34
NOTE
:
Uplink cell backup devices send zone 99 for a low battery and a zone 97 for communication failure (no
response from poll). These will report as contact ID E370 (protection loop). let me clarify this: these are sig-
nals GENERATED by the uplink to indicate STATUS of the uplink. The central station will assume that they
were generated by the panel. Additional codes that may be sent would be for zones 81-86 which correspond
to hardwire inputs 1-6. The contact ID message for these is selected by uplink when it is programmed. So,
next time someone reports an unusual zone 97 or 99 being reported to their Central Station, Uplink may be
the culprit. Uplink's number is 1-888-987- 5465 if you need it.
371
Protection Loop Open
Trouble-Prot. Loop Open-#
372
Protection Loop Short
Trouble-Prot. Loop Short-#
373
FIRE TROUBLE
Trouble-Fire Loop-# (Supervision Loss, base tamper, Supervisory open)
374
EXIT ERROR (BY USER)
Alarm-Exit Error-#
375
Panic Zone Trouble
Trouble-PA Trouble-#
376
Hold-Up Zone Trouble
Trouble-Hold-Up Trouble-#
377
Swinger Trouble
Trouble – Swinger Trouble-#
378
Cross-zone Trouble
Trouble – Cross Zone Trouble - # (restore not applicable)
SENSOR:
380
SENSOR TRBL - GLOBAL
Trouble-Sensor Trouble-#
381
LOSS OF SUPERVISION
Trouble-RF Sensor Super.-#
382
LOSS OF SUPRVSN
Trouble-RPM Sensor Super.-#
383
SENSOR TAMPER
Trouble-Sensor Tamper-#
384
RF LOW BATTERY
Trouble-RF Sensor Battery-#
385
SMOKE HI SENS.
Trouble-Smoke Hi Sens.-#
386
SMOKE LO SENS.
Trouble-Smoke Lo Sens.-#
-387 INTRUSION HI SENS.
Trouble-Intrusion Hi Sens.-#
-388 INTRUSION LO SENS.
Trouble-Intrusion Lo Sens.-# - These codes are similar to those used
for smart smoke detectors. The idea is to report a problem developing
in the detector’s operation.
389
DET. SELF TEST FAIL
Trouble-Sensor Test Fail-#
391
Sensor Watch Failure
Trouble-Sensor Watch Fail-#
392
Drift Comp. Error
Trouble-Drift Comp. Error-# - Reported by Firelite panels. The panel is
not able to adjust its thresholds to balance out drift in the normal oper-
ating point of a smoke detector.
393
Maintenance Alert
Trouble-Maintenance Alert-#
OPEN/CLOSE:
400
Open/Close
Opening/Closing E = Open, R = Close
401
OPEN/CLOSE BY USER
Opening-User # / Closing-User #
402
Group O/C
Closing-Group User #
403
AUTOMATIC OPEN/CLOSE
Opening-Automatic / Closing-Automatic
404
Late to O/C
Opening-Late / Closing-Late
405
Deferred O/C
Event & Restore Not Applicable
406
CANCEL (BY USER)
Opening-Cancel
407
REMOTE ARM/DISARM
Opening-Remote / Closing-Remote
408
QUICK ARM
Event Not Applicable for opening / Closing-Quick Arm
409
KEYSWITCH OPEN/CLOSE
Opening-Keyswitch / Closing-Keyswitch
435
Second Person Access
ACCESS – User #
436
Irregular Access
ACCESS – Irregular Access – User #
441
Armed Stay
Opening-Armed Stay / Closing-Armed Stay
442
Keyswitch Armed Stay
Opening-Keysw. Arm Stay / Opening-Keysw. Arm Stay
450
Exception O/C
Opening-Exception / Closing-Exception
451
Early O/C
Opening-Early / Closing-Early-User #
452
Late O/C
Opening-Late / Closing-Late-User #
453
Failed to Open
Trouble-Fail to open (Restore not applicable)
454
Failed to Close
Trouble-Fail to Close (Restore not applicable)
455
Auto-Arm Failed
Trouble-Auto Arm Failed (Restore not applicable)
456
Partial Arm
Closing-Partial arm-User #
457
Exit Error (User)
Closing-Exit Error-User #
458
User on Premises
Opening-User on Prem. – User #
459
Recent Close
Trouble-Recent Close – User # (Restore not applicable)
461
Wrong Code Entry
Access – Wrong Code entry (Restore not applicable)
462
Legal Code Entry
Access-Legal Code entry – user # (Restore not applicable)
463
Re-arm after Alarm
Status-Re Arm After Alarm-User # (restore not applicable)
Summary of Contents for T-LINK TL250