5 . 6   C o m m u n i c a t o r   –   A c c o u n t   N u m b e r s

17

5.6

Communicator – Account Numbers

The account number is used by the central station to distin-
guish between panels. There are two account numbers pro-
grammable for the PC5008.

First Account Code (4 digits) . . . . . . . . . . . . . .  Section [310]
Second Account Code (4 digits) . . . . . . . . . . .  Section [311]

5.7

Communicator – Telephone Numbers

The panel can use three different telephone numbers for com-
municating with the central station. The 

First Telephone

Number

 is the primary number, the 

Second Telephone Num-

ber

 is the secondary number and the 

Third Telephone Num-

ber

 will back up the First telephone number if enabled.

NOTE: The Third Telephone Number will NOT back up the
Second Telephone Number.

NOTE: If you enter a telephone number section (sections [301]
- [303]) at an LED keypad, pressing [#] will delete the pro-
grammed telephone number and change all the digits to [F].

If the 

Alternate Dial

 option is enabled, the panel will alternate

between the first and third telephone numbers when attempt-
ing to call the central station. If the option is disabled, the
panel will only attempt to call the Third telephone number after
failing to communicate with the first telephone number.

NOTE: To use the Third Telephone Number, you must enable it
in section [380], option [5], and program it in section [303].

Telephone numbers can be up to 32 digits. This allows you to
add special digits if required. To program the telephone number,
enter the numbers 0 through 9 as required. The following is a list
of programmable HEX digits and the functions they perform:
HEX (B) - simulates the [*] key on a touch tone telephone
HEX (C) - simulates the [#] key on a touch tone telephone
HEX (D) - forces the panel to search for dial tone
HEX (E) - forces the panel to pause for 2 seconds
HEX (F) - marks the end of the telephone number 

Two-way Voice Monitoring

The PC5928 module has built-in two-way voice for central sta-
tion monitoring. The central station can select the audio sta-
tion, listen/talk, extend on-line time and hang up. The 

Listen-

In

 feature can be enabled separately for telephone numbers

1/3 and 2.

NOTE:The first digit of all telephone numbers must be the HEX
digit ‘D’ for dial tone search, or HEX digit ‘E’ for a two-second
pause.

First Telephone Number . . . . . . . . . . . . . . . . . .  Section [301] 
Second Telephone Number . . . . . . . . . . . . . . .  Section [302] 
Third Telephone Number . . . . . . . . . . . . . . . . .  Section [303] 
Third Telephone Number Enable . . . . . . . .  Section [380]: [5] 
Alternate Dial  . . . . . . . . . . . . . . . . . . . . . . .  Section [380]: [6]
Telephone # 1 & 3 Listen-In Enable . . . . . .  Section [381]: [5]
Telephone # 2 Listen-In Enable  . . . . . . . . .  Section [381]: [6]

5.8

Communicator – Reporting Codes

The panel can be programmed to report events to the central
station by sending the Reporting Code programmed for a par-
ticular event.
Reporting codes can be one or two digits and can use HEX
digits (A through F). For a complete description of reporting

codes which can be programmed and lists of automatic Con-
tact ID and SIA format codes, please see Appendix A.

NOTE:Do not use the digit C in a reporting code when using 
Pager Format. In most cases, the digit C will be interpreted as
a [#] which will terminate the page before it has finished.

Reporting Codes . . . . . . . . . . . . . . . . . Section [320] to [353]

Cross Zone Police Reporting Code

The 

Cross Zone Police Code Alarm

 will be sent when two

different alarms occur during any armed-to-armed period.
When an alarm occurs while the panel is armed and a second
alarm occurs on a different zone during the same armed
period, or after the system is disarmed, this code will be sent.
All zone types contribute to this alarm. The cross zone police
code will be transmitted immediately unless either or both
zones have the Transmission Delay attribute enabled. If so,
the code will be delayed for the programmed transmission
delay time.

Cross Zone Police Code Alarm   . . . . . . . . . . . . Section [328]

Zone Restorals

If the 

Restoral on Bell Time-out

 option is selected, the panel

will send the 

Zone Restoral Reporting Code

 for the zone if

the bell cut-off time has expired and the zone is secured. If the
zone is not secured when the bell cut-off time expires, the
panel will send the restoral immediately once the zone is
secured, or when the system is disarmed. If the Restoral on
Bell Time-out option is not selected, the panel will immediately
send the Zone Restoral Reporting Code when the zone is
secured, regardless of whether or not the alarm output is
active.

NOTE:24 Hour type zones will report the restoral immediately 
when the zone is secured.

Restoral on Bell Time-out. . . . . . . . . . . . . . .Section [380]: [2]

Closings (Arming Codes)

If the 

Closing Confirmation

 option is enabled, once the exit

delay expires, the keypad will sound a series of eight beeps to
confirm to the user that the closing code was sent and
received by the central station.
The panel identifies which zones are bypassed on a Partial
Closing. To do this, the panel will send the partial closing
reporting code, and then the alarm restore reporting code(s)
for the zone(s) which are bypassed.
For example, if a panel is armed with Access Code 40 with
Zones 3 and 5 bypassed, the panel will transmit:

Partial Closing
Alarm Restore Zone 3
Alarm Restore Zone 5
Closing By User Code 40

The panel will follow the 

Alarm Restore Call Direction

options programming.

NOTE:This feature does not apply to the SIA format, which
uses CG-ZZ to identify zones for Partial Close.

NOTE:The LINKS2X50 does not communicate Alarm Restore
events. 

Closing Confirmation . . . . . . . . . . . . . . . . . .Section [381]: [4]

Summary of Contents for Power608

Page 1: ...manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be carefully read PC5008...

Page 2: ...ces or passing traffic Audible warning devices however loud may not be heard by a hearing impaired person Telephone Lines If telephone lines are used to transmit alarms they may be out of service or b...

Page 3: ...5 Program Descriptions 14 5 1 Programming Security Codes 14 5 2 Zone Programming 14 5 3 Zone Attributes 15 5 4 Assigning Keypad Zones 16 5 5 Communicator Dialing 16 5 6 Communicator Account Numbers 17...

Page 4: ...ii PC5008 Wiring Diagram...

Page 5: ...t in piezoelectric buzzer Digital Communicator Specifications Supports major communication formats including SIA and Contact ID Event initiated personal paging Three programmable telephone numbers Two...

Page 6: ...the PC5928 Audio Interface Module PC5921 EXT Door Box Audio Station Used in conjunction with the PC5928 Audio Interface Module PC5921 EXT R Door Box Audio Station Used in conjunction with the PC5928...

Page 7: ...out the Programming Worksheets completely before attempt ing to program the system Step 10 Testing the System Test the panel thoroughly to ensure that all features and func tions are operating as pro...

Page 8: ...These lines may incorporate a voice filter which dis connects the line if anything other than fax signals are detected resulting in incomplete transmissions 2 3 Keybus Operation and Wiring The Keybus...

Page 9: ...les are supervised upon installation Supervision is enabled at all times so that the panel can indi cate a trouble if a module is removed from the system To check on which modules are currently connec...

Page 10: ...one input to which a device such as a door contact can be connected This eliminates the need to run wires back to the control panel for every device To install the keypad open the keypad plastic by re...

Page 11: ...ing Stay arming please see section 3 5 Function Keys on page 10 3 3 Automatic Arming The system can be programmed to Auto Arm at a specific time every day if it is in the disarmed condition In order f...

Page 12: ...odule being powered by a PC5204 you must also remove and then restore power to the PC5204 and any connected modules This ensures that any troubles present on the module are correctly logged and or ann...

Page 13: ...ult These settings can be changed Access Code Attributes There are three access code attributes which can be pro grammed for each code To program each attribute enter 5 Master Code 9 to enter the attr...

Page 14: ...the panel will ignore only one activation of a Delay zone When the Delay zone is secured the panel will end the two minute quick exit delay If a second Delay zone is tripped or if the zone is not res...

Page 15: ...anual NOTE This function key cannot be programmed for PC55XX LED keypads with software version 1 0 19 7 3 Command Output Option 3 A valid access code may need to be entered 20 For future use 21 7 4 Co...

Page 16: ...the key to exit the section Select that section again and re enter the information correctly NOTE There must be one digit in each box in the program ming section in order for the change to be valid 4...

Page 17: ...y pad When a programming section is entered the keypad will immediately display the first digit of information programmed in that section The keypad displays the information using a binary format acco...

Page 18: ...ry time expires no alarm will be generated 02 Delay 2 Zone The Delay 2 entry delay time can be set independently of Delay 1 in programming section 005 System Times 03 Instant Zone This zone type will...

Page 19: ...e trouble 23 Maintained Keyswitch Arm Zone When this zone is violated the system will arm When this zone is secured the system will disarm Tampers and faults will not arm disarm the system but only ac...

Page 20: ...in and search for a dial tone for 5 seconds d the panel will then dial regardless of the presence of dial tone If there is no initial handshake recognized within 40 seconds the panel will then hang up...

Page 21: ...ed to report events to the central station by sending the Reporting Code programmed for a par ticular event Reporting codes can be one or two digits and can use HEX digits A through F For a complete d...

Page 22: ...Section 361 to 368 The following is a description of each reporting format Pulse Formats Depending on which pulse format is selected the panel will communicate using the following specifications 3 1 3...

Page 23: ...e pager once Once the appro priate telephone number is dialed the panel will send the account number and Reporting Code followed by the key Hex C The panel has no way of confirming if the pager was ca...

Page 24: ...ted Call Up option is enabled the user can have the panel initiate a call to the downloading computer by pressing 6 Master Code 6 The Download Access Code and Panel Identifier Code are for security an...

Page 25: ...ed to indicate that an alarm has occurred before entering the premises The PGM attributes for this option programmed in Sections 141 to 154 differ from the standard selection of attributes Program whi...

Page 26: ...outputs PGM attributes return to their default settings when you change PGM output options Please see the programming worksheets for a list of the default settings for each PGM out put type Care shou...

Page 27: ...me expires Communication of the signal to central station is immediate If the A Key is pressed and held for two seconds the panel will sound the keypad beeps three times to verify activa tion The pane...

Page 28: ...al applications Bell Squawk on Entry Delay may be enabled The panel will squawk the alarm output once every second until the entry delay expires or the system is dis armed If the Bell Squawk During Au...

Page 29: ...estoral Reporting Codes Section 338 System Tampers Req Installer Reset Section 701 4 NOTE After enabling keypad tampers it is recommended to tamper and restore all keypads to ensure proper functioning...

Page 30: ...5 31 Installer s Lockout If Installer s Lockout is selected a hardware default cannot be performed If a software default is performed all program ming will restore to factory default If Installer s L...

Page 31: ...________________________________________________________________________________________________I Keypad 7 I_____________________________________________I I____________________________________________...

Page 32: ...Keypads must be installed to use 24 hour Buzzer zones 001 Zone 1 8 Definitions Section 5 2 Zone Programming on page 14 Default Default 01 I_______I_______I Zone 1 04 I_______I_______I Zone 5 03 I____...

Page 33: ...Status 05 System Armed Status 18 Stay Armed Status 06 Ready To Arm 19 Command Output 1 7 1 07 Keypad Buzzer Follow Mode 20 Command Output 2 7 2 08 Courtesy Pulse 21 Command Output 3 7 3 09 System Tro...

Page 34: ...Arm Disarm Bell Squawk disabled 5 17 23 OFF I________I 2 Bell Squawk During Auto Arm No Bell Squawk During Auto Arm 5 18 24 OFF I________I 3 Bell Squawk On Exit Delay No Bell Squawk On Exit Delay 5 1...

Page 35: ...Contact I D Partial Close Identifier is 5 Partial Close Identifier is 4 5 9 18 OFF I________I 5 8 For future use 020 Keypad Zone Assignments Section 2 11 Keypad Zones on page 6 NOTE Only one keypad m...

Page 36: ...ion 001 Attribute 1 2 3 4 5 6 7 8 ON Audible Steady Chime Bypass Force Swing Tx Delay Wireless Zn OFF Silent Pulsed No No No No No No Zone Type 00 Null Zone N N N N N N N N 01 Delay 1 Y Y Y Y N Y N N...

Page 37: ...1 11 I________I I________ I________ I________ I________ I________ I________ I________I 152 12 I________I I________ I________ I________ I________ I________ I________ I________I 153 13 I________I I_____...

Page 38: ...nd Telephone Number 32 Digits Section 5 7 Communicator Telephone Numbers on page 17 I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_...

Page 39: ..._____I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I 342 Code 25 Code 26 Code 27 Code 28 Code 29 Code 30 Code 31 Code 32 I_______I_______I I_______I...

Page 40: ..._____I General Zone Trouble Alarm I_______I_______I General Zone Trouble Restore I_______I_______I For future use 352 Test Transmission Reporting Codes Section 5 8 Communicator Reporting Codes on pg 1...

Page 41: ...5 23 030 I_______I_______I_______I AC Failure Communication Delay 001 255 minutes 5 8 17 003 I_______I_______I_______I TLM Trouble Delay No of checks required valid entries 003 255 5 12 22 030 I______...

Page 42: ...indow OFF I_______I 3 Call Back Enabled Call Back Disabled OFF I_______I 4 User initiated Call up Enabled User initiated Call up Disabled OFF I_______I 5 8 For future use 402 Downloading Computer s Te...

Page 43: ...line Test Transmission in minutes Land line Test Transmission in days 5 14 23 OFF I_______I 4 1600 Hz Handshake Standard Handshake 5 9 18 OFF I_______I 5 ID Tone enabled ID Tone disabled 5 5 16 OFF I_...

Page 44: ...BAD 3 Beeps Squawks 990 Installer Lockout Enable Section 5 31 Installer s Lockout on page 26 991 Installer Lockout Disable Section 5 31 Installer s Lockout on page 26 993 Restore LINKS2X50 Factory De...

Page 45: ...der Supervisory Alarm Rest panel loses restores supervisory transmission over the Keybus from enrolled PC5132 module or keypads with zone inputs A R 1 43 UA 00 UH 00 328 Cross Zone Police Code Alarm t...

Page 46: ...T 00 UJ 00 352 Periodic Test periodic system test transmission T 6 A2 RP 00 352 System Test 6 bell communications test T 6 A1 RX 00 352 LINKS Test LINKS test transmission T 6 A3 TX 00 353 Wireless Dev...

Page 47: ...one 5 I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I Default Zone 6 I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I Default...

Page 48: ...bled ON I_______I 2 A uxiliary Keys enabled A uxiliary Keys disabled ON I_______I 3 P anic Keys enabled P anic Keys disabled OFF I_______I 4 8 For future use 65 Fourth User Display Mask Default Option...

Page 49: ...Label Broadcast All LCD programming is done per keypad If more than one LCD keypad are present on the system and the PC5400 receives labels labels pro grammed at one keypad can be broadcast to all oth...

Page 50: ...46 NOTES...

Page 51: ...6 of the Telecommunications Act 1981 6 It is important that the installer verifies the correct operation of stored telephone numbers subsequent to their entry 7 The connection to this equipment consis...

Page 52: ...e 18 New PGM Output Type 26 Battery Test See 5 11 PGM Output Options on page 20 New Zone Types 27 Push to Set 28 24 Hr Bell Buzzer See 5 2 Zone Programming on page 14 New Options Troubles are Latching...

Reviews: