Maxsys V3.5 Only:

If the panel sends events to Receiver 0, the T-Link will perform backups automatically to IPs
from Receiver 1 and Receiver 2. If the panels sends events to specific receivers then the
panel will be responsible for all backup/alternate dial functions.

NOTE: The IP Receiver addresses are programmed in the T-Link TL250.

9.2

T-Link TL250 Basic Programming (PC1616/1832/1864, PC5020 Panels)

NOTE: PC1616/1832/1864 or PC5020 software version 3.2 or higher required (Rev03 hardware).

Programming Steps:

Step 1: Program the hex digits [DCAA] in the telephone number that will be used for T-Link TL250

communications (section [301] to [303], ‘Telephone Phone Number Programming’). 

NOTE: The leading digit [D] in the telephone number for dial tone detection is already programmed.

Step 2: Program the communication format as SIA FSK format in section [350] and Auto SIA,

option 3 in section [381] has to be OFF.

Step 3: Program the call direction options in section [351] to [376] for the phone number being used

to communicate using T-Link TL250.

Step 4: Section [382]

 

Option 5 ‘PC-Link Active’ option must be ON to enable T-Link TL250 com-

munication.

Step 5: Enter section [851] for T-Link TL250 module programming options. 

NOTE: Option [5] in Section [382] must be enabled to access this section.

NOTE:Data must be entered within a 14-second window. Exceeding the 14s limit will result in the following
sequence: a tone will sound, exit from the programming section, all data previously entered will be lost.   

Step 6: Program the static IP address for the T-Link TL250 module in section [001]. Program

000.000.000.000 for DHCP.

Step 7: Program the subnet mask for the T-Link TL250 module in section [002]. This option will be

ignored if the unit is set for DHCP.

Step 8: Program the static IP address of the receiver (DRL3-IP line card) in section [007].
Step 9: If the Sur-Gard receiver is on a different network segment than the T-Link TL250 module,

the gateway address associated with the T-Link TL250 module

 

must be programmed in sec-

tion [008]. This is an optional step; verify with the network administrator if this is required.

Step 10: Program the T-Link account number in section [003].

NOTE: The T-Link account number can be up to 10 digits long. If account number is less then 10 digits lead-
ing zeros must be entered.

Step 11: When T-Link Programming is completed perform the following for programming changes to

take effect. In T-Link Programming Section [999], enter digits [55]. It will take approxi-
mately 15s for the module to reboot. Press [#] key to exit T-Link TL250 programming.

9.3

T-Link TL250 DVACS Programming

Obtain the following information from the station monitoring the DVACS alarm panel:
1. The SG-DVL2A Receiver number and line number that the DVACS panel is connected to.
2. The DVACS panel ID (Account Number).
3. The programmed value of the SG-DVL2A extended format (Option [07]) for step 2 below.

Step 1: Program the Account Number of the DVACS control panel in the DVACS account option of

the T-Link (Option [067]). The T-Link will use this number to supervise the control panel
and poll for DVACS signals from the panel.

NOTE: Alarms generated by the DVACS panel will be sent using the T-Link account.

Step 2: Program the T-Link DVACS extended Option [068] so that it is identical to the SG-DVL2A

extended option 07. 

Step 3: Program the T-Link Account (Option [003]). To use the DVACS account number for alarm
reporting, program the T-Link account option with this value. 
When an alarm is sent from the DVACS control panel to the central station, the account number is
expanded to a 10-digit value. The first four digits emulate the line number and receiver number on the

CAAA = Receiver 0

CCCC = Receiver 2

CBBB = Receiver 1

CDDD = Receiver 3

Summary of Contents for T-LINK TL250

Page 1: ...T Link TL250 TL300 Network Internet Alarm Communicator Software Version 1 5 Installation Manual...

Page 2: ...may not properly alert occupants of a fire for a number of reasons some of which follow The smoke detectors may have been improperly installed or positioned Smoke may not be able to reach the smoke d...

Page 3: ...stallation 9 6 2 DVACS Events 9 Section 7 TL300 Telephone Simulation 11 7 1 TL300 Panel Installation 11 7 2 T Link TL300 Operation 11 Section 8 T Link TL250 TL300 Operation 12 8 1 Remote Control 12 8...

Page 4: ...rovided the recipient agrees to the terms of thisEULA IftheSOFTWAREPRODUCTisanupgrade anytransfermustalso includeallpriorversionsof the SOFTWARE PRODUCT f Termination Without prejudice to any other ri...

Page 5: ...Installer Code has changed from CAFE to 5555 for this software version Software Version 1 3 1 5 Supports TL250 and TL300 and all version 1 20 options Supports programmable heart beat interval Section...

Page 6: ...nected and is intended to be installed by service persons i e having the appropriate technical training and experience necessary to be aware of hazards which that person may be exposed to in performin...

Page 7: ...h conduit to a junction box if possible 4 Mount the T Link TL250 300 Panel 2 2 Testing Mode 4 Standard Mode Ensure the panel is programmed to use the T Link TL250 in accor dance with the settings outl...

Page 8: ...can be done only on power up for 30 seconds and only if the reset to factory default is not activated Access the Installer mode using 8 followed by the installer code NOTE The and keys are not support...

Page 9: ...C enclosure model PC5003C when used in a Bell Follower configuration Refer to section 036 99 Connect the and terminals to the external 12 24Vdc power source NOTE Bell Follower mode can not be used in...

Page 10: ...uire an external 12VDC power supply PC5003C Cabinet NOTE Wiring between the control panel and the T Link TL250 TL300 must be enclosed in metal conduit Outputs Input 12 24Vdc TX RX GND RED BLK YEL GRN...

Page 11: ...earth ground connection 5 2 Standard Connection with PC1616 1832 1864 PC4020 CF PC5020 CF NOTE All circuits are supervised and power limited Refer to section 5 4 UL Listed Commercial Fire Sys tems di...

Page 12: ...should power up Program the T Link TL250 as instructed in Section 9 NOTE If a Bell Siren will not be used wire the Bell Siren terminals on the panel with a 1000 ohm resistor For Commercial Fire instal...

Page 13: ...ith receiver set as 1 digit line number Printer Computer Example 2 DVACS with receiver set as 3 digits line number Printer Computer 01 Nov 2004 11 38 22 01 02 SG 01 1 001 Burgl Alm Zn 02 1011 001 A 02...

Page 14: ...represents the receiver and line number originally used on the SG DVL2A and are programmed as the first 4 digits of the T Link account refer to Appendix F of SG DRL3 IP Installation Manual NOTE If the...

Page 15: ...tral Station receiver are as follows When an alarm triggers the panel goes off hook The T Link TL300 module sends a dial tone to the panel The panel dials the telephone number of the central station T...

Page 16: ...h the network administrator that the following ports are locked open and that the SG DRL3 IP has network access for all required network segments 8 5 Integrated Call Directions The T Link TL250 TL300...

Page 17: ...eive pairs and allows two hosts to communicate without the use of a network hub Upon T Link power up without the Ethernet cable connected LED2 will blink periodically approximately once every 12 secon...

Page 18: ...s Phone Numbers NOTE You must delete the D in the telephone number first this is the dial tone detection Step 2 Program YES for T Link Enabled option section 000401 Communication Toggles Step 3 If usi...

Page 19: ...static IP address of the receiver DRL3 IP line card in section 007 Step 9 If the Sur Gard receiver is on a different network segment than the T Link TL250 module the gateway address associated with th...

Page 20: ...subnet mask for T Link TL300 in section 002 if required This option will be ignored if the unit is set for DHCP Section 001 Step 3 Program the T Link account number in section 003 NOTE The T Link acco...

Page 21: ...er can program a value from 1 8 bytes long in each section To disable the encryption program both sections with zeros If the encryption key does not match the central station key then the communicatio...

Page 22: ...or UL installations this option shall be set to B4h 180s For ULC installations this option shall be set to 5Ah 90s for Security Level 4 and to 4Bh 75s for Security Level 5 025 Receiver Restoral Deboun...

Page 23: ...E mail server Contact your Internet ser vice provider or system administrator for this information This option can only be programmed with T Link Console software 031 E mail Account 64 characters max...

Page 24: ...is input is violated the panel immediately communicates to the central station SIA Reporting Code BA BH 16 24hr Panic Input If this input is violated when the system is armed or disarmed the panel rep...

Page 25: ...nerated Refer to options 062 through 065 Mode 1 Bell Follower Operation 048 Input 1 Configuration Default 0 Set to 0 for normally open inputs Set to 1 for normally closed inputs NOTE Select this optio...

Page 26: ...Default 03 The Fire Pulse Count is used with Digital Input 1 when configured for Bell Follower mode The pulsed count will be the minimum number of pulses high and low forming 1 cycle before the T Lin...

Page 27: ...1400Hz 071 TL300 Dial Tone Selection Default 00 Enter the 2 digit code corresponding to country indicated in the table below 072 Heart Beat Interval This option will control the heart beat interval Va...

Page 28: ...s 0 0 0 0 _______ _______ _______ ______ _______ _______ _______ _______ ________ _______ _______ ________ 009 Receiver Local Port 3060 0BF4Hex _______ _______ _______ _______ 010 Receiver Remote Port...

Page 29: ...____ ______ ______ ______ ______ ______ ______ ______ ______ ______ 032 E mail Password Null ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ __...

Page 30: ...l Input 10 SIA Reporting Code 0xFF _______ _______ 060 Digital Input 11 SIA Reporting Code 0xFF _______ _______ 061 Digital Input 12 SIA Reporting Code 0xFF _______ _______ 062 Fire On Time 0x05 _____...

Page 31: ...of 1 Gigabit 1 000 Megabits per second IEEE Abbreviation of Institute of Electrical and Electronics Engineers pronounced I triple E Founded in 1963 the IEEE is an organization composed of engineers sc...

Page 32: ...the main protocols in TCP IP networks Whereas the IP protocol deals only with packets TCP enables two devices to establish a connection and exchange data TCP guarantees delivery of data and also guara...

Page 33: ...om with a valid password For use with PC1616 1832 1864 v4 2 or higher DLS2002 Required CD from distributor or free download from dsc com with a valid password Maxsys PC4020 V3 3 with TCP IP support Dr...

Page 34: ...a 20P Napco 2600 Paradox Digiplex 848 Simplex 4005 4006 4008 4010 4100U NOTE The T Link TL300 is designed to work with the Contact ID com munication format as described in SIA DC 05 Standard Before co...

Page 35: ...YS0001 FTC1 Restoral YK0001 FTC2 Alarm YS0002 FTC2 Restoral YK0002 PC5108 Tamper Alarm ES0000 PC5108 Tamper Restoral EJ0000 PC5108 Absent ET0002 PC5108 Restored ER0002 Keyswitch Arm CS0000 Keyswitch D...

Page 36: ...ant BURGLAR ALARMS 130 Burglary Burg Burglary 131 PERIMETER Burg Perimeter 132 INTERIOR Burg Interior 133 24 HR BURG AUX Burg 24 Hour 134 ENTRY EXIT Burg Entry Exit 135 DAY NIGHT Burg Day Night 136 Ou...

Page 37: ...tion Appl Ckt 4 SYSTEM PERIPHERAL TROUBLES R330 System Peripheral E355 Trouble Sys Peripheral From LRR ECP data connection to panel 331 Polling Loop Open Trouble Polling Loop Open 332 POLLING LOOP SHO...

Page 38: ...n the detector s operation 389 DET SELF TEST FAIL Trouble Sensor Test Fail 391 Sensor Watch Failure Trouble Sensor Watch Fail 392 Drift Comp Error Trouble Drift Comp Error Reported by Firelite panels...

Page 39: ...store Not Applicable 431 Access Threat Level Change Access ACS Threat Level Chg 432 Access Relay Trigger Fail Access ACS Relay Trig Fail 433 Access RTE Shunt Access ACS RTE Shunt 434 Access DSM Shunt...

Page 40: ...ing to log correctly 627 PROGRAM MODE ENTRY Trouble Program Mode Entry Restore Not Applicable 628 PROGRAM MODE EXIT Trouble Program Mode Exit Restore Not Applicable SCHEDULING 630 Schedule Change Trou...

Page 41: ...te to T Link Network Connector INSTALLATION of CAT 5 Ethernet Cable NOTE Install the ferrite inside the control panel as close to the T Link network connector as allowable 6 150 mm max from center of...

Page 42: ...to adversely affect performance or prevent adequate inspection or testing to verify any warranty claim Access cards or tags returned for replacement under warranty will be credited or replaced at DSC...

Page 43: ......

Page 44: ...nd on the user is encouraged to try to correct the interference by one or more of the following mea sures Re orient the receiving antenna Increase the separation between the equipment and receiver Con...

Reviews: