4

Keybus Terminals – AUX+, AUX-, YEL, GRN 

The Keybus is used by the panel to communicate with mod-
ules and vice versa. Each module has four Keybus terminals
that must be connected to the four Keybus terminals on the
panel. For more information, see section 

2.3 “Keybus Opera-

tion and Wiring”.

Programmable Output Terminals – PGM1 and PGM2

Each PGM output is designed so that when activated by the
panel, the terminal will switch to ground.

PGM1 can sink up to 300mA of
current. Connect the positive
side of the LED or buzzer to
AUX+, the negative side to
PGM1. If more than 300 mA of
current are required, a relay
must be used. Please study
PGM wiring in the accompany-
ing diagram.
PGM2 operates similarly to
PGM1. However, PGM2 can
only sink up to 50mA of cur-
rent. For a list of the program-
mable output options, see
section 5.11 

“PGM Output

Options” on page 20.

Zone Input Terminals – Z1 to Z6

Each detection device must be connected to a zone on the
control panel. We suggest that one detection device be con-
nected to each zone; wiring multiple detection devices to a
single zone, however, is possible. For zone wiring specifics,
please see section 2.8 

“Zone Wiring” on page 5.

Telephone Connection Terminals – TIP, RING, T-1, R-1

If a telephone line is required for central station communica-
tion or downloading, connect an RJ-31X telephone jack in the
following manner:

Connect the PC5008 and modules which use the telephone
line(s) in the following order:

For example, if you are installing a PC5008 with an Escort5580
and a PC5928 Intercom module, connect the incoming line to
the control panel, then to the Escort5580 and then to the
PC5928 Intercom. Next, connect the PC5928 to the house
telephones.

NOTE: For proper operation, no other telephone equipment 
should be connected between the control panel and the tele-
phone company facilities. Do not connect the alarm panel com-

municator to telephone lines intended for use with a fax
machine. These lines may incorporate a voice filter which dis-
connects the line if anything other than fax signals are
detected, resulting in incomplete transmissions.

2.3

Keybus Operation and Wiring

The Keybus is used by the panel to communicate with all con-
nected modules and vice versa. The red (AUX+) and black
(AUX-) terminals are used to provide power, while the yellow
(YEL) and green (GRN) terminals are clock and data respec-
tively.

NOTE: The four Keybus terminals of the panel must be con-
nected to the four Keybus terminals or wires of all modules.

The following restrictions apply to Keybus wiring:

Keybus should be run in minimum 22 gauge quad
(0.5mm); two pair twist is preferred. 

The modules should be home-run to the panel but can be
connected in series or T-tapped.

Any module can be connected anywhere along the Key-
bus. You do not need to run a separate Keybus wire for
keypads, etc. 

No module can be more than 1,000'/305m (in wire length)
from the panel. 

Shielded wire should not be used.

Example of Keybus Wiring

NOTE: 
Module (A) is correctly
wired within 1,000'/
305m of wire from the
panel.
Module (B) is correctly
wired within 1,000'/
305m of wire from the
panel.
Module (C) is NOT wired correctly as it is further than 1,000'/
305m from the panel, in wire distance.

2.4

Current Ratings – Modules and 
Accessories

In order for the PC5008 system to operate properly, the power
output capabilities of the main control and the expansion
devices must not be exceeded. Use the data presented below
to ensure that no part of the system is overloaded and cannot
function properly.

PC5008 (12 V

DC

)

AUX+: ........550mA: Subtract the listed rating for each key-

pad, expansion module and accessory con-
nected to AUX+ or Keybus.

BELL: .........700mA continuous rating; 3.0A short term. Avail-

able only with standby battery connected.

PC5008 Device Ratings (at 12 V

DC

)

LCD5500Z Keypad: 85mA

PC5508Z Keypad: 75-85mA

PC5400 Serial Module: 65mA

Escort5580 Audio Assistant: 65mA standby / 130mA on-
line

PC5204 High Current Output module: 20mA

PC5208 Low Current Output module: 50mA

PC5132 Wireless Receiver: 125mA

PC5928 Audio Interface module: 65mA

PC5921/EXT Door Box Audio Station: 20mA

Summary of Contents for Power608

Page 1: ...manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be carefully read PC5008...

Page 2: ...ces or passing traffic Audible warning devices however loud may not be heard by a hearing impaired person Telephone Lines If telephone lines are used to transmit alarms they may be out of service or b...

Page 3: ...5 Program Descriptions 14 5 1 Programming Security Codes 14 5 2 Zone Programming 14 5 3 Zone Attributes 15 5 4 Assigning Keypad Zones 16 5 5 Communicator Dialing 16 5 6 Communicator Account Numbers 17...

Page 4: ...ii PC5008 Wiring Diagram...

Page 5: ...t in piezoelectric buzzer Digital Communicator Specifications Supports major communication formats including SIA and Contact ID Event initiated personal paging Three programmable telephone numbers Two...

Page 6: ...the PC5928 Audio Interface Module PC5921 EXT Door Box Audio Station Used in conjunction with the PC5928 Audio Interface Module PC5921 EXT R Door Box Audio Station Used in conjunction with the PC5928...

Page 7: ...out the Programming Worksheets completely before attempt ing to program the system Step 10 Testing the System Test the panel thoroughly to ensure that all features and func tions are operating as pro...

Page 8: ...These lines may incorporate a voice filter which dis connects the line if anything other than fax signals are detected resulting in incomplete transmissions 2 3 Keybus Operation and Wiring The Keybus...

Page 9: ...les are supervised upon installation Supervision is enabled at all times so that the panel can indi cate a trouble if a module is removed from the system To check on which modules are currently connec...

Page 10: ...one input to which a device such as a door contact can be connected This eliminates the need to run wires back to the control panel for every device To install the keypad open the keypad plastic by re...

Page 11: ...ing Stay arming please see section 3 5 Function Keys on page 10 3 3 Automatic Arming The system can be programmed to Auto Arm at a specific time every day if it is in the disarmed condition In order f...

Page 12: ...odule being powered by a PC5204 you must also remove and then restore power to the PC5204 and any connected modules This ensures that any troubles present on the module are correctly logged and or ann...

Page 13: ...ult These settings can be changed Access Code Attributes There are three access code attributes which can be pro grammed for each code To program each attribute enter 5 Master Code 9 to enter the attr...

Page 14: ...the panel will ignore only one activation of a Delay zone When the Delay zone is secured the panel will end the two minute quick exit delay If a second Delay zone is tripped or if the zone is not res...

Page 15: ...anual NOTE This function key cannot be programmed for PC55XX LED keypads with software version 1 0 19 7 3 Command Output Option 3 A valid access code may need to be entered 20 For future use 21 7 4 Co...

Page 16: ...the key to exit the section Select that section again and re enter the information correctly NOTE There must be one digit in each box in the program ming section in order for the change to be valid 4...

Page 17: ...y pad When a programming section is entered the keypad will immediately display the first digit of information programmed in that section The keypad displays the information using a binary format acco...

Page 18: ...ry time expires no alarm will be generated 02 Delay 2 Zone The Delay 2 entry delay time can be set independently of Delay 1 in programming section 005 System Times 03 Instant Zone This zone type will...

Page 19: ...e trouble 23 Maintained Keyswitch Arm Zone When this zone is violated the system will arm When this zone is secured the system will disarm Tampers and faults will not arm disarm the system but only ac...

Page 20: ...in and search for a dial tone for 5 seconds d the panel will then dial regardless of the presence of dial tone If there is no initial handshake recognized within 40 seconds the panel will then hang up...

Page 21: ...ed to report events to the central station by sending the Reporting Code programmed for a par ticular event Reporting codes can be one or two digits and can use HEX digits A through F For a complete d...

Page 22: ...Section 361 to 368 The following is a description of each reporting format Pulse Formats Depending on which pulse format is selected the panel will communicate using the following specifications 3 1 3...

Page 23: ...e pager once Once the appro priate telephone number is dialed the panel will send the account number and Reporting Code followed by the key Hex C The panel has no way of confirming if the pager was ca...

Page 24: ...ted Call Up option is enabled the user can have the panel initiate a call to the downloading computer by pressing 6 Master Code 6 The Download Access Code and Panel Identifier Code are for security an...

Page 25: ...ed to indicate that an alarm has occurred before entering the premises The PGM attributes for this option programmed in Sections 141 to 154 differ from the standard selection of attributes Program whi...

Page 26: ...outputs PGM attributes return to their default settings when you change PGM output options Please see the programming worksheets for a list of the default settings for each PGM out put type Care shou...

Page 27: ...me expires Communication of the signal to central station is immediate If the A Key is pressed and held for two seconds the panel will sound the keypad beeps three times to verify activa tion The pane...

Page 28: ...al applications Bell Squawk on Entry Delay may be enabled The panel will squawk the alarm output once every second until the entry delay expires or the system is dis armed If the Bell Squawk During Au...

Page 29: ...estoral Reporting Codes Section 338 System Tampers Req Installer Reset Section 701 4 NOTE After enabling keypad tampers it is recommended to tamper and restore all keypads to ensure proper functioning...

Page 30: ...5 31 Installer s Lockout If Installer s Lockout is selected a hardware default cannot be performed If a software default is performed all program ming will restore to factory default If Installer s L...

Page 31: ...________________________________________________________________________________________________I Keypad 7 I_____________________________________________I I____________________________________________...

Page 32: ...Keypads must be installed to use 24 hour Buzzer zones 001 Zone 1 8 Definitions Section 5 2 Zone Programming on page 14 Default Default 01 I_______I_______I Zone 1 04 I_______I_______I Zone 5 03 I____...

Page 33: ...Status 05 System Armed Status 18 Stay Armed Status 06 Ready To Arm 19 Command Output 1 7 1 07 Keypad Buzzer Follow Mode 20 Command Output 2 7 2 08 Courtesy Pulse 21 Command Output 3 7 3 09 System Tro...

Page 34: ...Arm Disarm Bell Squawk disabled 5 17 23 OFF I________I 2 Bell Squawk During Auto Arm No Bell Squawk During Auto Arm 5 18 24 OFF I________I 3 Bell Squawk On Exit Delay No Bell Squawk On Exit Delay 5 1...

Page 35: ...Contact I D Partial Close Identifier is 5 Partial Close Identifier is 4 5 9 18 OFF I________I 5 8 For future use 020 Keypad Zone Assignments Section 2 11 Keypad Zones on page 6 NOTE Only one keypad m...

Page 36: ...ion 001 Attribute 1 2 3 4 5 6 7 8 ON Audible Steady Chime Bypass Force Swing Tx Delay Wireless Zn OFF Silent Pulsed No No No No No No Zone Type 00 Null Zone N N N N N N N N 01 Delay 1 Y Y Y Y N Y N N...

Page 37: ...1 11 I________I I________ I________ I________ I________ I________ I________ I________I 152 12 I________I I________ I________ I________ I________ I________ I________ I________I 153 13 I________I I_____...

Page 38: ...nd Telephone Number 32 Digits Section 5 7 Communicator Telephone Numbers on page 17 I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_...

Page 39: ..._____I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I 342 Code 25 Code 26 Code 27 Code 28 Code 29 Code 30 Code 31 Code 32 I_______I_______I I_______I...

Page 40: ..._____I General Zone Trouble Alarm I_______I_______I General Zone Trouble Restore I_______I_______I For future use 352 Test Transmission Reporting Codes Section 5 8 Communicator Reporting Codes on pg 1...

Page 41: ...5 23 030 I_______I_______I_______I AC Failure Communication Delay 001 255 minutes 5 8 17 003 I_______I_______I_______I TLM Trouble Delay No of checks required valid entries 003 255 5 12 22 030 I______...

Page 42: ...indow OFF I_______I 3 Call Back Enabled Call Back Disabled OFF I_______I 4 User initiated Call up Enabled User initiated Call up Disabled OFF I_______I 5 8 For future use 402 Downloading Computer s Te...

Page 43: ...line Test Transmission in minutes Land line Test Transmission in days 5 14 23 OFF I_______I 4 1600 Hz Handshake Standard Handshake 5 9 18 OFF I_______I 5 ID Tone enabled ID Tone disabled 5 5 16 OFF I_...

Page 44: ...BAD 3 Beeps Squawks 990 Installer Lockout Enable Section 5 31 Installer s Lockout on page 26 991 Installer Lockout Disable Section 5 31 Installer s Lockout on page 26 993 Restore LINKS2X50 Factory De...

Page 45: ...der Supervisory Alarm Rest panel loses restores supervisory transmission over the Keybus from enrolled PC5132 module or keypads with zone inputs A R 1 43 UA 00 UH 00 328 Cross Zone Police Code Alarm t...

Page 46: ...T 00 UJ 00 352 Periodic Test periodic system test transmission T 6 A2 RP 00 352 System Test 6 bell communications test T 6 A1 RX 00 352 LINKS Test LINKS test transmission T 6 A3 TX 00 353 Wireless Dev...

Page 47: ...one 5 I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I Default Zone 6 I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I Default...

Page 48: ...bled ON I_______I 2 A uxiliary Keys enabled A uxiliary Keys disabled ON I_______I 3 P anic Keys enabled P anic Keys disabled OFF I_______I 4 8 For future use 65 Fourth User Display Mask Default Option...

Page 49: ...Label Broadcast All LCD programming is done per keypad If more than one LCD keypad are present on the system and the PC5400 receives labels labels pro grammed at one keypad can be broadcast to all oth...

Page 50: ...46 NOTES...

Page 51: ...6 of the Telecommunications Act 1981 6 It is important that the installer verifies the correct operation of stored telephone numbers subsequent to their entry 7 The connection to this equipment consis...

Page 52: ...e 18 New PGM Output Type 26 Battery Test See 5 11 PGM Output Options on page 20 New Zone Types 27 Push to Set 28 24 Hr Bell Buzzer See 5 2 Zone Programming on page 14 New Options Troubles are Latching...

Reviews: