2004 11 38 22 01 02 SG 01 1 001 Burgl Alm Zn 02 1011 001 A 02...

Page 14: ...represents the receiver and line number originally used on the SG DVL2A and are programmed as the first 4 digits of the T Link account refer to Appendix F of SG DRL3 IP Installation Manual NOTE If the...

Page 15: ...tral Station receiver are as follows When an alarm triggers the panel goes off hook The T Link TL300 module sends a dial tone to the panel The panel dials the telephone number of the central station T...

Page 16: ...h the network administrator that the following ports are locked open and that the SG DRL3 IP has network access for all required network segments 8 5 Integrated Call Directions The T Link TL250 TL300...

Page 17: ...eive pairs and allows two hosts to communicate without the use of a network hub Upon T Link power up without the Ethernet cable connected LED2 will blink periodically approximately once every 12 secon...

Page 18: ...s Phone Numbers NOTE You must delete the D in the telephone number first this is the dial tone detection Step 2 Program YES for T Link Enabled option section 000401 Communication Toggles Step 3 If usi...

Page 19: ...static IP address of the receiver DRL3 IP line card in section 007 Step 9 If the Sur Gard receiver is on a different network segment than the T Link TL250 module the gateway address associated with th...

Page 20: ...subnet mask for T Link TL300 in section 002 if required This option will be ignored if the unit is set for DHCP Section 001 Step 3 Program the T Link account number in section 003 NOTE The T Link acco...

Page 21: ...er can program a value from 1 8 bytes long in each section To disable the encryption program both sections with zeros If the encryption key does not match the central station key then the communicatio...

Page 22: ...or UL installations this option shall be set to B4h 180s For ULC installations this option shall be set to 5Ah 90s for Security Level 4 and to 4Bh 75s for Security Level 5 025 Receiver Restoral Deboun...

Page 23: ...E mail server Contact your Internet ser vice provider or system administrator for this information This option can only be programmed with T Link Console software 031 E mail Account 64 characters max...

Page 24: ...is input is violated the panel immediately communicates to the central station SIA Reporting Code BA BH 16 24hr Panic Input If this input is violated when the system is armed or disarmed the panel rep...

Page 25: ...nerated Refer to options 062 through 065 Mode 1 Bell Follower Operation 048 Input 1 Configuration Default 0 Set to 0 for normally open inputs Set to 1 for normally closed inputs NOTE Select this optio...

Page 26: ...Default 03 The Fire Pulse Count is used with Digital Input 1 when configured for Bell Follower mode The pulsed count will be the minimum number of pulses high and low forming 1 cycle before the T Lin...

Page 27: ...1400Hz 071 TL300 Dial Tone Selection Default 00 Enter the 2 digit code corresponding to country indicated in the table below 072 Heart Beat Interval This option will control the heart beat interval Va...

Page 28: ...s 0 0 0 0 _______ _______ _______ ______ _______ _______ _______ _______ ________ _______ _______ ________ 009 Receiver Local Port 3060 0BF4Hex _______ _______ _______ _______ 010 Receiver Remote Port...

Page 29: ...____ ______ ______ ______ ______ ______ ______ ______ ______ ______ 032 E mail Password Null ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ __...

Page 30: ...l Input 10 SIA Reporting Code 0xFF _______ _______ 060 Digital Input 11 SIA Reporting Code 0xFF _______ _______ 061 Digital Input 12 SIA Reporting Code 0xFF _______ _______ 062 Fire On Time 0x05 _____...

Page 31: ...of 1 Gigabit 1 000 Megabits per second IEEE Abbreviation of Institute of Electrical and Electronics Engineers pronounced I triple E Founded in 1963 the IEEE is an organization composed of engineers sc...

Page 32: ...the main protocols in TCP IP networks Whereas the IP protocol deals only with packets TCP enables two devices to establish a connection and exchange data TCP guarantees delivery of data and also guara...

Page 33: ...om with a valid password For use with PC1616 1832 1864 v4 2 or higher DLS2002 Required CD from distributor or free download from dsc com with a valid password Maxsys PC4020 V3 3 with TCP IP support Dr...

Page 34: ...a 20P Napco 2600 Paradox Digiplex 848 Simplex 4005 4006 4008 4010 4100U NOTE The T Link TL300 is designed to work with the Contact ID com munication format as described in SIA DC 05 Standard Before co...

Page 35: ...YS0001 FTC1 Restoral YK0001 FTC2 Alarm YS0002 FTC2 Restoral YK0002 PC5108 Tamper Alarm ES0000 PC5108 Tamper Restoral EJ0000 PC5108 Absent ET0002 PC5108 Restored ER0002 Keyswitch Arm CS0000 Keyswitch D...

Page 36: ...ant BURGLAR ALARMS 130 Burglary Burg Burglary 131 PERIMETER Burg Perimeter 132 INTERIOR Burg Interior 133 24 HR BURG AUX Burg 24 Hour 134 ENTRY EXIT Burg Entry Exit 135 DAY NIGHT Burg Day Night 136 Ou...

Page 37: ...tion Appl Ckt 4 SYSTEM PERIPHERAL TROUBLES R330 System Peripheral E355 Trouble Sys Peripheral From LRR ECP data connection to panel 331 Polling Loop Open Trouble Polling Loop Open 332 POLLING LOOP SHO...

Page 38: ...n the detector s operation 389 DET SELF TEST FAIL Trouble Sensor Test Fail 391 Sensor Watch Failure Trouble Sensor Watch Fail 392 Drift Comp Error Trouble Drift Comp Error Reported by Firelite panels...

Page 39: ...store Not Applicable 431 Access Threat Level Change Access ACS Threat Level Chg 432 Access Relay Trigger Fail Access ACS Relay Trig Fail 433 Access RTE Shunt Access ACS RTE Shunt 434 Access DSM Shunt...

Page 40: ...ing to log correctly 627 PROGRAM MODE ENTRY Trouble Program Mode Entry Restore Not Applicable 628 PROGRAM MODE EXIT Trouble Program Mode Exit Restore Not Applicable SCHEDULING 630 Schedule Change Trou...

Page 41: ...te to T Link Network Connector INSTALLATION of CAT 5 Ethernet Cable NOTE Install the ferrite inside the control panel as close to the T Link network connector as allowable 6 150 mm max from center of...

Page 42: ...to adversely affect performance or prevent adequate inspection or testing to verify any warranty claim Access cards or tags returned for replacement under warranty will be credited or replaced at DSC...

Page 43: ......

Page 44: ...nd on the user is encouraged to try to correct the interference by one or more of the following mea sures Re orient the receiving antenna Increase the separation between the equipment and receiver Con...

Reviews: