DSC Power608 Installation Manual Download Page 18

14

Section 5: Program Descriptions

The following section explains the operation of all programma-
ble features and options and provides a summary of all corre-
sponding programming locations.

5.1

Programming Security Codes

There are three codes which can be programmed by the
installer in the Installer’s Programming function: the Master
code, the Installer’s code, and a Maintenance code. All other
access codes can be programmed through the [*][5] com-
mand (see section 3.4 

“[*] Commands” on page 7). 

The master code can also be programmed by the user as
access code (40). If the 

Master Code Not Changeable

 option

is enabled, the system master code can only be changed by
the installer.
General access codes can arm and disarm the system. When
the 

Code Required for Bypassing

 option is enabled, users

will need to enter a valid access code when bypassing zones.
Individual access codes can have the Zone Bypassing
attribute disabled under access code attribute programming
(see section 3.4 

“[*] Commands” on page 7).

If the 

6-Digit User Access Codes

 option is enabled, all the

access codes may be programmed with six digits instead of
four, with the exception of the Panel ID code and the Down-
loading Access code.

Installer’s Code  . . . . . . . . . . . . . . . . . . . . . . . . . Section [006]
Master Code . . . . . . . . . . . . . . . . . . . . . . . . . . . Section [007]
Maintenance Code  . . . . . . . . . . . . . . . . . . . . . . Section [008]
Master Code Not Changeable  . . . . . . . . . . Section [015]: [6]
Code Required for Bypassing   . . . . . . . . . . Section [015]: [5]
6-digit User Access Codes . . . . . . . . . . . . . Section [701]: [5]

NOTE: The Maintenance code is limited to arming and disarm-
ing the system. The Maintenance code cannot use [*][9] to arm
the system, bypass zones, or perform [*][7] command func-
tions.

5.2

Zone Programming

All eight zones are enabled by default. Unused zones should
be disabled in programming section [202].
Section [001] will allow you to select how each of the zones
you use will operate. Each zone requires a two-digit code to
be programmed, which describes the zone definition. Select a
definition from the list below. 
In addition, each zone has eight different attributes which may
be programmed in sections [101] to [108] (see section 5.3
“Zone Attributes” on page 15).

Zone Definitions

[00]  Null Zone

The zone is vacant. Unused zones should be programmed as
Null zones.

[01]  Delay 1 Zone

This zone type, normally used for entry/exit doors, can be vio-
lated during the exit delay time without causing an alarm.
Once the exit delay has expired, opening the zone will start
the entry delay timer. During the entry delay time, the keypad
buzzer will sound steadily to advise the user that the system

should be disarmed. If the panel is disarmed before the entry
time expires, no alarm will be generated.

[02]  Delay 2 Zone

The Delay 2 entry delay time can be set independently of
Delay 1 in programming section [005] (System Times).

[03]  Instant Zone

This zone type will cause an instant alarm if it is violated when
the panel is armed. Typically, this zone is used for windows,
patio doors or other perimeter zones, and glass break detec-
tors.

[04]  Interior Zone

This zone will not cause an alarm if violated during the entry
delay. If the zone is violated before the entry delay has begun,
it will cause an instant alarm. Typically, this zone is used for
interior protection devices, such as motion detectors.

[05]  Interior Stay/Away Zone

This zone type works similarly to the Interior zone type, except
that it will be automatically bypassed under the following con-
ditions:

When the panel is armed in the Stay Mode (see section
3.5 

“Function Keys” on page 10).

When the panel is armed without entry delay (see 

“[*][9]

Arming Without Entry Delay” on page 10).

When the panel is armed with an access code and a
Delay type zone is NOT tripped during the exit delay.

The automatic bypass prevents the user from having to manu-
ally bypass interior type zones when arming at home. This
zone is typically used for interior protection devices, such as
motion detectors. 

[06]  Delay Stay/Away Zone

This zone type will operate similarly to Interior Stay/Away
zones, except that it will always provide an entry delay. Typi-
cally, this zone is used for interior protection devices, such as
motion detectors. This zone option will help prevent false
alarms since it always provides an entry delay time for the
user to turn off the panel. 

NOTE: Hardwire motion detectors covering entry/exit doors
that are using wireless transmitters must be programmed as
Delay Stay/Away. If not, the panel may see the motion detector
violation before the entry/exit transmitter has time to transmit to
the receiver, causing a false alarm.

[07]  Delayed 24 Hour Fire Zone

NOTE: Do not wire Fire zones on keypad zone terminals if the
DEOL supervision option is enabled for the panel (section
[013], option [2]).

When this zone is violated, the alarm output will be immedi-
ately activated (pre-alert) but the communicator will be
delayed for 30 seconds. If the user presses any key on any
keypad during this delay, the alarm output and the communi-
cator will be delayed an additional 90 seconds, giving the
user time to correct the problem. If the zone is still violated
after the 90 second delay, the panel will sound the alarm out-
put and delay the communicator for 30 seconds.
If the user does not press a key during the 30 second pre-
alert, the alarm output will latch and the panel will communi-
cate the alarm to the central station. The alarm will sound until

Summary of Contents for Power608

Page 1: ...manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be carefully read PC5008...

Page 2: ...ces or passing traffic Audible warning devices however loud may not be heard by a hearing impaired person Telephone Lines If telephone lines are used to transmit alarms they may be out of service or b...

Page 3: ...5 Program Descriptions 14 5 1 Programming Security Codes 14 5 2 Zone Programming 14 5 3 Zone Attributes 15 5 4 Assigning Keypad Zones 16 5 5 Communicator Dialing 16 5 6 Communicator Account Numbers 17...

Page 4: ...ii PC5008 Wiring Diagram...

Page 5: ...t in piezoelectric buzzer Digital Communicator Specifications Supports major communication formats including SIA and Contact ID Event initiated personal paging Three programmable telephone numbers Two...

Page 6: ...the PC5928 Audio Interface Module PC5921 EXT Door Box Audio Station Used in conjunction with the PC5928 Audio Interface Module PC5921 EXT R Door Box Audio Station Used in conjunction with the PC5928...

Page 7: ...out the Programming Worksheets completely before attempt ing to program the system Step 10 Testing the System Test the panel thoroughly to ensure that all features and func tions are operating as pro...

Page 8: ...These lines may incorporate a voice filter which dis connects the line if anything other than fax signals are detected resulting in incomplete transmissions 2 3 Keybus Operation and Wiring The Keybus...

Page 9: ...les are supervised upon installation Supervision is enabled at all times so that the panel can indi cate a trouble if a module is removed from the system To check on which modules are currently connec...

Page 10: ...one input to which a device such as a door contact can be connected This eliminates the need to run wires back to the control panel for every device To install the keypad open the keypad plastic by re...

Page 11: ...ing Stay arming please see section 3 5 Function Keys on page 10 3 3 Automatic Arming The system can be programmed to Auto Arm at a specific time every day if it is in the disarmed condition In order f...

Page 12: ...odule being powered by a PC5204 you must also remove and then restore power to the PC5204 and any connected modules This ensures that any troubles present on the module are correctly logged and or ann...

Page 13: ...ult These settings can be changed Access Code Attributes There are three access code attributes which can be pro grammed for each code To program each attribute enter 5 Master Code 9 to enter the attr...

Page 14: ...the panel will ignore only one activation of a Delay zone When the Delay zone is secured the panel will end the two minute quick exit delay If a second Delay zone is tripped or if the zone is not res...

Page 15: ...anual NOTE This function key cannot be programmed for PC55XX LED keypads with software version 1 0 19 7 3 Command Output Option 3 A valid access code may need to be entered 20 For future use 21 7 4 Co...

Page 16: ...the key to exit the section Select that section again and re enter the information correctly NOTE There must be one digit in each box in the program ming section in order for the change to be valid 4...

Page 17: ...y pad When a programming section is entered the keypad will immediately display the first digit of information programmed in that section The keypad displays the information using a binary format acco...

Page 18: ...ry time expires no alarm will be generated 02 Delay 2 Zone The Delay 2 entry delay time can be set independently of Delay 1 in programming section 005 System Times 03 Instant Zone This zone type will...

Page 19: ...e trouble 23 Maintained Keyswitch Arm Zone When this zone is violated the system will arm When this zone is secured the system will disarm Tampers and faults will not arm disarm the system but only ac...

Page 20: ...in and search for a dial tone for 5 seconds d the panel will then dial regardless of the presence of dial tone If there is no initial handshake recognized within 40 seconds the panel will then hang up...

Page 21: ...ed to report events to the central station by sending the Reporting Code programmed for a par ticular event Reporting codes can be one or two digits and can use HEX digits A through F For a complete d...

Page 22: ...Section 361 to 368 The following is a description of each reporting format Pulse Formats Depending on which pulse format is selected the panel will communicate using the following specifications 3 1 3...

Page 23: ...e pager once Once the appro priate telephone number is dialed the panel will send the account number and Reporting Code followed by the key Hex C The panel has no way of confirming if the pager was ca...

Page 24: ...ted Call Up option is enabled the user can have the panel initiate a call to the downloading computer by pressing 6 Master Code 6 The Download Access Code and Panel Identifier Code are for security an...

Page 25: ...ed to indicate that an alarm has occurred before entering the premises The PGM attributes for this option programmed in Sections 141 to 154 differ from the standard selection of attributes Program whi...

Page 26: ...outputs PGM attributes return to their default settings when you change PGM output options Please see the programming worksheets for a list of the default settings for each PGM out put type Care shou...

Page 27: ...me expires Communication of the signal to central station is immediate If the A Key is pressed and held for two seconds the panel will sound the keypad beeps three times to verify activa tion The pane...

Page 28: ...al applications Bell Squawk on Entry Delay may be enabled The panel will squawk the alarm output once every second until the entry delay expires or the system is dis armed If the Bell Squawk During Au...

Page 29: ...estoral Reporting Codes Section 338 System Tampers Req Installer Reset Section 701 4 NOTE After enabling keypad tampers it is recommended to tamper and restore all keypads to ensure proper functioning...

Page 30: ...5 31 Installer s Lockout If Installer s Lockout is selected a hardware default cannot be performed If a software default is performed all program ming will restore to factory default If Installer s L...

Page 31: ...________________________________________________________________________________________________I Keypad 7 I_____________________________________________I I____________________________________________...

Page 32: ...Keypads must be installed to use 24 hour Buzzer zones 001 Zone 1 8 Definitions Section 5 2 Zone Programming on page 14 Default Default 01 I_______I_______I Zone 1 04 I_______I_______I Zone 5 03 I____...

Page 33: ...Status 05 System Armed Status 18 Stay Armed Status 06 Ready To Arm 19 Command Output 1 7 1 07 Keypad Buzzer Follow Mode 20 Command Output 2 7 2 08 Courtesy Pulse 21 Command Output 3 7 3 09 System Tro...

Page 34: ...Arm Disarm Bell Squawk disabled 5 17 23 OFF I________I 2 Bell Squawk During Auto Arm No Bell Squawk During Auto Arm 5 18 24 OFF I________I 3 Bell Squawk On Exit Delay No Bell Squawk On Exit Delay 5 1...

Page 35: ...Contact I D Partial Close Identifier is 5 Partial Close Identifier is 4 5 9 18 OFF I________I 5 8 For future use 020 Keypad Zone Assignments Section 2 11 Keypad Zones on page 6 NOTE Only one keypad m...

Page 36: ...ion 001 Attribute 1 2 3 4 5 6 7 8 ON Audible Steady Chime Bypass Force Swing Tx Delay Wireless Zn OFF Silent Pulsed No No No No No No Zone Type 00 Null Zone N N N N N N N N 01 Delay 1 Y Y Y Y N Y N N...

Page 37: ...1 11 I________I I________ I________ I________ I________ I________ I________ I________I 152 12 I________I I________ I________ I________ I________ I________ I________ I________I 153 13 I________I I_____...

Page 38: ...nd Telephone Number 32 Digits Section 5 7 Communicator Telephone Numbers on page 17 I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_...

Page 39: ..._____I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I 342 Code 25 Code 26 Code 27 Code 28 Code 29 Code 30 Code 31 Code 32 I_______I_______I I_______I...

Page 40: ..._____I General Zone Trouble Alarm I_______I_______I General Zone Trouble Restore I_______I_______I For future use 352 Test Transmission Reporting Codes Section 5 8 Communicator Reporting Codes on pg 1...

Page 41: ...5 23 030 I_______I_______I_______I AC Failure Communication Delay 001 255 minutes 5 8 17 003 I_______I_______I_______I TLM Trouble Delay No of checks required valid entries 003 255 5 12 22 030 I______...

Page 42: ...indow OFF I_______I 3 Call Back Enabled Call Back Disabled OFF I_______I 4 User initiated Call up Enabled User initiated Call up Disabled OFF I_______I 5 8 For future use 402 Downloading Computer s Te...

Page 43: ...line Test Transmission in minutes Land line Test Transmission in days 5 14 23 OFF I_______I 4 1600 Hz Handshake Standard Handshake 5 9 18 OFF I_______I 5 ID Tone enabled ID Tone disabled 5 5 16 OFF I_...

Page 44: ...BAD 3 Beeps Squawks 990 Installer Lockout Enable Section 5 31 Installer s Lockout on page 26 991 Installer Lockout Disable Section 5 31 Installer s Lockout on page 26 993 Restore LINKS2X50 Factory De...

Page 45: ...der Supervisory Alarm Rest panel loses restores supervisory transmission over the Keybus from enrolled PC5132 module or keypads with zone inputs A R 1 43 UA 00 UH 00 328 Cross Zone Police Code Alarm t...

Page 46: ...T 00 UJ 00 352 Periodic Test periodic system test transmission T 6 A2 RP 00 352 System Test 6 bell communications test T 6 A1 RX 00 352 LINKS Test LINKS test transmission T 6 A3 TX 00 353 Wireless Dev...

Page 47: ...one 5 I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I Default Zone 6 I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I Default...

Page 48: ...bled ON I_______I 2 A uxiliary Keys enabled A uxiliary Keys disabled ON I_______I 3 P anic Keys enabled P anic Keys disabled OFF I_______I 4 8 For future use 65 Fourth User Display Mask Default Option...

Page 49: ...Label Broadcast All LCD programming is done per keypad If more than one LCD keypad are present on the system and the PC5400 receives labels labels pro grammed at one keypad can be broadcast to all oth...

Page 50: ...46 NOTES...

Page 51: ...6 of the Telecommunications Act 1981 6 It is important that the installer verifies the correct operation of stored telephone numbers subsequent to their entry 7 The connection to this equipment consis...

Page 52: ...e 18 New PGM Output Type 26 Battery Test See 5 11 PGM Output Options on page 20 New Zone Types 27 Push to Set 28 24 Hr Bell Buzzer See 5 2 Zone Programming on page 14 New Options Troubles are Latching...

Reviews: