Ethernet Receiver 1 Options
3G Alarm Communicator Installation Manual
18
Table 10: Panel Tamper Alarm Restore
E
THERNET
R
ECEIVER
1 O
PTIONS
[101] Ethernet Receiver 1 Account Code
Default (0000000000)
The account code is used by the central station to distinguish between transmitters. This account code is used when transmitting heart-
beat signals to the central station receiver. Signals received from the Panel will use the control panel account number. Valid range:
000000000
1
-FFFFFFFFF
E
. Programming all
0
or all
F
will cause a Module Configuration Trouble.
NOTE:
If Ethernet Receiver 1 and Cellular Receiver 1 are programmed as the same receiver (IP and port number are identical), Ether-
net Receiver 1 account code will be used.
[102] Ethernet Receiver 1 DNIS
Default (000000)
The Dialled Number Information Service (DNIS) is used in addition to the Account Code to identify the Communicator module at the
central station. Valid range: 000000 -
0
99999. Value is entered as a leading 0 followed by the 5 digit DNIS. Format is Binary Coded
Decimal (BCD).
NOTE:
Each Ethernet/Cellular receiver must be programmed with a unique DNIS.
[103] Ethernet Receiver 1 Address
Default (127.000.000.001)
The default address enables the Communicator to operate in
Unattended Mode
.
Unattended Mode is used when a receiver is not available and the unit is required to perform DLS sessions. Typically used where the
customer programs the control panel daily due to access control and still wants to receive alarms without buying extra hardware
(receiver) or software.
NOTE:
When a valid IP address has been programmed, Ethernet Receiver 1 is enabled and will communicate events over the Ethernet
channel.
Ethernet Receiver 1 and Cellular Receiver 1 may be configured to communicate to the same central station receiver. To configure the
device to operate using this Common Receiver Mode functionality, program Ethernet Receiver 1 and Cellular Receiver 1, IP address
and port number with identical values.
NOTE:
When operating in Common Receiver Mode, Ethernet Receiver 1 account code will be used for Ethernet and Cellular.
[104] Ethernet Receiver 1 Remote Port
Default (0BF5/3061)
This Section determines the remote port of Ethernet receiver 1. Valid range: 0000 - FFFF.
[105] Ethernet Receiver 1 Local Port
Default (0BF4/3060)
Use this Section to set the value of the local outgoing port. Set the value of this port when your installation is located behind a firewall
and must be assigned a particular port number as determined by your central station
system administrator. Valid range: 0000 - FFFF.[106] Ethernet Receiver 1 Domain Name
[106] Ethernet Receiver 1 Domain Name
Default ( )
Enter the Domain Name as 32 ASCII characters.
Programming this Section is
not
permitted on a UL/ULC listed system.
E
THERNET
R
ECEIVER
2 O
PTIONS
[111] Ethernet Receiver 2 Account Code
Default (0000000000)
The account code is used by the central station to distinguish between transmitters. The account code is used when transmitting heart-
beat signals to the central station receiver. Signals received from the control panel will use the control panel account number. Valid
range: 000000000
1
- FFFFFFFFF
E
. Programming all
0
or all
F
will cause a Module Configuration Trouble (yellow LED=12 flashes).
NOTE:
If both Ethernet Receiver 2 and Cellular Receiver 2 are the same receiver (IP and port number are identical), Ethernet Receiver
2 account will be used for Ethernet and Cellular.
Event
SIA
Identifier
SIA
Reporting
Code
Contact ID
Qualifier
Contact ID
Event Code
Contact ID
Reporting
Code
Contact ID
User/Zone
[033] Comm. FW Update
Begin
LB
00
1
9
03
002
[034] Comm. FW Update Suc-
cessful
LS
00
3
9
03
002
[035] Panel FW Update Begin
LB
00
1
9
03
003
[036] Panel FW Update Suc-
cessful
LS
00
3
9
03
003
[037] Panel FW Update Fail
LU
00
1
9
04
003