DSC Power608 Installation Manual Download Page 26

22

[22] [*][7][2] Command Output Option #4

These outputs are user-initiated by entering [*][7][1-4] at any
keypad. When any output is activated, three acknowledgment
beeps are sounded.

NOTES on Option [20]  [*][7][2]:

Press [*][7][2][Access Code, if required] to activate any out-
put programmed as one of PGM output option [03] or [20].
Traditionally, [*][7][2] has been reserved for resetting smoke
detectors. Smoke detectors should now be programmed as
output [03] “Sensor Reset”. 

NOTE:Only ONE of options [03] Sensor Reset and [20][*][7][2] 
Command Output Option #2 may be programmed on the same
system.

[23] Silent 24 Hour (PGM2 Only)

A Panic button may be placed on the PGM2 terminal for use
as a silent 24 hour Panic. The keypad will not indicate the
alarm in any way and the Bell will remain silent but the PGM2
Alarm reporting code will be sent to the central station. PGM
output option [23] will not activate other programmable out-
puts of any kind. This input does not follow Swinger Shutdown. 

[24] Audible 24 Hour (PGM2 Only)

A Panic button may be placed on the PGM2 Terminal for use
as an Audible 24 Hour Panic. When the button is pressed,
LCD keypads will indicate “System in Alarm”, the bell will
sound until the Bell Cut-off expires or until a valid access code
is entered, and the PGM2 Alarm reporting code will be sent to
the central station. PGM output option [24] will not activate
other programmable outputs except for outputs programmed
as [01]. This input does not follow Swinger Shutdown. 

[26] Battery Test (PGM1 only)

When the panel performs the 10-second battery check, the
Battery Test output will activate. You may use this output type
to switch a 20 ohm load across to test the battery for the 10
second battery check period. Connect a resistor between the
Bell+ and PGM1 terminals.

PGM Output Attributes

In addition to programming the output type, you must also
program the PGM output attributes for each output. 
PGM output options [09] “System Trouble” and [10] “System
Event” have their own unique set of attributes listed below the
description of each output type.
PGM output options [01], [03], [05]-[08], [11]-[26] have the
following attributes:

Attribute.... ON

OFF

[1] ....... Output Enabled

Disabled

[3] ....... True Output

Inverted Output

Attribute ON: the output energizes when activated
Attribute OFF: the output de-energizes when acti-
vated

[4] ....... Output Pulsed

Output ON/OFF

Attribute ON: the output will activate once for the
amount of time programmed in section [164]
when initiated by the user
Attribute OFF: the output will toggle ON or OFF
when initiated by the user. 
(Only applicable to options [19]-[22].)

[5] ....... Access Code Req.

No code Req.

Attribute ON: the output requires a code for acti-
vation.
Attribute OFF: no code required.
(only applicable to keypad-activated outputs)

PGM attributes return to their default settings when you
change PGM output options. Please see the programming
worksheets for a list of the default settings for each PGM out-
put type.
Care should be taken in selecting the normal and active states
of each PGM output to ensure that an undesirable output state
does not occur after a loss and restore of AC power.

NOTE: Attribute [3] must be ON (default) for PGM output
options [16], [23] and [24].

NOTE: If you program more than one PGM output as the same
output type (e.g. if PGM1 and PGM2 are both programmed as
[19] Command Output 1), the settings for output attributes [1],
[2] and [5] must be the same. This does not apply to outputs
programmed as types [09] and [10].

PGM Output Attributes . . . . . . . . . . . . . .  Section [141]-[142]

5.12 Telephone Line Monitor (TLM)

When the 

TLM Enable

 option is selected, the panel will super-

vise the telephone line and will indicate a trouble condition if
the telephone line is disconnected. 
If the TLM Enable option is ON, the panel will check the tele-
phone line every 10 seconds. If the telephone line voltage is
below 3V for the number of checks programmed in the 

TLM

Trouble Delay

 section, the panel will report a TLM trouble.

The default number of checks is 3. Enter a number from [003]
to [255] in the TLM Trouble Delay section to change the num-
ber of checks before the TLM trouble is reported. Program-
ming a delay means that a momentary interruption of the
telephone line will not cause a trouble condition.
If the 

TLM Trouble Beeps When Armed

 option is enabled,

the panel will indicate a TLM trouble at the keypad while the
system is armed. To activate the bell output in the case of a
TLM trouble while the system is armed, the 

TLM Audible

(Bell) When Armed

 option must be selected.

When the trouble condition is restored, the panel can send a
TLM Restoral reporting code. Any events which occur while
the telephone line is down will also be communicated.
If the LINKS2X50 is being used, the panel can be pro-
grammed to report a TLM Trouble Reporting Code.

TLM Enable/Disable . . . . . . . . . . . . . . . . . . Section [015]: [7] 
TLM Trouble Beeps When Armed or 
TLM Audible (Bell) When Armed  . . . . . . . . Section [015]: [8] 
TLM Trouble Reporting Code . . . . . . . . . . . . . .  Section [349] 
TLM Restoral Reporting Code  . . . . . . . . . . . . .  Section [350]
TLM Trouble Delay  . . . . . . . . . . . . . . . . . . . . . .  Section [370]

5.13 Bell

If you program the 

Bell Delay 

timer, after a zone triggers an

audible burglary alarm, the panel will delay sounding the bell
for the programmed amount of time (000-255 minutes). If a
user enters an access code during this time period, the panel
will not activate the bell. 

NOTE:The Bell Delay timer will also delay any PGM outputs
that follow the main bell.

The bell will silence after the number of minutes programmed
for the

 Bell Cut-off

 time have passed. 

The panel supervises the Bell output. If an open condition is
detected, the panel will immediately indicate a trouble condi-
tion by beeping the keypad twice every 10 seconds to alert

Summary of Contents for Power608

Page 1: ...manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be carefully read PC5008...

Page 2: ...ces or passing traffic Audible warning devices however loud may not be heard by a hearing impaired person Telephone Lines If telephone lines are used to transmit alarms they may be out of service or b...

Page 3: ...5 Program Descriptions 14 5 1 Programming Security Codes 14 5 2 Zone Programming 14 5 3 Zone Attributes 15 5 4 Assigning Keypad Zones 16 5 5 Communicator Dialing 16 5 6 Communicator Account Numbers 17...

Page 4: ...ii PC5008 Wiring Diagram...

Page 5: ...t in piezoelectric buzzer Digital Communicator Specifications Supports major communication formats including SIA and Contact ID Event initiated personal paging Three programmable telephone numbers Two...

Page 6: ...the PC5928 Audio Interface Module PC5921 EXT Door Box Audio Station Used in conjunction with the PC5928 Audio Interface Module PC5921 EXT R Door Box Audio Station Used in conjunction with the PC5928...

Page 7: ...out the Programming Worksheets completely before attempt ing to program the system Step 10 Testing the System Test the panel thoroughly to ensure that all features and func tions are operating as pro...

Page 8: ...These lines may incorporate a voice filter which dis connects the line if anything other than fax signals are detected resulting in incomplete transmissions 2 3 Keybus Operation and Wiring The Keybus...

Page 9: ...les are supervised upon installation Supervision is enabled at all times so that the panel can indi cate a trouble if a module is removed from the system To check on which modules are currently connec...

Page 10: ...one input to which a device such as a door contact can be connected This eliminates the need to run wires back to the control panel for every device To install the keypad open the keypad plastic by re...

Page 11: ...ing Stay arming please see section 3 5 Function Keys on page 10 3 3 Automatic Arming The system can be programmed to Auto Arm at a specific time every day if it is in the disarmed condition In order f...

Page 12: ...odule being powered by a PC5204 you must also remove and then restore power to the PC5204 and any connected modules This ensures that any troubles present on the module are correctly logged and or ann...

Page 13: ...ult These settings can be changed Access Code Attributes There are three access code attributes which can be pro grammed for each code To program each attribute enter 5 Master Code 9 to enter the attr...

Page 14: ...the panel will ignore only one activation of a Delay zone When the Delay zone is secured the panel will end the two minute quick exit delay If a second Delay zone is tripped or if the zone is not res...

Page 15: ...anual NOTE This function key cannot be programmed for PC55XX LED keypads with software version 1 0 19 7 3 Command Output Option 3 A valid access code may need to be entered 20 For future use 21 7 4 Co...

Page 16: ...the key to exit the section Select that section again and re enter the information correctly NOTE There must be one digit in each box in the program ming section in order for the change to be valid 4...

Page 17: ...y pad When a programming section is entered the keypad will immediately display the first digit of information programmed in that section The keypad displays the information using a binary format acco...

Page 18: ...ry time expires no alarm will be generated 02 Delay 2 Zone The Delay 2 entry delay time can be set independently of Delay 1 in programming section 005 System Times 03 Instant Zone This zone type will...

Page 19: ...e trouble 23 Maintained Keyswitch Arm Zone When this zone is violated the system will arm When this zone is secured the system will disarm Tampers and faults will not arm disarm the system but only ac...

Page 20: ...in and search for a dial tone for 5 seconds d the panel will then dial regardless of the presence of dial tone If there is no initial handshake recognized within 40 seconds the panel will then hang up...

Page 21: ...ed to report events to the central station by sending the Reporting Code programmed for a par ticular event Reporting codes can be one or two digits and can use HEX digits A through F For a complete d...

Page 22: ...Section 361 to 368 The following is a description of each reporting format Pulse Formats Depending on which pulse format is selected the panel will communicate using the following specifications 3 1 3...

Page 23: ...e pager once Once the appro priate telephone number is dialed the panel will send the account number and Reporting Code followed by the key Hex C The panel has no way of confirming if the pager was ca...

Page 24: ...ted Call Up option is enabled the user can have the panel initiate a call to the downloading computer by pressing 6 Master Code 6 The Download Access Code and Panel Identifier Code are for security an...

Page 25: ...ed to indicate that an alarm has occurred before entering the premises The PGM attributes for this option programmed in Sections 141 to 154 differ from the standard selection of attributes Program whi...

Page 26: ...outputs PGM attributes return to their default settings when you change PGM output options Please see the programming worksheets for a list of the default settings for each PGM out put type Care shou...

Page 27: ...me expires Communication of the signal to central station is immediate If the A Key is pressed and held for two seconds the panel will sound the keypad beeps three times to verify activa tion The pane...

Page 28: ...al applications Bell Squawk on Entry Delay may be enabled The panel will squawk the alarm output once every second until the entry delay expires or the system is dis armed If the Bell Squawk During Au...

Page 29: ...estoral Reporting Codes Section 338 System Tampers Req Installer Reset Section 701 4 NOTE After enabling keypad tampers it is recommended to tamper and restore all keypads to ensure proper functioning...

Page 30: ...5 31 Installer s Lockout If Installer s Lockout is selected a hardware default cannot be performed If a software default is performed all program ming will restore to factory default If Installer s L...

Page 31: ...________________________________________________________________________________________________I Keypad 7 I_____________________________________________I I____________________________________________...

Page 32: ...Keypads must be installed to use 24 hour Buzzer zones 001 Zone 1 8 Definitions Section 5 2 Zone Programming on page 14 Default Default 01 I_______I_______I Zone 1 04 I_______I_______I Zone 5 03 I____...

Page 33: ...Status 05 System Armed Status 18 Stay Armed Status 06 Ready To Arm 19 Command Output 1 7 1 07 Keypad Buzzer Follow Mode 20 Command Output 2 7 2 08 Courtesy Pulse 21 Command Output 3 7 3 09 System Tro...

Page 34: ...Arm Disarm Bell Squawk disabled 5 17 23 OFF I________I 2 Bell Squawk During Auto Arm No Bell Squawk During Auto Arm 5 18 24 OFF I________I 3 Bell Squawk On Exit Delay No Bell Squawk On Exit Delay 5 1...

Page 35: ...Contact I D Partial Close Identifier is 5 Partial Close Identifier is 4 5 9 18 OFF I________I 5 8 For future use 020 Keypad Zone Assignments Section 2 11 Keypad Zones on page 6 NOTE Only one keypad m...

Page 36: ...ion 001 Attribute 1 2 3 4 5 6 7 8 ON Audible Steady Chime Bypass Force Swing Tx Delay Wireless Zn OFF Silent Pulsed No No No No No No Zone Type 00 Null Zone N N N N N N N N 01 Delay 1 Y Y Y Y N Y N N...

Page 37: ...1 11 I________I I________ I________ I________ I________ I________ I________ I________I 152 12 I________I I________ I________ I________ I________ I________ I________ I________I 153 13 I________I I_____...

Page 38: ...nd Telephone Number 32 Digits Section 5 7 Communicator Telephone Numbers on page 17 I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_...

Page 39: ..._____I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I 342 Code 25 Code 26 Code 27 Code 28 Code 29 Code 30 Code 31 Code 32 I_______I_______I I_______I...

Page 40: ..._____I General Zone Trouble Alarm I_______I_______I General Zone Trouble Restore I_______I_______I For future use 352 Test Transmission Reporting Codes Section 5 8 Communicator Reporting Codes on pg 1...

Page 41: ...5 23 030 I_______I_______I_______I AC Failure Communication Delay 001 255 minutes 5 8 17 003 I_______I_______I_______I TLM Trouble Delay No of checks required valid entries 003 255 5 12 22 030 I______...

Page 42: ...indow OFF I_______I 3 Call Back Enabled Call Back Disabled OFF I_______I 4 User initiated Call up Enabled User initiated Call up Disabled OFF I_______I 5 8 For future use 402 Downloading Computer s Te...

Page 43: ...line Test Transmission in minutes Land line Test Transmission in days 5 14 23 OFF I_______I 4 1600 Hz Handshake Standard Handshake 5 9 18 OFF I_______I 5 ID Tone enabled ID Tone disabled 5 5 16 OFF I_...

Page 44: ...BAD 3 Beeps Squawks 990 Installer Lockout Enable Section 5 31 Installer s Lockout on page 26 991 Installer Lockout Disable Section 5 31 Installer s Lockout on page 26 993 Restore LINKS2X50 Factory De...

Page 45: ...der Supervisory Alarm Rest panel loses restores supervisory transmission over the Keybus from enrolled PC5132 module or keypads with zone inputs A R 1 43 UA 00 UH 00 328 Cross Zone Police Code Alarm t...

Page 46: ...T 00 UJ 00 352 Periodic Test periodic system test transmission T 6 A2 RP 00 352 System Test 6 bell communications test T 6 A1 RX 00 352 LINKS Test LINKS test transmission T 6 A3 TX 00 353 Wireless Dev...

Page 47: ...one 5 I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I Default Zone 6 I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I Default...

Page 48: ...bled ON I_______I 2 A uxiliary Keys enabled A uxiliary Keys disabled ON I_______I 3 P anic Keys enabled P anic Keys disabled OFF I_______I 4 8 For future use 65 Fourth User Display Mask Default Option...

Page 49: ...Label Broadcast All LCD programming is done per keypad If more than one LCD keypad are present on the system and the PC5400 receives labels labels pro grammed at one keypad can be broadcast to all oth...

Page 50: ...46 NOTES...

Page 51: ...6 of the Telecommunications Act 1981 6 It is important that the installer verifies the correct operation of stored telephone numbers subsequent to their entry 7 The connection to this equipment consis...

Page 52: ...e 18 New PGM Output Type 26 Battery Test See 5 11 PGM Output Options on page 20 New Zone Types 27 Push to Set 28 24 Hr Bell Buzzer See 5 2 Zone Programming on page 14 New Options Troubles are Latching...

Reviews: