21
[21] 24hr Tamper
When this input is violated, the panel immediately communicates to the central station. SIA
Reporting Code: TA/TH.
[23] Maintained Keyswitch Arm Input (Input 2 Only)
When this input is violated, the system will arm. When this input is secured, the system will
disarm. All instant type inputs have force arming suport.
SIA Reporting Code: CS/OS.
[97] AC Trouble (delayed)
When this input is violated, the T-Link will display a zone trouble and delay the transmission
of the reporting code for 2 hours. If the zone restores, the transmission of the event will be can-
celled immediately. New zone activations will restart the delay timer. Only one zone may be
used as an AC Trouble type zone at any given time. This zone type may be used on any of the
zones on the board.
SIA Reporting Code: AT/AR
[98] 24hr Panel Absent
When this input is violated, the T-Link immediately communicates to the central station
SIA Reporting Code: ET0001/ER0001.
[99] 24hr Bell Follower Input
Input 1 can only be programmed to follow the Bell output for burg/fire monitoring. Connect
Input 1 to the Control Panel Bell+ output. This will disable signal sending when arm and dis-
arm squawks are generated. Refer to options [062] through [065].
Mode 1 - Bell Follower Operation
[048] Input 1 Configuration
Default:
0
Set to 0 for normally open inputs.
Set to 1 for normally closed inputs.
NOTE: Select this option when Normally Closed (NC) detection devices or contacts are being used on Input 1.
[049] Input 2 to 4 Configuration
Default:
0
Set to 0 for normally open contacts.
Set to 1 for normally close contacts.
[050]-[061] SIA Reporting Input
If '00' is entered, central station reporting is disabled. All other actions for PGM outputs and
status are still activated.
If 'FF' is entered, default reporting code is enabled using the input definitions, with the hard
coded input number.
If anything between 01 and 99 is programmed, the hard coded input number will be replaced
by the programmed value.
Alarm Reporting Codes, Inputs 1-12
Default:
Default:
FF
|______|______|
Input 1 Alarm
FF
|______|______|
Input 7 Alarm
FF
|______|______|
Input 2 Alarm
FF
|______|______|
Input 8 Alarm
FF
|______|______|
Input 3 Alarm
FF
|______|______|
Input 9 Alarm
FF
|______|______|
Input 4 Alarm
FF
|______|______|
Input 10 Alarm
FF
|______|______|
Input 5 Alarm
FF
|______|______|
Input 11 Alarm
FF
|______|______|
Input 6 Alarm
FF
|______|______|
Input 12 Alarm
BELL+ BELL-
Alter n
a
te connection fo r
Control P
a
nel
s
where Bell
s
w itche
s
High
Rel
a
y
Com
NC
NO
12-24Vdc YX RX GND RED YEL GRNPGM1PGM2IN1 GND
GND
IN2 IN
3
IN4 EARTH
+
-